Vent Parts List - Horizontal

Direct vent pipe by Security™ or Simpson Dura-Vent may be used with 
the Ravelle™ 42 gas fireplace. Please see the lists below to verify the 
components  available  from  each  direct-vent  pipe  manufacturer.  All 
horizontally terminated venting of the Ravelle 42 gas fireplace uses 8” 
x 5” size vent pipe and all vertically terminated venting uses 6-5/8” x 4” 
size vent pipe. The flue collar on the fireplace is 8” x 5” in size. Therefore, 
when vertically terminating it is necessary to use a reducer - part number 
75247 (available from Lennox Hearth Products) - to make the transition 
from the 8” x 5” flue collar to the 6-5/8” x 4” pipe. Snorkel terminations 
are available for applications which may require vertical rise on the building 
exterior. The components listed below come in a galvanized finish. Most 
of the components are also available in a painted black finish. Add a “B” 
to the end of the part number when ordering if a black part is desired.

Security™ Secure Vent™ 8”x 5” Pipe 

Part Number 

Description

SV5L6 

6” Pipe Length

SV5L12 

12” Pipe Length

SV5L24 

24” Pipe Length 

SV5L36 

36” Pipe Length 

SV5L48 

48” Pipe Length 

SV5LA 

6” Pipe, Adjustable

SV5LA12 

12” Pipe, Adjustable

SV5E45 

45º Elbow

SV5E90 

90º Elbow

SV5RSM 

Wall Radiation Shield

SV5VS 

Vinyl Shield Protector

SV5BF 

Firestop

SV5CHC-1 

Horizontal Termination Cap

SV5STC14 

Snorkel Termination (14”) Cap

SV5STC36 

Snorkel Termination (36”) Cap

SV5BM 

 

 

Wall Band

Simpson Dura-Vent GS 8”x 5” Pipe

Part Number   

Description

1208 

6” Pipe Length

1207 

9”  Pipe Length

1206 

12” Pipe Length

1204 

24” Pipe Length

1203 

36” Pipe Length

1202 

8” Pipe Length

1211 

11” to 14-5/8” Pipe, Adjustable

1217 

17” to 24” Pipe, Adjustable

1290 

90° Elbow

1247 

Wall Thimble

1263 

Ceiling Firestop

1288 

Wall Strap

1281 

Snorkel Termination (36”)

1282 

Snorkel Termination (14”)

1284 

Horizontal Termination Cap

1285 

Horizontal Termination Cap (High Wind)

1250 

Vinyl Siding Standoff

Vent Parts List - Vertical

Direct vent pipe by Security or Simpson Dura-Vent may be used with 
the  Ravelle  42  gas  fireplace.  Please  see  the  lists  below  to  verify  the 
components  available  from  each  direct-vent  pipe  manufacturer.  All 
horizontally terminated venting of the Ravelle 42 gas fireplace uses 8” 
x 5” size vent pipe and all vertically terminated venting uses 6-5/8” x 4” 
size vent pipe. The flue collar on the fireplace is 8” x 5” in size. Therefore, 
when vertically terminating it is necessary to use a reducer - part number 
75247 (available from Lennox Hearth Products) - to make the transition 
from the 8” x 5” flue collar to the 6-5/8” x 4” pipe. Snorkel terminations 
are available for applications which may require vertical rise on the building 
exterior. The components listed below come in a galvanized finish. Most 
of the components are also available in a painted black finish. Add a “B” 
to the end of the part number when ordering if a black part is desired.

Security Secure Vent 6-5/8”x 4” Pipe 

Part Number 

 

Description

SV4L6   

 

 

6” Pipe Length

SV4L12   

 

 

12” Pipe Length

SV4L24   

 

 

24” Pipe Length 

SV4L36   

 

 

36” Pipe Length 

SV4L48   

 

 

48” Pipe Length 

SV4LA   

 

 

6” Pipe, Adjustable

SV4LA12  

 

 

12” Pipe, Adjustable

SV4FA   

 

 

Flashing, 1/12 to 176/12 Roof Pitch

SV4FB    

 

 

Flashing, 8/12 to 12/12 Roof Pitch

SV4RSM   

 

 

Wall Radiation Shield

SV4E46   

 

 

45° Elbow

SV4E90   

 

 

90° Elbow

SV4VS   

 

 

Vinyl Shield Protector

SV4FC   

 

 

Storm Collar

SV4CGV   

 

 

Vertical Termination Cap

SV4BF   

 

 

Firestop

SV4BM   

 

 

Wall Band

Part Available from Lennox Hearth Products Only:

75247 

 

 

 

8” x  5” to 6-5/8” x  4” Reducer

Simpson Dura-Vent GS 6-5/8” x 4” Pipe

Part Number   

 

Description

908   

 

 

 

6” Pipe Length

907   

 

 

 

9”  Pipe Length

906   

 

 

 

12” Pipe Length

904   

 

 

 

24” Pipe Length

903   

 

 

 

36” Pipe Length

902   

 

 

 

48” Pipe Length

911   

 

 

 

11” to 14-5/8” Pipe, Adjustable

912   

 

 

 

12” to 17” Pipe, Adjustable

917   

 

 

 

17” to 24” Pipe, Adjustable

942   

 

 

 

Wall Thimble

945   

 

 

 

45° Elbow

943   

 

 

 

Flashing, 0/12 to 6/12 Roof Pitch

943S 

 

 

 

Flashing, 7/12 to 12/12 Roof Pitch

953   

 

 

 

Storm Collar

963   

 

 

 

Ceiling Firestop

988   

 

 

 

Wall Strap

980   

 

 

 

Vertical Termination Cap

991   

 

 

 

Vertical Termination Cap (High Wind)

Содержание Ravelle 42

Страница 1: ...vous trouvez Appelez imm diatement votre fournisseur de gaz depuis un voisin Suivez les instructions du fournis seur Si vous ne pouvez rejoindre le fournisseur de gaz appelez le service des incindies...

Страница 2: ...nsiderations 16 Horizontal Vent Installation 17 Vertical Vent Installation 17 Flue Restrictors 18 Vertical Vent Termination Clearances 18 Horizontal Terminations 19 Vertical Terminations 19 Horizontal...

Страница 3: ...ler service agency or the gas supplier WARNING Failure to comply with these installation instructions will result in an improperly installed and operating appliance voiding its warranty Any change to...

Страница 4: ...not be connected to a chimney or flue serving a separate solid fuel burning appliance These appliances are vented gas appliances Do not burn wood or other material in these appliances This appliance i...

Страница 5: ...l building department for requirements in your area SMOKE DETECTORS Certification Gas appliances must be tested and certified by a nationally recognized testing and certification laboratory to ANSI Am...

Страница 6: ...cassette valve and pilot assembly or installing a conversionkit OnlyLennoxHearthProductsconversionkitscanbeusedto convert from NG to LP or LP to NG Contact your Lennox Hearth Products dealer for detai...

Страница 7: ...Mantel The drawing at the lower right shows the minimum distances from the base of the fireplace to combustible mantel and facing material Combustible materials may be placed above and within the sha...

Страница 8: ...the valve wThe electrical power supply wiring should be routed to the right rear of the unit Note The fireplace may be placed directly on wood or non combustible flooring but not on vinyl floor coveri...

Страница 9: ...756 20 3 4 527 47 3 4 1213 35 1 2 902 2 51 34 864 41 1041 38 1 4 972 30 762 43 1092 30 762 3 1 2 89 9 1 2 241 10 3 4 273 72 1 2 1842 6 7 8 175 18 3 16 462 32 5 16 821 3 1 2 89 5 127 6 1 4 159 2 1 4 5...

Страница 10: ...fireplace must be raised the thickness of that hearth extension less the 7 8 22 mm For example if a 2 7 8 73 mm thick cultured stone is to be placed on the floor to serve as the hearth extension then...

Страница 11: ...replace face see below Facing Installation Considerations Non combustible cement board such as Wonderboard Durock or Har dybacker must extend 10 254 mm above the 1 25 mm top reveal and a minimum of 3...

Страница 12: ...75098 Foundry 75035 and Classic Louver 75101 should be used while installing the facing material Templates for the various faces may be purchased from your Lennox Hearth Products dealer or a template...

Страница 13: ...e place face The acid wash will tarnish the face Consult your masonry installer Face Installation A number of different faces are available for the Ravelle 42 gas fire place however all the faces are...

Страница 14: ...red by the approved vent manufacturer Installation other than as instructed by Lennox Hearth Products and vent manufacturers instructions Vent Parts List Direct vent pipe Security Secure Vent may be u...

Страница 15: ...gh Wind 1250 Vinyl Siding Standoff Vent Parts List Vertical Direct vent pipe by Security or Simpson Dura Vent may be used with the Ravelle 42 gas fireplace Please see the lists below to verify the com...

Страница 16: ...orizontal runs of vent must be supported every three feet Wall straps are available for this purpose Pipe Sealing If Security Secure Vent pipe is used then sealant is required at only the first pipe j...

Страница 17: ...inations locations see the diagram on Page 20 9 Allowableclearancesfromtheventpipetocombustiblemateri als must be maintained See Page 7 for these clearances 10 Do not locate the termination cap where...

Страница 18: ...and 23 the burner flame appearance should be evaluated to determined if the flue restrictors need to be set to a different position to adjust for variables in your installation Light the appliance an...

Страница 19: ...of pipe does not exceed those shown below Use the restrictor positions indicated If the fireplace is vented with an elbow directly off the top of the flue collar and three to four feet of horizontal p...

Страница 20: ...ove meter regulator assembly 3 feet 91 cm within a height of 15 feet above the meter regulator assembly 3 feet 91 cm within a height of 15 feet above the meter regulator assembly I Clearance to servic...

Страница 21: ...g 2 on tab An air shield is provided for natural gas use only For LP conversions remove the air shield 5 Place Logs 3 4 and 5 on tab inserts Important Maintain a 1 4 6 4mm air space along the entire l...

Страница 22: ...ff at the electrical panel before any connections are made The loop of wire with the label attached E in Figure 29 may be cut and the wire leads from the wall mounted speed control connected to each e...

Страница 23: ...p is to the right of the inlet tap To check manifold pressure with the fireplace burning at the high burn setting insert a small flat bladed screwdriver into the tap and turn a half turn counter clock...

Страница 24: ...ing air is drawn from a distant room lowering the pressure in that room through the return air duct into the bottom of the fireplace The air then passes through the outer shell and heat exchanger of t...

Страница 25: ...nting Brackets Two White Headed Grille Screws Six Wire Nuts Sixteen Sheet Metal Screws One Wire Clamp The system draws heated air from the Ravelle 42 gas fireplace and moves it with the use of a 150 C...

Страница 26: ...the fan box Since the fan box body is wider than the portion that comes up through the floor an additional piece of floor ing F below should also be cut out for the fan box to slide through Save this...

Страница 27: ...ape at each joint 5 Secure the ducting to prevent sagging Wiring of the Forced Air System Disconnect the electrical supply to the fireplace at the electrical panel prior to wiring the forced air syste...

Страница 28: ...erentcolorsofcovers and knobs come with the kit Select the cover desired and fasten the speed control and cover to the box with the screws supplied Push the desired knob onto the shaft of the speed co...

Страница 29: ...ermostat mural voir Figure B et le cas ch ant sur le bo tier delat l commande FigureC Pouracheverl instal lationcorrectedecefoyer proc dezcommesuitavec les tiquettesadh sivesenlangues trang resfournie...

Страница 30: ...and don t try to repair it call a qualified service technician Force or attempted repair may result in a fire or explosion D DO NOT use this appliance if any part has been under water Immediately call...

Страница 31: ...ner gas is burning properly i e no floating lifting or flashback Adjust the primary air shutter s as required Check for proper main burner operation at both high and low flame PILOT ASSEMBLY Thermopil...

Страница 32: ...ed with a 200 CFM blower with a variable speed control and an automatic temperature activated on off snap switch Operation 1 After the fireplace warms up a heat activated switch will turn on the fan A...

Страница 33: ...osition when using the thermostat or remote control and set the thermostat or remote control to the lowest temperature when you wish to use the rocker switch only otherwise one may override the other...

Страница 34: ...ot air outlet vents for lint or other accumulations Never block or restrict vent openings obstruct flow of ventilation air or use vents other than those approved for use with this appliance o Check th...

Страница 35: ...er in place 5 Remove the labeled cover through which the valve control knobs protrude by removing the two allen head screws securing it and slide it off the valve knobs 6 Mark and disconnect wires on...

Страница 36: ...ht pilot If pilot lights turn off pilot and trigger the igniter again If pilot lights an intermittent gas air supply may be the problem if longer purge will not light check gap between electrode and p...

Страница 37: ...to NG Conversion Kit LP to NG ref form 775241M 75064 RAVL42 CK NG to LP Conversion Kit NG to LP ref form 775250M Misc 75259 NP RAVL30 42 Nail Plates 4 x 12 galvanized 75247 Reducer 8 6 5 8 Reducer 8 t...

Страница 38: ...AN BRNKL TUSCAN Brushed Nickel 75317 AI42 TUSCAN BKNKL TUSCAN Black Nickel Screen Kit ref form 775289M 75029 Screen Face double Door black 43 1 4 W x 31 7 8 H INSETS Required Includes 1 Top and 1 Bott...

Страница 39: ...CSA P 4 1 02 ET CGA 2 17 M91 CET APPAREIL DOIT TRE INSTALL CONFORM MENT AUX EXIGENCES DES CODES R GIONAUX ET DU CODE D INSTALLATION ANSI NFPA 54 DERNI RE DITION ETATS UNIS OU CAN CGA B149 1 DERNI RE...

Страница 40: ...Pour assistance ou information suppl mentaires contactez un installateur qualifi un agent de service ou un fournisseur de gaz Si vous op rez cet appareil sans qu il ne soit correctement raccord un con...

Страница 41: ...41 NOTES...

Страница 42: ...rts list Use only parts sup plied from the manufacturer Normally all parts should be ordered through your Lennox distributor or dealer Parts will be shipped at prevailing prices at time of order When...

Отзывы: