INSTALLATION

INSTRUCTIONS

©

2019 Lennox Industries Inc. 

Dallas, Texas, USA

WARNING

Improper installation, adjustment, alteration, ser vice 

or maintenance can cause property damage, personal 

injury or loss of life.
Installation and service must be performed by a li­

censed professional HVAC installer (or equivalent) or a 

service agency.

CAUTION

In order to avoid injury, take proper precaution when 

lifting heavy objects.

General

Refer to the Product Specifications bulletin (EHB) for more 

product information. These instructions are intended as 

a general guide and do not supersede local or national 

codes in any way. Authorities having jurisdiction should 

be consulted before installation.
This wall­mounted indoor unit is matched with an outdoor 

heat pump unit to create a mini­split system that uses 

HFC­410A refrigerant.

Use of Mini-Split System During 

Construction

Lennox does not recommend the use of its mini­split 

systems during any phase of construction. Very low return 

air temperatures, harmful vapors and operation of the unit 

with clogged or misplaced filters will damage the system.

However, mini­split systems may be used for cooling of 

buildings under construction, if the following  conditions 

are met:

• 

Air filter must be installed in the system and must be 

maintained during construction.

• 

Air filter must be replaced upon construction comple

­

tion.

•  The indoor wall unit assembly must be thoroughly 

cleaned following final construction clean-up.

• 

 All mini-split operating conditions must be verified ac

­

cording to these installation instructions.

MHA Series Units

SINGLE-ZONE MINI-SPLIT SYSTEM 

 

(115V and 208/230V)  

507927­01 6/2019 

Supersedes 3/2019

Table of Contents

General ...........................................................................1

Use of Mini­Split System During Construction................1

Included Parts.................................................................2

Catalog Numbers............................................................2

Model Number Identification

 ...........................................3

Typical System Components ..........................................4

System Dimensions ........................................................4

Outdoor Units ..............................................................4

Indoor Units .................................................................5

Indoor Unit Wall Mounts ..............................................5

System Clearances ........................................................5

Outdoor Unit ................................................................5

Indoor Unit ...................................................................6

Multiple Outdoor Units .................................................6

Torque Requirements for Caps and Fasteners...............7

Indoor Unit Installation ....................................................7

Unit Placement Considerations ...................................7

Determining Wall Mounting Plate Location ..................7

Installation of Wall Mounting Plate...............................7

Installation of Wall Sleeve............................................8

Installation of Indoor Unit on Wall Mounting Plate .......8

Indoor Unit Condensate Piping Connections ...............8

Outdoor Unit Installation

 .................................................9

Placement Considerations ...........................................9

Direct Sunlight, Rain and Ice Protection ......................9

Condensate Piping ....................................................10

Buried Refrigerant Pipe Protection ............................10

Securing the Outdoor Unit .........................................11

Refrigerant Piping Connections ....................................11

Adding Refrigerant for Longer Line Set ........................13

Leak Test and Evacuation

 ............................................13

Leak Test ...................................................................13

Triple Evacuation Procedure......................................13

Wiring Connections ......................................................14

Outdoor Unit  .............................................................14

Indoor Unit .................................................................14

Wiring Diagrams ........................................................16

Unit Start­Up .................................................................18

Troubleshooting ............................................................18

Test Run .......................................................................19

Pre-Checks ................................................................19

Procedure ..................................................................19

Test Run Checklist ........................................................19

Double­Check Line Set Connections............................19

Ambient Temperature is Below 63ºF (17ºC)

 .................19

THIS MANUAL MUST BE LEFT WITH THE OWNER 

FOR FUTURE REFERENCE

Содержание MWHA009S4-1L

Страница 1: ...unit assembly must be thoroughly cleaned following final construction clean up All mini split operating conditions must be verified ac cording to these installation instructions MHA Series Units SING...

Страница 2: ...umbers Table 2 Component Catalog Number Cross Reference Product Capacity Voltage Lennox Model Number Catalog Numbers Wall Mounted Indoor Unit 9K 115V MWHA009S4 1L 17K07 Wall Mounted Indoor Unit 12K 11...

Страница 3: ...bility properties with mineral based oil and POE oil Polyolester it is not recommended to mix PVE oil with any other type of refrigerant oil Model Number Identification M WH A 009 S 4 1 P Unit Type WH...

Страница 4: ...1 2 13 1 2 13 MHA009S4S BOTTOM VIEW FRONT VIEW SIDE VIEW SIDE VIEW 12 5 8 322 11 1 4 286 2 3 8 60 3 5 8 92 DRAIN HOLE bottom of unit 11 3 4 298 Figure 2 9K Outdoor Unit Dimensions Inches mm BOTTOM VIE...

Страница 5: ...425 9 1 8 232 5 127 31 5 8 803 7 1 2 191 11 3 4 298 1 3 4 44 Figure 7 12K Indoor Unit Wall Plate Dimensions Inches mm MHWA018S4 Left Rear Hole 2 1 2 in 64 mm diameter Right Rear Hole 2 1 2 in 64 mm d...

Страница 6: ...m 10 254 Minimum 10 254 Minimum AIR FLO W AIR FLO W CLEARANCE NOTES FOR MULTIPLE UNITS If the height of the wall C is less than or equal to the height of the smallest unit A the distance from the unit...

Страница 7: ...cient space around unit for proper operation and maintenance Install unit a minimum of 3 feet 1m away from any antenna power cord line radio telephone security system or intercom Electrical interferen...

Страница 8: ...ded refrigerant piping connections and field provided flexible condensate piping are long enough to enable final field connections after unit is installed on wall mounting plate use field provided tap...

Страница 9: ...and vibration of the unit where the operation noise will not be amplified Choose a location where the hot air discharged from the unit or the operation noise will not be a nuisance to neighbors Avoid...

Страница 10: ...the outdoor unit as illustrated in Figure 24 Avoid Defrost Water Ice Hazard Air Inlet Air Outlet Figure 22 Outdoor Unit on Brackets above Snow Line Air Outlet Air Inlet 12 in 305 mm 79 in 2007 mm Fig...

Страница 11: ...oor Unit to Hanging Brackets If the outdoor unit is installed on field provided wall mounting brackets use lag bolts or equivalent to secure the outdoor unit to the bracket Minimum rear clearance can...

Страница 12: ...ections Male to Female Connection Table 5 Refrigerant Piping and Indoor Unit Connection Sizes Size Btuh Liquid Line in Suction Line in 9K 1 4 3 8 12K 1 4 1 2 18K 1 4 1 2 24K 3 8 5 8 A B CANT ON THE OU...

Страница 13: ...s Cooling or heating efficiency drops Moisture in the refrigerant circuit may freeze Water may lead to corrosion of parts in the refrigera tion system The line set between the indoor and outdoor units...

Страница 14: ...tween indoor and outdoor units Outdoor Unit Refer to unit nameplate for minimum circuit ampacity and maximum over current protection size Make all electrical power wiring connections at the outdoor un...

Страница 15: ...AC 4 16AWG 16A 20A Outdoor to Main Power L N and GND 09K 115VAC 3 16AWG 16A Indoor to Outdoor Wiring Communication Power 1 2 3 and GND 12K 115VAC 4 Stranded and unshielded 16AWG 15A 20A Outdoor to Mai...

Страница 16: ...4 Note Th e progra mmable wired controlle r and L VM use the sam e port CN4 03 CN 2 C N201 NOTE COMPONENT IN DASH LINE IS OPTIONAL OR FIELD WIRING CN402 S5 FOR REMOTE ON OF FACTORY SETTING MODE REMOTE...

Страница 17: ...CN 1 CN 2 CN 16 CN 50 CN 30 CN 29 CN 28 OUTDOOR CONTROL TP T5 T3 T4 Figure 37 12K 115VAC Outdoor Unit Wiring Diagram 4 WAY VALVE OU TDOOR FAN CN 7 3 6 CN 31 PAN HEATER CN 15 CN 60 CRANKCASE HEATER CN...

Страница 18: ...nameplate If not do not start the equipment until you have consulted with the power company and the voltage condition has been corrected 7 Refer to the included user guide to operate the system using...

Страница 19: ...ireless remote Double Check Line Set Connections During operation the pressure of the refrigerant circuit will increase This may reveal leaks that were not present during your initial leak check Take...

Страница 20: ...20...

Отзывы: