background image

8

wall construction. Use the appropriate type of 

anchors for the application.

3. 

The  wall  mounting  plate  must  be  installed  flush 

against the wall so that the indoor unit will be flush 

after installation. Any space between the wall and unit 

will cause noise and vibration.

4.  The wall mounting plate must be installed horizontally 

level on the wall.

Installation of Wall Sleeve

The utility bundle may be routed out of the back of the unit 

or out either side. If the bundle is to be routed out the back 

through an external wall, use a field-provided wall sleeve 

to protect the utility bundle. 

NOTE: 

If the utility bundle will be routed out the side of the 

indoor unit and up the wall above a false ceiling, 

continue to the next section.

1.  Prior to making the hole and installing the wall sleeve 

for the utility bundle, check to ensure that there are 

no other utilities located in the wall behind the hole 

location.

2.  Cut a hole in the wall using a suitable hole saw. Hole 

should be at a slight downward slant ­ 3/16” to 3/8” 

toward the outdoor side.

3.  Measure the thickness of the wall from the inside 

edge to the outside edge and cut the field-provided 

wall sleeve at a slight angle 1/4” (6 mm) shorter than 

the thickness of the wall.

INSIDE

OUTSIDE

Typical

installation

procedure

shown.

Figure 14. Boring Hole for Wall Sleeve

USE SUITABLE TOOL TO CUT PVC FOR WALL

SLEEVE AT SLIGHT ANGLE AS SHOWN.

Figure 15. PVC Wall Sleeve Installation

NOTE: 

When passing bundled services through an 

exterior  brick  or  concrete  wall,  protect  the 

copper pipes and wiring from the effects of these 

construction materials by using a sleeve made 

of suitable material. The integrity of copper pipe 

and wiring can deteriorate when exposed to these 

construction materials.

Installation of Indoor Unit on Wall Mounting Plate

1. 

A length of field-provided flexible condensate piping 

should be connected to the drain prior to securing the 

unit to the wall mounting plate.

2.  If the factory­provided refrigerant piping connections 

and field-provided flexible condensate piping are long 

enough to enable final field connections after unit is 

installed  on  wall  mounting  plate,  use  field-provided 

tape to bundle them together.

3.  The utility bundle may be routed out of the back of 

the unit or out either side. If the bundle is to be routed 

out the back through an external wall, feed the utility 

bundle through the wall sleeve. If the utility bundle is 

to be routed out of the side of the indoor unit and up 

an inside wall, carefully form the utility bundle so that 

it makes a gentle 90° turn.

4.  Align the back of the indoor unit with the hooks at the 

top of the wall mounting plate. Move the unit from side 

to side to make sure that it settles securely.

5.  The bottom of the unit can be lifted to facilitate 

refrigerant piping and condensate drain connections, 

if necessary.

TEMPORARY

SPACER

(To facilitate

connections)

HOOKS AT TOP

OF MOUNTING

BRACKET

Figure 16. Secure Unit to Wall Mounting Plate

Indoor Unit Condensate Piping Connections

IMPORTANT

Make sure that drain piping is properly routed and 

insulated to prevent both leaks and condensation.

1. 

Use a field-provided hose clamp to secure the drain 

line stub on the side of the cabinet to a field-supplied 

1­inch (25 mm) drain line. 

NOTE: 

Take care not to over-tighten the hose clamps this 

may damage the drain line stub.

NOTE: 

Connection between stub and drain line must be 

watertight. Apply non-hardening plumbing joint 

compound if needed to ensure a watertight seal. 

2. 

Confirm proper slope (not less than 1/4 inch per foot 

(18 mm per meter) and routing of condensate lines to 

ensure moisture is drained away from the indoor unit.

3.  Drain should be as short as possible and should 

not have any droops or kinks that would restrict 

condensate flow and shall be approved resistant pipe. 

There must be a 2­inch (51 mm) space between the 

end of the condensate drain and the final termination 

point (ground, open drain, etc.) to ensure that the line 

will drain freely.

4.  After the system installation is complete, the 

condensate drain line must be checked for leaks 

and proper drainage. If a field-provided condensate 

Содержание MWHA009S4-1L

Страница 1: ...unit assembly must be thoroughly cleaned following final construction clean up All mini split operating conditions must be verified ac cording to these installation instructions MHA Series Units SING...

Страница 2: ...umbers Table 2 Component Catalog Number Cross Reference Product Capacity Voltage Lennox Model Number Catalog Numbers Wall Mounted Indoor Unit 9K 115V MWHA009S4 1L 17K07 Wall Mounted Indoor Unit 12K 11...

Страница 3: ...bility properties with mineral based oil and POE oil Polyolester it is not recommended to mix PVE oil with any other type of refrigerant oil Model Number Identification M WH A 009 S 4 1 P Unit Type WH...

Страница 4: ...1 2 13 1 2 13 MHA009S4S BOTTOM VIEW FRONT VIEW SIDE VIEW SIDE VIEW 12 5 8 322 11 1 4 286 2 3 8 60 3 5 8 92 DRAIN HOLE bottom of unit 11 3 4 298 Figure 2 9K Outdoor Unit Dimensions Inches mm BOTTOM VIE...

Страница 5: ...425 9 1 8 232 5 127 31 5 8 803 7 1 2 191 11 3 4 298 1 3 4 44 Figure 7 12K Indoor Unit Wall Plate Dimensions Inches mm MHWA018S4 Left Rear Hole 2 1 2 in 64 mm diameter Right Rear Hole 2 1 2 in 64 mm d...

Страница 6: ...m 10 254 Minimum 10 254 Minimum AIR FLO W AIR FLO W CLEARANCE NOTES FOR MULTIPLE UNITS If the height of the wall C is less than or equal to the height of the smallest unit A the distance from the unit...

Страница 7: ...cient space around unit for proper operation and maintenance Install unit a minimum of 3 feet 1m away from any antenna power cord line radio telephone security system or intercom Electrical interferen...

Страница 8: ...ded refrigerant piping connections and field provided flexible condensate piping are long enough to enable final field connections after unit is installed on wall mounting plate use field provided tap...

Страница 9: ...and vibration of the unit where the operation noise will not be amplified Choose a location where the hot air discharged from the unit or the operation noise will not be a nuisance to neighbors Avoid...

Страница 10: ...the outdoor unit as illustrated in Figure 24 Avoid Defrost Water Ice Hazard Air Inlet Air Outlet Figure 22 Outdoor Unit on Brackets above Snow Line Air Outlet Air Inlet 12 in 305 mm 79 in 2007 mm Fig...

Страница 11: ...oor Unit to Hanging Brackets If the outdoor unit is installed on field provided wall mounting brackets use lag bolts or equivalent to secure the outdoor unit to the bracket Minimum rear clearance can...

Страница 12: ...ections Male to Female Connection Table 5 Refrigerant Piping and Indoor Unit Connection Sizes Size Btuh Liquid Line in Suction Line in 9K 1 4 3 8 12K 1 4 1 2 18K 1 4 1 2 24K 3 8 5 8 A B CANT ON THE OU...

Страница 13: ...s Cooling or heating efficiency drops Moisture in the refrigerant circuit may freeze Water may lead to corrosion of parts in the refrigera tion system The line set between the indoor and outdoor units...

Страница 14: ...tween indoor and outdoor units Outdoor Unit Refer to unit nameplate for minimum circuit ampacity and maximum over current protection size Make all electrical power wiring connections at the outdoor un...

Страница 15: ...AC 4 16AWG 16A 20A Outdoor to Main Power L N and GND 09K 115VAC 3 16AWG 16A Indoor to Outdoor Wiring Communication Power 1 2 3 and GND 12K 115VAC 4 Stranded and unshielded 16AWG 15A 20A Outdoor to Mai...

Страница 16: ...4 Note Th e progra mmable wired controlle r and L VM use the sam e port CN4 03 CN 2 C N201 NOTE COMPONENT IN DASH LINE IS OPTIONAL OR FIELD WIRING CN402 S5 FOR REMOTE ON OF FACTORY SETTING MODE REMOTE...

Страница 17: ...CN 1 CN 2 CN 16 CN 50 CN 30 CN 29 CN 28 OUTDOOR CONTROL TP T5 T3 T4 Figure 37 12K 115VAC Outdoor Unit Wiring Diagram 4 WAY VALVE OU TDOOR FAN CN 7 3 6 CN 31 PAN HEATER CN 15 CN 60 CRANKCASE HEATER CN...

Страница 18: ...nameplate If not do not start the equipment until you have consulted with the power company and the voltage condition has been corrected 7 Refer to the included user guide to operate the system using...

Страница 19: ...ireless remote Double Check Line Set Connections During operation the pressure of the refrigerant circuit will increase This may reveal leaks that were not present during your initial leak check Take...

Страница 20: ...20...

Отзывы: