 IMPORTANT

Use a thermocouple or thermistor electronic vacuum 

gauge that is calibrated in microns. Use an instrument 

capable of accurately measuring down to 50 microns.

 WARNING

Possible equipment damage.

Avoid deep vacuum operation. Do not use compressors 

to evacuate a system. Extremely low vacuum can cause 

internal arcing and compressor failure. Damage caused 

by deep vacuum operation will void warranty.

Evacuating the system of non-condensables is critical for 

proper  operation  of  the  unit.  Non-condensables  are  de-

fined as any gas that will not condense under tempera-

tures and pressures present during operation of an air 

conditioning  system.  Non-condensables  and  water  suc-

tion combine with refrigerant to produce substances that 

corrode copper piping and compressor parts.

Electrical

In the U.S.A., wiring must conform with current local codes 

and the current National Electric Code (NEC). In Canada, 

wiring must conform with current local codes and the cur

-

rent Canadian Electrical Code (CEC).
Refer to the furnace or air handler installation instructions 

for additional wiring application diagrams and refer to unit 

nameplate for minimum circuit ampacity and maximum 

overcurrent protection size.

24VAC TRANSFORMER

Use the transformer provided with the furnace or air han

-

dler for low-voltage control power (24VAC - 40 VA mini-

mum). 

 WARNING

Electric Shock Hazard. Can cause injury or 

death. Unit must be properly grounded in 

accordance with national and local codes.
Line voltage is present at all components 

when unit is not in operation on units with 

single-pole contactors. Disconnect all remote 

electric power supplies before opening 

access panel. Unit may have multiple power 

supplies.

Refer to the unit nameplate for minimum circuit ampacity, and maximum

fuse or circuit breaker (HACR per NEC). Install power wiring and properly

sized disconnect switch.

NOTE — Units are approved for use only with copper conductors.

Ground unit at disconnect switch or to an earth ground.

SIZE CIRCUIT AND INSTALL SERVICE

DISCONNECT SWITCH

NOTE — 24VAC, Class II circuit connections are made in the control

panel.

Install  room  thermostat  (ordered  separately)  on  an  inside  wall

approximately in the center of the conditioned area and 5 feet (1.5m) from

the floor. It should not be installed on an outside wall or where it can be

affected by sunlight or drafts.

THERMOSTAT

5 FEET

(1.5M)

INSTALL THERMOSTAT

SERVICE

DISCONNECT

SWITCH

MAIN FUSE BOX/

BREAKER PANEL

Содержание ML18XC2 Series

Страница 1: ...cal Unit Parts Arrangement 5 Operating Gauge Set and Service Valves 5 Unit Placement 7 Removing and Installing Louvered Panels 8 New or Replacement Line Set 9 Brazing Connections 11 Flushing Line Set...

Страница 2: ...the remaining two sides may be A clearance of 24 in must be maintained between two units 48 in 1219 mm clearance required on top of unit Model Number Identification Nominal Cooling Capacity 024 2 ton...

Страница 3: ...NNECTION 6 3 8 162 TOP VIEW BASE SECTION COMPRESSOR COIL DRAIN OUTLETS Around perimeter of base OPTIONAL UNIT STAND OFF KIT 4 Field Installed 111 4 3 8 4 3 8 4 3 8 4 3 8 6 3 8 162 111 111 111 111 4 3...

Страница 4: ...t ampacity MCA 14 6 20 2 26 2 32 2 Compressor Rated load amps 10 9 15 4 19 9 23 7 Locked rotor amps 61 92 127 151 Power factor 0 97 0 94 0 93 0 92 Outdoor Fan Motor Full load amps 1 1 1 4 2 6 Locked R...

Страница 5: ...ugly over the cap before tightening TABLE 1 Torque Requirements Parts Recommended Torque Service valve cap 8 ft lb 11 NM Sheet metal screws 16 ft lb 2 NM Machine screws 10 28 ft lb 3 NM Compressor bol...

Страница 6: ...7 8 9 10 11 12 1 12 TURN To Access Service Port A service port cap protects the service port core from contamination and serves as the primary leak seal 1 Remove service port cap with an appropriately...

Страница 7: ...ent of unit in relation to a window see the provided illustration in figure 3 detail A PLACING UNIT ON SLAB When installing unit at grade level the top of the slab should be high enough above grade so...

Страница 8: ...ons that may cause panels to be blown around and battered WARNING REMOVAL STEP 1 INSERT PANEL UNDER UNIT TOP CAP LIP AND LIFT SLIGHTLY TO CLEAR SIDE LIP OF PANEL FROM BASE STEP 2 PANEL INSTALLATION TO...

Страница 9: ...ge in the system No need to add oil in system with 20 pounds of refrigerant or less For systems over 20 pounds add one ounce for every five pounds of refrigerant Recommended topping off POE oils are M...

Страница 10: ...be used if line set is to be installed on exterior of outside wall PVC PIPE FIBERGLASS INSULATION CAULK OUTSIDE WALL VAPOR LINE WRAPPED WITH ARMAFLEX LIQUID LINE OUTSIDE WALL LIQUID LINE VAPOR LINE WO...

Страница 11: ...dous to your health Avoid breathing vapors or fumes from brazing operations Perform operations only in well ventilated areas Wear gloves and protective goggles or face shield to protect against burns...

Страница 12: ...SERVICE VALVE Flow regulated nitrogen at 1 to 2 psig through the low side refrigeration gauge set into the liquid line service port valve and out of the suction vapor line service port valve CUT AND D...

Страница 13: ...tions for the next step in preparing the unit WHEN BRAZING LINE SET TO SERVICE VALVES POINT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WARNING 1 FIRE PERSONAL INJURY OR PROPERTY DAMAGE...

Страница 14: ...ISTING INDOOR UNIT GAUGE MANIFOLD INVERTED CYLINDER CONTAINS CLEAN HCFC22 TO BE USED FOR FLUSHING LIQUID LINE SERVICE VALVE INLET DISCHARGE TANK RETURN CLOSED OPENED RECOVERY CYLINDER RECOVERY MACHINE...

Страница 15: ...reads and expose surface of the Teflon ring with refrigerantoil E Attach the liquid line assembly to the expansion valve Finger tighten and use an appropriately sized wrench to turn an additional 1 2...

Страница 16: ...losed connect the cylinder of HFC 410A refrigerant to the center port of the manifold gauge set Open the valve on the HFC 410A cylinder vapor only B Open the high pressure side of the manifold to allo...

Страница 17: ...r unit until the absolute pressure does not rise above 500 microns 29 9 inches of mercury within a 20 minute period after shutting off the vacuum pump and closing the manifold gauge valves F When the...

Страница 18: ...to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size 24VAC TRANSFORMER Use the transformer provided with the furnace or air han dler for low voltage control power 24...

Страница 19: ...Y1 Y2 C K1 S4 R C R W2 W1 Y2 C BLACK BLUE YELLOW Y Y1 G G W INDOOR UNIT TB1 THERMOSTAT A2 EL196E ML180E ML193E EL180E EL195E ML196E R W2 W1 G C BLACK BLUE YELLOW Y1 Y2 INDOOR UNIT A92 TB1 DS O W914 W9...

Страница 20: ...to shut off compressor operation The auto reset switch closes when the compressor cas ing temperature falls to 151 187 F 66 C 86 C and the compressor is re energized This single pole single throw SPS...

Страница 21: ...sure no obstructions restrict airflow to the outdoor unit Grass clippings leaves or shrubs crowding the unit can cause the unit to work harder and use more energy Keep shrubbery trimmed away from the...

Страница 22: ...all factory and field installed wiring for loose connections 3 After evacuation is complete open the liquid line and suction line service valves to release the refrigerant charge contained in outdoor...

Страница 23: ...pply Air Temperature Ambient Temperature Return Air Temperature System Refrigerant Charge Refer to manufacturer s information on unit or installation instructions for required subcooling and approach...

Отзывы: