Maximum  Line  Set

Length

Maximum Line Set

Length

Maximum 

Elevation - 

Outdooor 

Unit BELOW 

Indoor Unit

Maximum 

Elevation - 

Outdooor 

Unit ABOVE 

Indoor Unit

Minimum Line Set 

Length - 10 ft. (3m) 

Minimum Line Set 

Length - 10 ft.  (3m)

Outside Unit BELOW Indoor Unit

Outside Unit ABOVE Indoor Unit

Figure 32. Indoor and Outdoor Unit Elevation Relationships

Table 7.  Line Set Guide

Each system size has a line set length and vertical elevation parameters.

System 

Size (KBtu)

Line Set Diameters (in.)

Maximum Elevation 

Outdoor Unit BELOW 

Indoor Unit - Feet 

(Meter)

Maximum 

Elevation 

Outdoor Unit 

ABOVE Indoor 

Unit - Feet (Meter)

Maximum Line 

Set Length - 

Feet (Meters)

Additional Refrigerant for 

greater than 25 Foot Line Set 

Length

Liquid

Gas

009

1/4

3/8

33 (10)

33 (10)

82 (25)

For the additional charging, 

add 0.16 oz. for 1/4” liquid line 

and 0.32 oz. for 3/8” liquid line 

per foot.

012

1/4

1/2

33 (10)

33 (10)

82 (25)

018

1/4

1/2

66 (20)

66 (20)

98 (30)

024

3/8

5/8

66 (20)

66 (20)

98 (30)

Adding Refrigerant for Longer Line Set

The outdoor unit is factory­charged with refrigerant 

to accommodate up to 25 feet of line set.  For adding 

additional refrigerant for longer line sets, see “Table 7. 

Line Set Guide”.

Be sure to add the proper amount of additional refrigerant. 

Failure to do so may result in reduced performance. 

Leak Test and Evacuation

Air and moisture remaining in the refrigerant system will 

have undesirable effects as indicated below:

•  Pressure in the system rises.
• 

Operating current rises.

• 

Cooling or heating efficiency drops.

•  Moisture in the refrigerant circuit may freeze.
•  Water may lead to corrosion of parts in the refrigera­

tion system.

The line set between the indoor and outdoor units 

must be leak tested and evacuated to remove any non­

condensables and moisture from the system.

Leak Test

Use the following procedure to test for system leaks:

1.  Connect the manifold gauge set and dry nitrogen gas 

cylinder to the suction and gas service ports.

2. 

Open valve on nitrogen cylinder.

3.  Pressurize the system per the pressure test 

specifications  in  “Table  8.  Pressure  Test 

Specifications”.

4.  Check that the system pressure remains stable. If 

there is any movement check system for leaks.

5.  After the system is found to be free of leaks:

•  Close valve on nitrogen cylinder.
•  Relieve the nitrogen pressure by: loosening the 

charge hose connector at the nitrogen cylinder.

•  When the system pressure is reduced to normal, 

disconnect the hose from the cylinder.

Table 8. 

Pressure Test Specifications

Bar Psig

kPa

Duration

1

3

44

303

Minimum of 10 minutes

2

15

220

1517

Minimum of 10 minutes

3

32

470

3241

Minimum of 10 minutes

4

45

650

4482

1 hour. Stress test to prove the 

integrity of the complete installation.

5

32

470

3241

24 hours. Lower system pressure 

test, after confirmation No. 4 was 

successfully completed.

IMPORTANT

Use only oxygen-free nitrogen (OFN).

Triple Evacuation Procedure

A Micron or Torr gauge must be used for this procedure.

1.  Discharge the oxygen­free nitrogen and evacuate the 

system to a reading of 8000 Microns (8 Torr) using all 

service valves.

2. 

Break the vacuum by allowing nitrogen into the port 

connections (liquid and gas line pipes) until a positive 

pressure is achieved. 

Содержание MWHA009S4-1L

Страница 1: ...unit assembly must be thoroughly cleaned following final construction clean up All mini split operating conditions must be verified ac cording to these installation instructions MHA Series Units SING...

Страница 2: ...umbers Table 2 Component Catalog Number Cross Reference Product Capacity Voltage Lennox Model Number Catalog Numbers Wall Mounted Indoor Unit 9K 115V MWHA009S4 1L 17K07 Wall Mounted Indoor Unit 12K 11...

Страница 3: ...bility properties with mineral based oil and POE oil Polyolester it is not recommended to mix PVE oil with any other type of refrigerant oil Model Number Identification M WH A 009 S 4 1 P Unit Type WH...

Страница 4: ...1 2 13 1 2 13 MHA009S4S BOTTOM VIEW FRONT VIEW SIDE VIEW SIDE VIEW 12 5 8 322 11 1 4 286 2 3 8 60 3 5 8 92 DRAIN HOLE bottom of unit 11 3 4 298 Figure 2 9K Outdoor Unit Dimensions Inches mm BOTTOM VIE...

Страница 5: ...425 9 1 8 232 5 127 31 5 8 803 7 1 2 191 11 3 4 298 1 3 4 44 Figure 7 12K Indoor Unit Wall Plate Dimensions Inches mm MHWA018S4 Left Rear Hole 2 1 2 in 64 mm diameter Right Rear Hole 2 1 2 in 64 mm d...

Страница 6: ...m 10 254 Minimum 10 254 Minimum AIR FLO W AIR FLO W CLEARANCE NOTES FOR MULTIPLE UNITS If the height of the wall C is less than or equal to the height of the smallest unit A the distance from the unit...

Страница 7: ...cient space around unit for proper operation and maintenance Install unit a minimum of 3 feet 1m away from any antenna power cord line radio telephone security system or intercom Electrical interferen...

Страница 8: ...ded refrigerant piping connections and field provided flexible condensate piping are long enough to enable final field connections after unit is installed on wall mounting plate use field provided tap...

Страница 9: ...and vibration of the unit where the operation noise will not be amplified Choose a location where the hot air discharged from the unit or the operation noise will not be a nuisance to neighbors Avoid...

Страница 10: ...the outdoor unit as illustrated in Figure 24 Avoid Defrost Water Ice Hazard Air Inlet Air Outlet Figure 22 Outdoor Unit on Brackets above Snow Line Air Outlet Air Inlet 12 in 305 mm 79 in 2007 mm Fig...

Страница 11: ...oor Unit to Hanging Brackets If the outdoor unit is installed on field provided wall mounting brackets use lag bolts or equivalent to secure the outdoor unit to the bracket Minimum rear clearance can...

Страница 12: ...ections Male to Female Connection Table 5 Refrigerant Piping and Indoor Unit Connection Sizes Size Btuh Liquid Line in Suction Line in 9K 1 4 3 8 12K 1 4 1 2 18K 1 4 1 2 24K 3 8 5 8 A B CANT ON THE OU...

Страница 13: ...s Cooling or heating efficiency drops Moisture in the refrigerant circuit may freeze Water may lead to corrosion of parts in the refrigera tion system The line set between the indoor and outdoor units...

Страница 14: ...tween indoor and outdoor units Outdoor Unit Refer to unit nameplate for minimum circuit ampacity and maximum over current protection size Make all electrical power wiring connections at the outdoor un...

Страница 15: ...AC 4 16AWG 16A 20A Outdoor to Main Power L N and GND 09K 115VAC 3 16AWG 16A Indoor to Outdoor Wiring Communication Power 1 2 3 and GND 12K 115VAC 4 Stranded and unshielded 16AWG 15A 20A Outdoor to Mai...

Страница 16: ...4 Note Th e progra mmable wired controlle r and L VM use the sam e port CN4 03 CN 2 C N201 NOTE COMPONENT IN DASH LINE IS OPTIONAL OR FIELD WIRING CN402 S5 FOR REMOTE ON OF FACTORY SETTING MODE REMOTE...

Страница 17: ...CN 1 CN 2 CN 16 CN 50 CN 30 CN 29 CN 28 OUTDOOR CONTROL TP T5 T3 T4 Figure 37 12K 115VAC Outdoor Unit Wiring Diagram 4 WAY VALVE OU TDOOR FAN CN 7 3 6 CN 31 PAN HEATER CN 15 CN 60 CRANKCASE HEATER CN...

Страница 18: ...nameplate If not do not start the equipment until you have consulted with the power company and the voltage condition has been corrected 7 Refer to the included user guide to operate the system using...

Страница 19: ...ireless remote Double Check Line Set Connections During operation the pressure of the refrigerant circuit will increase This may reveal leaks that were not present during your initial leak check Take...

Страница 20: ...20...

Отзывы: