background image

18

Flue Restrictors

The flue restrictor settings shown in 

Figures 22 and 23

 are for typical 

installations and may need to be adjusted from standard to take into 

account other variables in the installation to achieve proper combustion.  

See 

Flue Restrictor Guidelines

 on this page to assist you in making a 

proper flue restrictor adjustment. 

The Ravelle™ 42 gas fireplace uses balanced flue technology to ensure 

proper combustion. Flue restrictors may need to be installed depending 

on the vent configuration of your fireplace. The drawings on 

Page 19

 

show all the allowable pipe configurations for the Ravelle 42 gas fireplace. 

To properly install the flue restrictor, find your pipe configuration in the 

drawings on 

Page 19 

 and note which restrictor setting is recommended. 

The flue restrictors and four black self-tapping 5/32” allen head screws 

can be found in the firebox in a plastic bag. The restrictors should be 

placed over the openings at both sides of the ceiling of the firebox. For 

each restrictor, two self-tapping 5/32” allen head screws should be in-

stalled in either holes 1, 2, 3, or 4 in the restrictor and screwed into the 

two holes in the firebox ceiling. (There are four holes at each side of the 

firebox ceiling to receive only two screws. Insert the screws into either 

two holes). See the drawing to the right for the location of hole numbers 

on the restrictor. The numbered holes in which the screws are inserted 

in the restrictor should correspond to the restrictor position numbers 

found on the drawings for your pipe configuration. Restrictor positions 

are based on tests run in a laboratory. The optimum restrictor positions 

may need to be adjusted slightly depending on the conditions surround-

ing the residential installation. Do not adjust restrictors to a point where 

the fireplace is sooting.

Notes: The higher the number of the flue restrictor position, the greater 

amount of combustion air will be delivered.

Flue Restrictor Adjustment Guidelines

After the flue restrictors have been set to the standard settings as shown 

in 

Figures 22 and 23

, the burner flame appearance should be evaluated 

to determined if the flue restrictors need to be set to a different position 

to adjust for variables in your installation. Light the appliance and allow 

it to burn for 20 minutes. See 

Flame Color and Behavior

 on 

Page 31 

to 

determine if you have a proper burner flame appearance. If the proper 

flame appearance cannot be achieved, the flue restrictor may need to be 

set to a different position. See the following guidelines to determine if 

you need to readjust the flue restrictors.

Before proceeding, confirm the manifold and inlet gas pressure is correct, 

primary air shutter is properly adjusted, venting system connections are 

secure and not blocked and if you are at a high elevation, ensure unit has 

been properly derated:

Symptoms - Lack of Combustion Air

If the symptoms listed below are present, you may need to adjust the 

flue restrictor to a more open position

.   

•  Flame appears yellow

•  Floating Flames (lazy, ill defined, quiet, may roll)

•  Sooting

•  Pilot becomes yellow and appliance shuts down

Symptoms - Excessive Combustion Air

If the symptoms listed below are present, you may need to adjust the 

flue restrictor to a more closed position

•  Low Flame

•  Pilot pulls and appliance shuts down

•  Pilot flame ghosts

Termination Heights For Vents 

Above Flat Or Sloped Roofs

Ref. NFPA 54 / ANSI Z223.1

Roof Pitch

* Feet

* Meters

Flat to 6/12

1.0

0.3

6/12 to 7/12

1.25

0.38

7/12 to 8/12

1.5

0.46

8/12 to 9/12

2.0

0.61

9/12 to 10/12

2.5

0.76

10/12 to 11/12

3.25

0.99

11/12 to 12/12

4.0

1.22

12/12 to 14/12

5.0

1.52

14/12 to 16/12

6.0

1.83

16/12 to 18/12

7.0

2.13

18/12 to 20/12

7.5

2.29

20/12 to 21/12

8.0

2.44

12 

Roof Pitch is X/12 

2 FT 

MIN. 

2 FT MIN. 

Lowest 

Discharge 

Opening 

H* 

*H = MINIMUM HEIGHT FROM ROOF TO 

LOWEST DISCHARGE OPENING OF VENT 

TERMINATION HEIGHTS FOR VENTS ABOVE 

FLAT OR SLOPED ROOFS 

Horizontal Overhang 

Vertical 

Wall 

Vent 

Termination 

Storm Collar 

Concentric 

Vent Pipe 

Flashing 

1 inch (25.4 mm) Minimum 

Clearance to Combustibles 

Vertical Vent Termination Clearances

The vent / air intake termination clearances above the high side of an 

angled roof is as shown in the table below.

Figure 20

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

Figure 21

Restrictors

Interior of Firebox

Restrictors

Interior of Firebox

Содержание Ravelle 42

Страница 1: ...vous trouvez Appelez imm diatement votre fournisseur de gaz depuis un voisin Suivez les instructions du fournis seur Si vous ne pouvez rejoindre le fournisseur de gaz appelez le service des incindies...

Страница 2: ...nsiderations 16 Horizontal Vent Installation 17 Vertical Vent Installation 17 Flue Restrictors 18 Vertical Vent Termination Clearances 18 Horizontal Terminations 19 Vertical Terminations 19 Horizontal...

Страница 3: ...ler service agency or the gas supplier WARNING Failure to comply with these installation instructions will result in an improperly installed and operating appliance voiding its warranty Any change to...

Страница 4: ...not be connected to a chimney or flue serving a separate solid fuel burning appliance These appliances are vented gas appliances Do not burn wood or other material in these appliances This appliance i...

Страница 5: ...l building department for requirements in your area SMOKE DETECTORS Certification Gas appliances must be tested and certified by a nationally recognized testing and certification laboratory to ANSI Am...

Страница 6: ...cassette valve and pilot assembly or installing a conversionkit OnlyLennoxHearthProductsconversionkitscanbeusedto convert from NG to LP or LP to NG Contact your Lennox Hearth Products dealer for detai...

Страница 7: ...Mantel The drawing at the lower right shows the minimum distances from the base of the fireplace to combustible mantel and facing material Combustible materials may be placed above and within the sha...

Страница 8: ...the valve wThe electrical power supply wiring should be routed to the right rear of the unit Note The fireplace may be placed directly on wood or non combustible flooring but not on vinyl floor coveri...

Страница 9: ...756 20 3 4 527 47 3 4 1213 35 1 2 902 2 51 34 864 41 1041 38 1 4 972 30 762 43 1092 30 762 3 1 2 89 9 1 2 241 10 3 4 273 72 1 2 1842 6 7 8 175 18 3 16 462 32 5 16 821 3 1 2 89 5 127 6 1 4 159 2 1 4 5...

Страница 10: ...fireplace must be raised the thickness of that hearth extension less the 7 8 22 mm For example if a 2 7 8 73 mm thick cultured stone is to be placed on the floor to serve as the hearth extension then...

Страница 11: ...replace face see below Facing Installation Considerations Non combustible cement board such as Wonderboard Durock or Har dybacker must extend 10 254 mm above the 1 25 mm top reveal and a minimum of 3...

Страница 12: ...75098 Foundry 75035 and Classic Louver 75101 should be used while installing the facing material Templates for the various faces may be purchased from your Lennox Hearth Products dealer or a template...

Страница 13: ...e place face The acid wash will tarnish the face Consult your masonry installer Face Installation A number of different faces are available for the Ravelle 42 gas fire place however all the faces are...

Страница 14: ...red by the approved vent manufacturer Installation other than as instructed by Lennox Hearth Products and vent manufacturers instructions Vent Parts List Direct vent pipe Security Secure Vent may be u...

Страница 15: ...gh Wind 1250 Vinyl Siding Standoff Vent Parts List Vertical Direct vent pipe by Security or Simpson Dura Vent may be used with the Ravelle 42 gas fireplace Please see the lists below to verify the com...

Страница 16: ...orizontal runs of vent must be supported every three feet Wall straps are available for this purpose Pipe Sealing If Security Secure Vent pipe is used then sealant is required at only the first pipe j...

Страница 17: ...inations locations see the diagram on Page 20 9 Allowableclearancesfromtheventpipetocombustiblemateri als must be maintained See Page 7 for these clearances 10 Do not locate the termination cap where...

Страница 18: ...and 23 the burner flame appearance should be evaluated to determined if the flue restrictors need to be set to a different position to adjust for variables in your installation Light the appliance an...

Страница 19: ...of pipe does not exceed those shown below Use the restrictor positions indicated If the fireplace is vented with an elbow directly off the top of the flue collar and three to four feet of horizontal p...

Страница 20: ...ove meter regulator assembly 3 feet 91 cm within a height of 15 feet above the meter regulator assembly 3 feet 91 cm within a height of 15 feet above the meter regulator assembly I Clearance to servic...

Страница 21: ...g 2 on tab An air shield is provided for natural gas use only For LP conversions remove the air shield 5 Place Logs 3 4 and 5 on tab inserts Important Maintain a 1 4 6 4mm air space along the entire l...

Страница 22: ...ff at the electrical panel before any connections are made The loop of wire with the label attached E in Figure 29 may be cut and the wire leads from the wall mounted speed control connected to each e...

Страница 23: ...p is to the right of the inlet tap To check manifold pressure with the fireplace burning at the high burn setting insert a small flat bladed screwdriver into the tap and turn a half turn counter clock...

Страница 24: ...ing air is drawn from a distant room lowering the pressure in that room through the return air duct into the bottom of the fireplace The air then passes through the outer shell and heat exchanger of t...

Страница 25: ...nting Brackets Two White Headed Grille Screws Six Wire Nuts Sixteen Sheet Metal Screws One Wire Clamp The system draws heated air from the Ravelle 42 gas fireplace and moves it with the use of a 150 C...

Страница 26: ...the fan box Since the fan box body is wider than the portion that comes up through the floor an additional piece of floor ing F below should also be cut out for the fan box to slide through Save this...

Страница 27: ...ape at each joint 5 Secure the ducting to prevent sagging Wiring of the Forced Air System Disconnect the electrical supply to the fireplace at the electrical panel prior to wiring the forced air syste...

Страница 28: ...erentcolorsofcovers and knobs come with the kit Select the cover desired and fasten the speed control and cover to the box with the screws supplied Push the desired knob onto the shaft of the speed co...

Страница 29: ...ermostat mural voir Figure B et le cas ch ant sur le bo tier delat l commande FigureC Pouracheverl instal lationcorrectedecefoyer proc dezcommesuitavec les tiquettesadh sivesenlangues trang resfournie...

Страница 30: ...and don t try to repair it call a qualified service technician Force or attempted repair may result in a fire or explosion D DO NOT use this appliance if any part has been under water Immediately call...

Страница 31: ...ner gas is burning properly i e no floating lifting or flashback Adjust the primary air shutter s as required Check for proper main burner operation at both high and low flame PILOT ASSEMBLY Thermopil...

Страница 32: ...ed with a 200 CFM blower with a variable speed control and an automatic temperature activated on off snap switch Operation 1 After the fireplace warms up a heat activated switch will turn on the fan A...

Страница 33: ...osition when using the thermostat or remote control and set the thermostat or remote control to the lowest temperature when you wish to use the rocker switch only otherwise one may override the other...

Страница 34: ...ot air outlet vents for lint or other accumulations Never block or restrict vent openings obstruct flow of ventilation air or use vents other than those approved for use with this appliance o Check th...

Страница 35: ...er in place 5 Remove the labeled cover through which the valve control knobs protrude by removing the two allen head screws securing it and slide it off the valve knobs 6 Mark and disconnect wires on...

Страница 36: ...ht pilot If pilot lights turn off pilot and trigger the igniter again If pilot lights an intermittent gas air supply may be the problem if longer purge will not light check gap between electrode and p...

Страница 37: ...to NG Conversion Kit LP to NG ref form 775241M 75064 RAVL42 CK NG to LP Conversion Kit NG to LP ref form 775250M Misc 75259 NP RAVL30 42 Nail Plates 4 x 12 galvanized 75247 Reducer 8 6 5 8 Reducer 8 t...

Страница 38: ...AN BRNKL TUSCAN Brushed Nickel 75317 AI42 TUSCAN BKNKL TUSCAN Black Nickel Screen Kit ref form 775289M 75029 Screen Face double Door black 43 1 4 W x 31 7 8 H INSETS Required Includes 1 Top and 1 Bott...

Страница 39: ...CSA P 4 1 02 ET CGA 2 17 M91 CET APPAREIL DOIT TRE INSTALL CONFORM MENT AUX EXIGENCES DES CODES R GIONAUX ET DU CODE D INSTALLATION ANSI NFPA 54 DERNI RE DITION ETATS UNIS OU CAN CGA B149 1 DERNI RE...

Страница 40: ...Pour assistance ou information suppl mentaires contactez un installateur qualifi un agent de service ou un fournisseur de gaz Si vous op rez cet appareil sans qu il ne soit correctement raccord un con...

Страница 41: ...41 NOTES...

Страница 42: ...rts list Use only parts sup plied from the manufacturer Normally all parts should be ordered through your Lennox distributor or dealer Parts will be shipped at prevailing prices at time of order When...

Отзывы: