Fuel                     

Type

Inlet Pressure

Manifold Pressure

Desired Minimum Maximum

On Hi 

Fire

On Lo 

Fire

Natural

Gas

7" WC

5" WC

10.5" WC

3.5" WC 1.7" WC

LP Gas

11" WC 11" WC

13" WC

11" WC

5.4” WC

Gas Line Installation 

The Ravelle™ 42 gas fireplace must be connected to the gas line in ac-

cordance with local codes and/or the National Fuel Gas Code, ANSI Z223.1 

(In Canada, the current CAN/CSA  B149.1 installation code). The gas line 

should enter the fireplace on the left side (see diagrams on 

Pages 8 and 

9

)

. If the gas line enters the unit from the right side, the line will need to 

be disconnected to remove the fan. The fireplace comes with a flex line 

attached to the supply side of the gas valve. The fitting on the end of the 

flex line can receive a 1/2” female iron pipe coupling, a 3/8” male iron 

pipe, or a shut-off valve. There is sufficient room to locate the shut-off 

valve under the firebox at the end of this flex line, however, local codes 

may require the shut-off to be located on the exterior of the fireplace. After 

connecting the gas line, all joints in the line and connections at the valve 

should be checked for leaks before final positioning of the unit. Conduct a 

gas leakage test of the appliance piping and control system downstream 

of the shutoff valve in the supply line to the appliance.

Gas Pressure Requirements

A MAJOR CAUSE OF OPERATING PROBLEMS WITH GAS APPLI-

ANCES IS IMPROPER GAS PRESSURE!

The most important item to check during the initial installation 

and the first thing to check when operating problems occur is 

gas pressure! 

This fireplace will not function properly unless the required 

gas pressure is supplied. See the table on this page for gas 

pressure requirements.

Two pressure taps are provided on the fireplace’s valve to check gas 

pressures. To access the taps remove the two socket head screws to 

remove the valve control panel/heat shield. The taps are located below 

the on/off/pilot knob (see 

Figure 32

)

. The left tap is the inlet (supply) 

pressure side. To check inlet pressure (with the fireplace burning) insert 

a small flat bladed screwdriver into the tap and turn a half turn counter-

clockwise. Cover the tap with the line from a manometer and read the 

pressure. Close the tap gently but securely after completing the check. 

The manifold (outlet) tap is to the right of the inlet tap. To check manifold 

pressure (with the fireplace burning at the high burn setting) insert a 

small flat bladed screwdriver into the tap and turn a half turn counter-

clockwise. Cover the tap with the line from the manometer and check 

the pressure. Again close the tap gently but securely after completing 

the check. Check the taps for gas leaks with a gas leak test solution 

(retighten if necessary).

If the pressure is not sufficient, make sure the gas supply line is large 

enough, the supply regulator is properly adjusted and the total gas load 

for the residence does not exceed the amount supplied.

Propane tanks are at pressures that will cause damage to valve com-

ponents.  Verify that the tanks have step down regulators to reduce the 

pressure to safe levels.

LP and Natural Gas Supplies

Your  Ravelle  gas  fireplace  is  equipped  from  the  factory  for  use  with 
natural gas only as specified on the Safety / Listing label attached to the 
appliance. This appliance can only be operated using propane gas (LP) 
if a certified fuel conversion kit provided by Lennox Hearth Products is 
installed by a qualified service technician.  

Also check the orifice size on the label on the igniter bracket. It must be 
the correct size for the fuel and altitude.

Do not run propane tank dry.  Running the tank dry may cause a 

hazardous condition due to pressure drop in empty tank. 

Solid fuel is NOT to be used with this unit.

Note:

  

The appliance and its individual shut-off valve must be disconnected 

from the gas supply piping system during any pressure testing of that 
system at test pressures in excess of 1/2 psig. The appliance must be 
isolated  from  the  gas  supply  piping  system  by  closing  its  individual 
manual shut-off valve during any pressure testing of the gas supply piping 
system at test pressures equal to or less than 1/2 psig. Check with your 
gas supplier or plumber.

Inlet (Supply) 

Pressure Tap

Figure 32

The Manifold

(Outlet) Tap

TP/TH

TH

TP

SIT Millivolt Gas Valve

These appliances must be isolated from the gas supply piping system 

(by closing their individual manual shut-off valve) during any pressure 

testing of the gas supply piping system at test pressures equal to or 

less than

 1/2 psig (3.5 kPa).

These appliances and their individual shut-off valves must be discon-

nected from the gas supply piping system during any pressure testing 

of that system at pressures 

greater than

 1/2 psig (3.5 kPa).

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

Содержание Ravelle 42

Страница 1: ...vous trouvez Appelez imm diatement votre fournisseur de gaz depuis un voisin Suivez les instructions du fournis seur Si vous ne pouvez rejoindre le fournisseur de gaz appelez le service des incindies...

Страница 2: ...nsiderations 16 Horizontal Vent Installation 17 Vertical Vent Installation 17 Flue Restrictors 18 Vertical Vent Termination Clearances 18 Horizontal Terminations 19 Vertical Terminations 19 Horizontal...

Страница 3: ...ler service agency or the gas supplier WARNING Failure to comply with these installation instructions will result in an improperly installed and operating appliance voiding its warranty Any change to...

Страница 4: ...not be connected to a chimney or flue serving a separate solid fuel burning appliance These appliances are vented gas appliances Do not burn wood or other material in these appliances This appliance i...

Страница 5: ...l building department for requirements in your area SMOKE DETECTORS Certification Gas appliances must be tested and certified by a nationally recognized testing and certification laboratory to ANSI Am...

Страница 6: ...cassette valve and pilot assembly or installing a conversionkit OnlyLennoxHearthProductsconversionkitscanbeusedto convert from NG to LP or LP to NG Contact your Lennox Hearth Products dealer for detai...

Страница 7: ...Mantel The drawing at the lower right shows the minimum distances from the base of the fireplace to combustible mantel and facing material Combustible materials may be placed above and within the sha...

Страница 8: ...the valve wThe electrical power supply wiring should be routed to the right rear of the unit Note The fireplace may be placed directly on wood or non combustible flooring but not on vinyl floor coveri...

Страница 9: ...756 20 3 4 527 47 3 4 1213 35 1 2 902 2 51 34 864 41 1041 38 1 4 972 30 762 43 1092 30 762 3 1 2 89 9 1 2 241 10 3 4 273 72 1 2 1842 6 7 8 175 18 3 16 462 32 5 16 821 3 1 2 89 5 127 6 1 4 159 2 1 4 5...

Страница 10: ...fireplace must be raised the thickness of that hearth extension less the 7 8 22 mm For example if a 2 7 8 73 mm thick cultured stone is to be placed on the floor to serve as the hearth extension then...

Страница 11: ...replace face see below Facing Installation Considerations Non combustible cement board such as Wonderboard Durock or Har dybacker must extend 10 254 mm above the 1 25 mm top reveal and a minimum of 3...

Страница 12: ...75098 Foundry 75035 and Classic Louver 75101 should be used while installing the facing material Templates for the various faces may be purchased from your Lennox Hearth Products dealer or a template...

Страница 13: ...e place face The acid wash will tarnish the face Consult your masonry installer Face Installation A number of different faces are available for the Ravelle 42 gas fire place however all the faces are...

Страница 14: ...red by the approved vent manufacturer Installation other than as instructed by Lennox Hearth Products and vent manufacturers instructions Vent Parts List Direct vent pipe Security Secure Vent may be u...

Страница 15: ...gh Wind 1250 Vinyl Siding Standoff Vent Parts List Vertical Direct vent pipe by Security or Simpson Dura Vent may be used with the Ravelle 42 gas fireplace Please see the lists below to verify the com...

Страница 16: ...orizontal runs of vent must be supported every three feet Wall straps are available for this purpose Pipe Sealing If Security Secure Vent pipe is used then sealant is required at only the first pipe j...

Страница 17: ...inations locations see the diagram on Page 20 9 Allowableclearancesfromtheventpipetocombustiblemateri als must be maintained See Page 7 for these clearances 10 Do not locate the termination cap where...

Страница 18: ...and 23 the burner flame appearance should be evaluated to determined if the flue restrictors need to be set to a different position to adjust for variables in your installation Light the appliance an...

Страница 19: ...of pipe does not exceed those shown below Use the restrictor positions indicated If the fireplace is vented with an elbow directly off the top of the flue collar and three to four feet of horizontal p...

Страница 20: ...ove meter regulator assembly 3 feet 91 cm within a height of 15 feet above the meter regulator assembly 3 feet 91 cm within a height of 15 feet above the meter regulator assembly I Clearance to servic...

Страница 21: ...g 2 on tab An air shield is provided for natural gas use only For LP conversions remove the air shield 5 Place Logs 3 4 and 5 on tab inserts Important Maintain a 1 4 6 4mm air space along the entire l...

Страница 22: ...ff at the electrical panel before any connections are made The loop of wire with the label attached E in Figure 29 may be cut and the wire leads from the wall mounted speed control connected to each e...

Страница 23: ...p is to the right of the inlet tap To check manifold pressure with the fireplace burning at the high burn setting insert a small flat bladed screwdriver into the tap and turn a half turn counter clock...

Страница 24: ...ing air is drawn from a distant room lowering the pressure in that room through the return air duct into the bottom of the fireplace The air then passes through the outer shell and heat exchanger of t...

Страница 25: ...nting Brackets Two White Headed Grille Screws Six Wire Nuts Sixteen Sheet Metal Screws One Wire Clamp The system draws heated air from the Ravelle 42 gas fireplace and moves it with the use of a 150 C...

Страница 26: ...the fan box Since the fan box body is wider than the portion that comes up through the floor an additional piece of floor ing F below should also be cut out for the fan box to slide through Save this...

Страница 27: ...ape at each joint 5 Secure the ducting to prevent sagging Wiring of the Forced Air System Disconnect the electrical supply to the fireplace at the electrical panel prior to wiring the forced air syste...

Страница 28: ...erentcolorsofcovers and knobs come with the kit Select the cover desired and fasten the speed control and cover to the box with the screws supplied Push the desired knob onto the shaft of the speed co...

Страница 29: ...ermostat mural voir Figure B et le cas ch ant sur le bo tier delat l commande FigureC Pouracheverl instal lationcorrectedecefoyer proc dezcommesuitavec les tiquettesadh sivesenlangues trang resfournie...

Страница 30: ...and don t try to repair it call a qualified service technician Force or attempted repair may result in a fire or explosion D DO NOT use this appliance if any part has been under water Immediately call...

Страница 31: ...ner gas is burning properly i e no floating lifting or flashback Adjust the primary air shutter s as required Check for proper main burner operation at both high and low flame PILOT ASSEMBLY Thermopil...

Страница 32: ...ed with a 200 CFM blower with a variable speed control and an automatic temperature activated on off snap switch Operation 1 After the fireplace warms up a heat activated switch will turn on the fan A...

Страница 33: ...osition when using the thermostat or remote control and set the thermostat or remote control to the lowest temperature when you wish to use the rocker switch only otherwise one may override the other...

Страница 34: ...ot air outlet vents for lint or other accumulations Never block or restrict vent openings obstruct flow of ventilation air or use vents other than those approved for use with this appliance o Check th...

Страница 35: ...er in place 5 Remove the labeled cover through which the valve control knobs protrude by removing the two allen head screws securing it and slide it off the valve knobs 6 Mark and disconnect wires on...

Страница 36: ...ht pilot If pilot lights turn off pilot and trigger the igniter again If pilot lights an intermittent gas air supply may be the problem if longer purge will not light check gap between electrode and p...

Страница 37: ...to NG Conversion Kit LP to NG ref form 775241M 75064 RAVL42 CK NG to LP Conversion Kit NG to LP ref form 775250M Misc 75259 NP RAVL30 42 Nail Plates 4 x 12 galvanized 75247 Reducer 8 6 5 8 Reducer 8 t...

Страница 38: ...AN BRNKL TUSCAN Brushed Nickel 75317 AI42 TUSCAN BKNKL TUSCAN Black Nickel Screen Kit ref form 775289M 75029 Screen Face double Door black 43 1 4 W x 31 7 8 H INSETS Required Includes 1 Top and 1 Bott...

Страница 39: ...CSA P 4 1 02 ET CGA 2 17 M91 CET APPAREIL DOIT TRE INSTALL CONFORM MENT AUX EXIGENCES DES CODES R GIONAUX ET DU CODE D INSTALLATION ANSI NFPA 54 DERNI RE DITION ETATS UNIS OU CAN CGA B149 1 DERNI RE...

Страница 40: ...Pour assistance ou information suppl mentaires contactez un installateur qualifi un agent de service ou un fournisseur de gaz Si vous op rez cet appareil sans qu il ne soit correctement raccord un con...

Страница 41: ...41 NOTES...

Страница 42: ...rts list Use only parts sup plied from the manufacturer Normally all parts should be ordered through your Lennox distributor or dealer Parts will be shipped at prevailing prices at time of order When...

Отзывы: