background image

10

12 in

305 mm

24 in

610 mm

12 in

305 mm

24 in

610 mm

NOTE - Minimum clearances shown.

Figure 21. Unit installed in Alcove

IMPORTANT

The construction of a canopy or shade is necessary 

because of an ambient limit control set to 122°F (50°C)

to protect the electronics. If the outdoor unit is placed in 

direct sunlight it is possible that the limit may activate 

and shut down the unit. 

•  Place unit away from overhanging roof lines which 

would allow water or ice to drop on, or in front of, coil 

or into unit. Construct a canopy as illustrated in “Fig­

ure 19. Outdoor Unit on Pedestal and Protective Can

­

opy”.

•  The unit base should be elevated above the depth of 

average snows as illustrated in “Figure 22. Outdoor 

Unit on Brackets above Snow Line”.

•   In heavy snow areas, do not place the unit where drift­

ing will occur as illustrated in “Figure 23. Outdoor Unit 

Air Flow Obstructed by Snow”.

•  Carefully consider how to manage defrost water dis­

posal to prevent ice from blocking walkways or creat­

ing a safety hazard near the outdoor unit as illustrated 

in “Figure 24. Avoid Defrost Water Ice Hazard”.

Air Inlet

Air Outlet

Figure 22. Outdoor Unit on Brackets above Snow 

Line

Air Outlet

Air Inlet

12 in

305 mm

79 in

2007 mm

Figure 23. Outdoor Unit Air Flow Obstructed by 

Snow

Figure 24. Avoid Defrost Water Ice Hazard

Condensate Piping

Condensate formed during the heating and defrost 

processes must be drained from heat pump units. Drain 

holes are provided in the base of the units to ensure proper 

drainage. Heat pumps must be raised when installed on a 

concrete pad or the ground to allow drainage to occur. If 

the heat pump unit is installed on wall mounting bracket, 

insert the provided drain connector into one of the 1 

inch (25 mm) drain holes and attached a field-provided 

insulated drain hose to the connector. Use field-provided 

rubber plugs to cover any unused drain holes (see “Figure 

25. Condensate Drain” on page 10). 

Drain

Connector

Chassis

Condensate Drain

(location varies per model)

Figure 25. Condensate Drain

Buried Refrigerant Pipe Protection

•  All refrigerant lines must be insulated regardless of if 

it is buried.

•  In addition to insulating each line of piping, buried 

lines must rest inside a 

sealed, watertight

 conduit.

Содержание MWHA009S4-1L

Страница 1: ...unit assembly must be thoroughly cleaned following final construction clean up All mini split operating conditions must be verified ac cording to these installation instructions MHA Series Units SING...

Страница 2: ...umbers Table 2 Component Catalog Number Cross Reference Product Capacity Voltage Lennox Model Number Catalog Numbers Wall Mounted Indoor Unit 9K 115V MWHA009S4 1L 17K07 Wall Mounted Indoor Unit 12K 11...

Страница 3: ...bility properties with mineral based oil and POE oil Polyolester it is not recommended to mix PVE oil with any other type of refrigerant oil Model Number Identification M WH A 009 S 4 1 P Unit Type WH...

Страница 4: ...1 2 13 1 2 13 MHA009S4S BOTTOM VIEW FRONT VIEW SIDE VIEW SIDE VIEW 12 5 8 322 11 1 4 286 2 3 8 60 3 5 8 92 DRAIN HOLE bottom of unit 11 3 4 298 Figure 2 9K Outdoor Unit Dimensions Inches mm BOTTOM VIE...

Страница 5: ...425 9 1 8 232 5 127 31 5 8 803 7 1 2 191 11 3 4 298 1 3 4 44 Figure 7 12K Indoor Unit Wall Plate Dimensions Inches mm MHWA018S4 Left Rear Hole 2 1 2 in 64 mm diameter Right Rear Hole 2 1 2 in 64 mm d...

Страница 6: ...m 10 254 Minimum 10 254 Minimum AIR FLO W AIR FLO W CLEARANCE NOTES FOR MULTIPLE UNITS If the height of the wall C is less than or equal to the height of the smallest unit A the distance from the unit...

Страница 7: ...cient space around unit for proper operation and maintenance Install unit a minimum of 3 feet 1m away from any antenna power cord line radio telephone security system or intercom Electrical interferen...

Страница 8: ...ded refrigerant piping connections and field provided flexible condensate piping are long enough to enable final field connections after unit is installed on wall mounting plate use field provided tap...

Страница 9: ...and vibration of the unit where the operation noise will not be amplified Choose a location where the hot air discharged from the unit or the operation noise will not be a nuisance to neighbors Avoid...

Страница 10: ...the outdoor unit as illustrated in Figure 24 Avoid Defrost Water Ice Hazard Air Inlet Air Outlet Figure 22 Outdoor Unit on Brackets above Snow Line Air Outlet Air Inlet 12 in 305 mm 79 in 2007 mm Fig...

Страница 11: ...oor Unit to Hanging Brackets If the outdoor unit is installed on field provided wall mounting brackets use lag bolts or equivalent to secure the outdoor unit to the bracket Minimum rear clearance can...

Страница 12: ...ections Male to Female Connection Table 5 Refrigerant Piping and Indoor Unit Connection Sizes Size Btuh Liquid Line in Suction Line in 9K 1 4 3 8 12K 1 4 1 2 18K 1 4 1 2 24K 3 8 5 8 A B CANT ON THE OU...

Страница 13: ...s Cooling or heating efficiency drops Moisture in the refrigerant circuit may freeze Water may lead to corrosion of parts in the refrigera tion system The line set between the indoor and outdoor units...

Страница 14: ...tween indoor and outdoor units Outdoor Unit Refer to unit nameplate for minimum circuit ampacity and maximum over current protection size Make all electrical power wiring connections at the outdoor un...

Страница 15: ...AC 4 16AWG 16A 20A Outdoor to Main Power L N and GND 09K 115VAC 3 16AWG 16A Indoor to Outdoor Wiring Communication Power 1 2 3 and GND 12K 115VAC 4 Stranded and unshielded 16AWG 15A 20A Outdoor to Mai...

Страница 16: ...4 Note Th e progra mmable wired controlle r and L VM use the sam e port CN4 03 CN 2 C N201 NOTE COMPONENT IN DASH LINE IS OPTIONAL OR FIELD WIRING CN402 S5 FOR REMOTE ON OF FACTORY SETTING MODE REMOTE...

Страница 17: ...CN 1 CN 2 CN 16 CN 50 CN 30 CN 29 CN 28 OUTDOOR CONTROL TP T5 T3 T4 Figure 37 12K 115VAC Outdoor Unit Wiring Diagram 4 WAY VALVE OU TDOOR FAN CN 7 3 6 CN 31 PAN HEATER CN 15 CN 60 CRANKCASE HEATER CN...

Страница 18: ...nameplate If not do not start the equipment until you have consulted with the power company and the voltage condition has been corrected 7 Refer to the included user guide to operate the system using...

Страница 19: ...ireless remote Double Check Line Set Connections During operation the pressure of the refrigerant circuit will increase This may reveal leaks that were not present during your initial leak check Take...

Страница 20: ...20...

Отзывы: