Thank you for choosing the Lennox Quantum Waterside 
Fan Coil Unit.  Please read the following information 
carefully prior to installation. These instructions should 
be kept in a safe place  for future reference.

WARNING:

 

ISOLATE FROM THE ELECTRICAL SUPPLY 

BEFORE COMMENCING WORK.

These units can be installed virtually as delivered.   They 
are intended for fitting behind a suspended ceiling or a 
similar ceiling void and have circular spigots for 
connecting to ducting.  Similarly, they can have a fresh air 
spigot fitted when specified.

MOUNTING

In all cases, the units are fixed to the mounting face by 
means of four slots in the end flanges.  Down rods, 10mm 
in diameter, should be used to support units 

1.

Unistrut should be mounted to the slab (see 
dimensional data) and four 10mm down rods fixed to 
the unistrut.

2.

The down rods should have two nuts and two washers 
to lock the unit in position. The unit can then be lifted 
into location, hooking the slots (in the top panel) over 
the washers. The nuts must then be securely 
tightened.

3.

Check to ensure the unit is level and adjust if 
necessary.

4.

Check that water runs into the waste from the drain 
tray, by pouring water into it.

NOTE:

 To allow for Service Clearances it is recommended 

that a minimum space of 50mm is provided from top of 
the unit to underside of slab.

Sufficient space should be provided to allow for clear and 
safe access to the control panel.

PIPEWORK CONNECTIONS

1. Water flow and return connection

Plain pipe connection tails are all to BS 2871, Part 1: 
1971 and are suitable for brazed or compression fittings.  
Connection sizes are 15mm or 22mm outside diameter 
on the cooling coil and 15mm on the heating coil.  Actual 
final connection pipesizes will vary depending on valve 
configuration where fitted.

2. Condensate Tray Connection

An end facing 22mm outside diameter copper 
condensate drain connection tube to BS 2871, Part 1: 
1971 is fitted as standard to the condensate tray on all 
units.

3. Air Vents and Drains

Brass air vent and drain tapping points are fitted as 
standard to all coils. These are positioned at the top and 
bottom of the header tubes.

DUCT CONNECTIONS

1. Discharge Air Side

An integral discharge plenum is fitted as standard 
complete with 197mm or 247mm outside diameter 
circular spigots.  These are to accept standard   diameter 
flexible ducting.  Blanking caps are available to order.

2. Inlet Air Side

When specified, units will be fitted with an Air Inlet 
Plenum, this will have the same number, size and 
position of circular spigots as on the discharge air side.  
Blanking caps are available subject to order.

3. Fresh Air Spigot

The fresh air spigot is available in a size of 100mm 
diameter.

4. Condensate pump

Condensate pump kits are available as an optional 
factory fitted option.  Refer to diagrams indicating 
electrical wiring details.

5. Electrical heating element

LQWFC150

 2KW

LQWFC190

2KW

LQWFC260

2KW

LQWFC330

4KW

LQWFC440      4KW

Refer  to   diagrams   indicating   electrical wiring   details.

MOUNTING / CONNECTIONS

3

R

LENN  X

Содержание Quantum Waterside LQWFC 150

Страница 1: ......

Страница 2: ...ns 4 Controls 4 Fan Speed Settings 5 Periodic Maintenance 6 Fancoil Maintenance 7 Coil Water Content 8 Weights 8 Minimum No Spigots 8 Coil Connections 8 Wiring Diagram 9 Fault Finding 10 Spares List 1...

Страница 3: ...s are to have maintenance free sealed for life bearings and built in thermal overload protec tion Insulation Dual function thermal and acoustic insulation shall be used and shall be to Class 0 specifi...

Страница 4: ...el PIPEWORK CONNECTIONS 1 Water flow and return connection Plain pipe connection tails are all to BS 2871 Part 1 1971 and are suitable for brazed or compression fittings Connection sizes are 15mm or 2...

Страница 5: ...acitor type and have a capacitor fixed to the outside of the motor All motors have thermal overload protection as standard Access to the fan tray is via removable panels on the bottom face of the unit...

Страница 6: ...ign speed EL 120 150 I 0 1 130 L 120 150 II 0 1 145 ML 135 165 II 0 1 160 M 150 180 II 0 1 175 H 165 195 III 0 0 195 Main tapping Fan speed switches Output Volts 150 W Y R 5 V 10 V design speed EL 120...

Страница 7: ...ace if necessary Ensureallelectricalconnectionsaresecure Check functions of controls according to operating procedures 6 Fan Motor and Fan A regular check on the fan motor assembly is advisable to asc...

Страница 8: ...ECK ACTUATOR EXAMINE VALVES ACTUATORS EXAMINE WATER FLOW TEMPERATURE CHECK CONTROLLER CHECK MOTOR CAPACITOR ADD LINK BETWEEN TERM 8 9 IF FCU WORKS CONTROL LER IS FAULTY CONTACT SPARES DEPT CONTACT SPA...

Страница 9: ...0 61 0 74 262 1 16 1 40 244 1 04 1 26 220 0 97 1 17 197 0 87 1 05 155 0 67 0 81 FAN MODEL SPEED Volts H 200 LQWFC M 170 150 ML 150 L 130 EL 120 H 170 LQWFC M 150 190 ML 140 L 130 EL 120 H 200 LQWFC M...

Страница 10: ...R LENN X 9 WIRING DIAGRAM...

Страница 11: ...R EMENT CALIBRATED CORRECTION FACTOR CHECK SOURCE OF CONTROLLER EXAMINE SWITCH WIRING CRIMP CONNECTIONS CONTINUITY TEST WIRES 24V AND MAINS OUTPUT OK BUT NEW FANCOIL FAULT FINDING CHECK QUANTITY LOCAT...

Страница 12: ...igh Temp 9 14 deg C Flow X Z303793 Cooling Coil 4 row High Temp 9 14 deg C Flow X Z303834 Cooling Coil 4 row High Temp 9 14 deg C Flow X Z303878 Cooling Coil 4 row High Temp 9 14 deg C Flow X Z301771...

Страница 13: ......

Отзывы: