background image

11

•  The conduit must be designed so it cannot collect and 

retain water.

Securing the Outdoor Unit

Slab or Roof Mounting

Install the unit a minimum of 4 inches (102 mm) above 

the roof or ground surface to avoid debris build­up around 

the unit. Place the unit above a load bearing wall or area 

of the roof that can adequately support the unit. Consult 

local codes for rooftop applications.

CAUTION

Roof Damage!
This system contains both refrigerant and oil. Some 

rubber roofing material may absorb oil. This will cause 

the rubber to swell when it comes into contact with oil. 

The rubber will then bubble and could cause leaks. 

Protect the roof surface to avoid exposure to refrigerant 

and oil during service and installation. Failure to follow 

this notice could result in damage to roof surface.

Securing Outdoor Unit to Slab, Frame, or Rails

If the outdoor unit is installed on a field-provided slab or 

frame, use lag bolts or equivalent to secure the outdoor 

unit to the slab or frame.

Four Field-provided Anchor Bolts

Figure 26. Securing Outdoor Unit to Slab

Four Field-Provided 

Anchor Bolts

Figure 27. Securing Outdoor Unit to Rails

Securing Outdoor Unit to Hanging Brackets

If  the  outdoor  unit  is  installed  on  field-provided  wall 

mounting brackets, use lag bolts or equivalent to secure 

the outdoor unit to the bracket. Minimum rear clearance 

can be reduced to 6 inches (152 mm) when mounted 

on brackets and with no obstructions on the other three 

sides. Allow for moisture disposal when placing units 

above one another.

Air Outlet

Air Inlet

6 in

152 mm

Figure 28. Securing Outdoor Unit to Brackets

Refrigerant Piping Connections

Field piping consists of two copper lines connecting the 

outdoor unit to the indoor unit. “Table 5. Refrigerant Piping 

and Indoor Unit Connection Sizes” on page 12 lists 

the connection sizes. The connections are made using 

the provided brass flare nuts at the end of the refrigerant 

piping connections. 

1.  Choose the correct pipe sizes for your application 

using  “Table 5. Refrigerant Piping and Indoor Unit 

Connection Sizes” on page 12.

2. 

Confirm that you are using the correct diameter piping.

3.  Determine the necessary piping length required for 

the application.

4.  Cut the selected pipes with a pipe cutter. Make the 

cuts  flat  and  smooth  as  illustrated  in  “Figure  29. 

Cutting Piping”.

90

Lean

Crude

Burr

o

 

 

Figure 29. Cutting Piping

5.  Insulate the copper piping.
6. 

Insert a flare nut onto each pipe before flaring. 

7. 

Use “Table 4. Flaring Pipe” to properly flare the pipe.

Содержание MWHA009S4-1L

Страница 1: ...unit assembly must be thoroughly cleaned following final construction clean up All mini split operating conditions must be verified ac cording to these installation instructions MHA Series Units SING...

Страница 2: ...umbers Table 2 Component Catalog Number Cross Reference Product Capacity Voltage Lennox Model Number Catalog Numbers Wall Mounted Indoor Unit 9K 115V MWHA009S4 1L 17K07 Wall Mounted Indoor Unit 12K 11...

Страница 3: ...bility properties with mineral based oil and POE oil Polyolester it is not recommended to mix PVE oil with any other type of refrigerant oil Model Number Identification M WH A 009 S 4 1 P Unit Type WH...

Страница 4: ...1 2 13 1 2 13 MHA009S4S BOTTOM VIEW FRONT VIEW SIDE VIEW SIDE VIEW 12 5 8 322 11 1 4 286 2 3 8 60 3 5 8 92 DRAIN HOLE bottom of unit 11 3 4 298 Figure 2 9K Outdoor Unit Dimensions Inches mm BOTTOM VIE...

Страница 5: ...425 9 1 8 232 5 127 31 5 8 803 7 1 2 191 11 3 4 298 1 3 4 44 Figure 7 12K Indoor Unit Wall Plate Dimensions Inches mm MHWA018S4 Left Rear Hole 2 1 2 in 64 mm diameter Right Rear Hole 2 1 2 in 64 mm d...

Страница 6: ...m 10 254 Minimum 10 254 Minimum AIR FLO W AIR FLO W CLEARANCE NOTES FOR MULTIPLE UNITS If the height of the wall C is less than or equal to the height of the smallest unit A the distance from the unit...

Страница 7: ...cient space around unit for proper operation and maintenance Install unit a minimum of 3 feet 1m away from any antenna power cord line radio telephone security system or intercom Electrical interferen...

Страница 8: ...ded refrigerant piping connections and field provided flexible condensate piping are long enough to enable final field connections after unit is installed on wall mounting plate use field provided tap...

Страница 9: ...and vibration of the unit where the operation noise will not be amplified Choose a location where the hot air discharged from the unit or the operation noise will not be a nuisance to neighbors Avoid...

Страница 10: ...the outdoor unit as illustrated in Figure 24 Avoid Defrost Water Ice Hazard Air Inlet Air Outlet Figure 22 Outdoor Unit on Brackets above Snow Line Air Outlet Air Inlet 12 in 305 mm 79 in 2007 mm Fig...

Страница 11: ...oor Unit to Hanging Brackets If the outdoor unit is installed on field provided wall mounting brackets use lag bolts or equivalent to secure the outdoor unit to the bracket Minimum rear clearance can...

Страница 12: ...ections Male to Female Connection Table 5 Refrigerant Piping and Indoor Unit Connection Sizes Size Btuh Liquid Line in Suction Line in 9K 1 4 3 8 12K 1 4 1 2 18K 1 4 1 2 24K 3 8 5 8 A B CANT ON THE OU...

Страница 13: ...s Cooling or heating efficiency drops Moisture in the refrigerant circuit may freeze Water may lead to corrosion of parts in the refrigera tion system The line set between the indoor and outdoor units...

Страница 14: ...tween indoor and outdoor units Outdoor Unit Refer to unit nameplate for minimum circuit ampacity and maximum over current protection size Make all electrical power wiring connections at the outdoor un...

Страница 15: ...AC 4 16AWG 16A 20A Outdoor to Main Power L N and GND 09K 115VAC 3 16AWG 16A Indoor to Outdoor Wiring Communication Power 1 2 3 and GND 12K 115VAC 4 Stranded and unshielded 16AWG 15A 20A Outdoor to Mai...

Страница 16: ...4 Note Th e progra mmable wired controlle r and L VM use the sam e port CN4 03 CN 2 C N201 NOTE COMPONENT IN DASH LINE IS OPTIONAL OR FIELD WIRING CN402 S5 FOR REMOTE ON OF FACTORY SETTING MODE REMOTE...

Страница 17: ...CN 1 CN 2 CN 16 CN 50 CN 30 CN 29 CN 28 OUTDOOR CONTROL TP T5 T3 T4 Figure 37 12K 115VAC Outdoor Unit Wiring Diagram 4 WAY VALVE OU TDOOR FAN CN 7 3 6 CN 31 PAN HEATER CN 15 CN 60 CRANKCASE HEATER CN...

Страница 18: ...nameplate If not do not start the equipment until you have consulted with the power company and the voltage condition has been corrected 7 Refer to the included user guide to operate the system using...

Страница 19: ...ireless remote Double Check Line Set Connections During operation the pressure of the refrigerant circuit will increase This may reveal leaks that were not present during your initial leak check Take...

Страница 20: ...20...

Отзывы: