Page 9

New or Replacement Line Set

This section provides information on new installation or re

-

placement of existing line set. If a new or replacement line 

set is not required, then proceed to Brazing Connections 

on page 11. 
If refrigerant lines are routed through a wall, seal and 

isolate the opening so vibration is not transmitted to the 

building. Pay close attention to line set isolation during 

installation of any HVAC system. When properly isolated 

from building structures (walls, ceilings. floors), the refrig-

erant lines will not create unnecessary vibration and sub

-

sequent sounds. 

REFRIGERANT LINE SET 

Field refrigerant piping consists of liquid and suction lines 

from the outdoor unit (braze connections) to the indoor 

unit  coil  (flare  or  braze  connections).  Use  Lennox  L15 

(braze,  non-flare)  series  line  set,  or  use  field-fabricated 

refrigerant lines as listed in table 2.

TABLE 2. Refrigerant Line Set – in. (mm)

Model

Field

Connections

Recommended Line Set

Liquid

Line

Suction

Line

Liquid

Line

Suction

Line

L15 Line Set

-024

3/8”

(10 mm)

3/4”

(19 mm)

3/8”

(10 mm)

3/4”

(19 mm)

L15-41: 15 ft.–50 ft.

(4.6 m–15 m)

-036

3/8”

(10mm)

7/8”

(22mm)

3/8”

(10 mm)

7/8” 

(22 mm)

L15-65: 15 ft.– 50 ft.

(4.6 m–15 m)

-048
-060

3/8”

(10mm)

1-1/8”

(29 mm)

3/8”

(10 mm)

1-1/8”

(29 mm)

Field-Fabricated

NOTE - 

Some applications may require a field-provided 7/8” to 1-1/8” adapter.

NOTE

 – 

When installing refrigerant lines longer than 50 

feet, contact Lennox Technical Support Product Applica-

tions for assistance or Lennox piping manual. To obtain 

the correct information from Lennox, be sure to communi-

cate the following points

:  

• 

Model (ML18XC2) and size of unit (e.g. -060).  

•   Line set diameters for the unit being installed as listed in 

table 4 and total length of installation.  

•   Number of elbows and if there is a rise or drop of the 

piping.

 IMPORTANT

Mineral  oils  are  not  compatible  with  HFC-410A.  If  oil 

must be added, it must be a Polyol ester oil.

The compressor is charged with sufficient Polyol ester oil 

for line set lengths up to 50 feet. Recommend adding oil to 

system based on the amount of refrigerant charge in the 

system. No need to add oil in system with 20 pounds of 

refrigerant or less. For systems over 20 pounds - add one 

ounce for every five pounds of refrigerant. 

Recommended topping-off POE oils are Mobil EAL ARC-

TIC 22 CC or ICI EMKARATE RL32CF. 

MATCHING WITH NEW OR EXISTING INDOOR COIL 

AND LINE SET 

The RFC1-metering line consisted of a small bore copper 

line that ran from condenser to evaporator coil. Refrig

-

erant was metered into the evaporator by utilizing tem

-

perature/pressure evaporation effects on refrigerant in the 

small RFC line. The length and bore of the RFC line cor

-

responded to the size of cooling unit. If the ML18XC2 is 

being used with either a new or existing indoor coil which 

is equipped with a liquid line which served as a meter

-

ing device (RFCI), the liquid line must be replaced prior to 

the installation of the ML18XC2 unit. Typically a liquid line 

used to meter flow is 1/4” in diameter and copper. 

LINE SET ISOLATION

 CAUTION

Brazing  alloys  and  flux  contain  materials  which  are 

hazardous to your health.
Avoid breathing vapors or fumes from brazing operations. 

Perform operations only in well-ventilated areas.

Wear gloves and protective goggles or face shield to 

protect against burns.
Wash hands with soap and water after handling brazing 

alloys and flux.

 IMPORTANT

The Clean Air Act of 1990 bans the intentional venting 

of refrigerant (CFC’s and HCFC’s) as of July 1, 1992. 

Approved methods of recovery, recycling or reclaiming 

must be followed. Fines and/or incarceration may be 

levied for non-compliance.

 IMPORTANT

If this unit is being matched with an approved line set 

or indoor unit coil that was previously charged with 

mineral oil, or if it is being matched with a coil which 

was manufactured before January of 1999, the coil and 

line set must be flushed prior to installation. Take care to 

empty all existing traps. Polyol ester (POE) oils are used 

in  Lennox  units  charged  with  HFC-410A  refrigerant. 

Residual mineral oil can act as an insulator, preventing 

proper heat transfer. It can also clog the expansion 

device and reduce system performance and capacity.

Failure to properly flush the system, per this instruction 

and the detailed Installation and Service Procedures 

manual will void the warranty.

Содержание ML18XC2 Series

Страница 1: ...cal Unit Parts Arrangement 5 Operating Gauge Set and Service Valves 5 Unit Placement 7 Removing and Installing Louvered Panels 8 New or Replacement Line Set 9 Brazing Connections 11 Flushing Line Set...

Страница 2: ...the remaining two sides may be A clearance of 24 in must be maintained between two units 48 in 1219 mm clearance required on top of unit Model Number Identification Nominal Cooling Capacity 024 2 ton...

Страница 3: ...NNECTION 6 3 8 162 TOP VIEW BASE SECTION COMPRESSOR COIL DRAIN OUTLETS Around perimeter of base OPTIONAL UNIT STAND OFF KIT 4 Field Installed 111 4 3 8 4 3 8 4 3 8 4 3 8 6 3 8 162 111 111 111 111 4 3...

Страница 4: ...t ampacity MCA 14 6 20 2 26 2 32 2 Compressor Rated load amps 10 9 15 4 19 9 23 7 Locked rotor amps 61 92 127 151 Power factor 0 97 0 94 0 93 0 92 Outdoor Fan Motor Full load amps 1 1 1 4 2 6 Locked R...

Страница 5: ...ugly over the cap before tightening TABLE 1 Torque Requirements Parts Recommended Torque Service valve cap 8 ft lb 11 NM Sheet metal screws 16 ft lb 2 NM Machine screws 10 28 ft lb 3 NM Compressor bol...

Страница 6: ...7 8 9 10 11 12 1 12 TURN To Access Service Port A service port cap protects the service port core from contamination and serves as the primary leak seal 1 Remove service port cap with an appropriately...

Страница 7: ...ent of unit in relation to a window see the provided illustration in figure 3 detail A PLACING UNIT ON SLAB When installing unit at grade level the top of the slab should be high enough above grade so...

Страница 8: ...ons that may cause panels to be blown around and battered WARNING REMOVAL STEP 1 INSERT PANEL UNDER UNIT TOP CAP LIP AND LIFT SLIGHTLY TO CLEAR SIDE LIP OF PANEL FROM BASE STEP 2 PANEL INSTALLATION TO...

Страница 9: ...ge in the system No need to add oil in system with 20 pounds of refrigerant or less For systems over 20 pounds add one ounce for every five pounds of refrigerant Recommended topping off POE oils are M...

Страница 10: ...be used if line set is to be installed on exterior of outside wall PVC PIPE FIBERGLASS INSULATION CAULK OUTSIDE WALL VAPOR LINE WRAPPED WITH ARMAFLEX LIQUID LINE OUTSIDE WALL LIQUID LINE VAPOR LINE WO...

Страница 11: ...dous to your health Avoid breathing vapors or fumes from brazing operations Perform operations only in well ventilated areas Wear gloves and protective goggles or face shield to protect against burns...

Страница 12: ...SERVICE VALVE Flow regulated nitrogen at 1 to 2 psig through the low side refrigeration gauge set into the liquid line service port valve and out of the suction vapor line service port valve CUT AND D...

Страница 13: ...tions for the next step in preparing the unit WHEN BRAZING LINE SET TO SERVICE VALVES POINT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WARNING 1 FIRE PERSONAL INJURY OR PROPERTY DAMAGE...

Страница 14: ...ISTING INDOOR UNIT GAUGE MANIFOLD INVERTED CYLINDER CONTAINS CLEAN HCFC22 TO BE USED FOR FLUSHING LIQUID LINE SERVICE VALVE INLET DISCHARGE TANK RETURN CLOSED OPENED RECOVERY CYLINDER RECOVERY MACHINE...

Страница 15: ...reads and expose surface of the Teflon ring with refrigerantoil E Attach the liquid line assembly to the expansion valve Finger tighten and use an appropriately sized wrench to turn an additional 1 2...

Страница 16: ...losed connect the cylinder of HFC 410A refrigerant to the center port of the manifold gauge set Open the valve on the HFC 410A cylinder vapor only B Open the high pressure side of the manifold to allo...

Страница 17: ...r unit until the absolute pressure does not rise above 500 microns 29 9 inches of mercury within a 20 minute period after shutting off the vacuum pump and closing the manifold gauge valves F When the...

Страница 18: ...to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size 24VAC TRANSFORMER Use the transformer provided with the furnace or air han dler for low voltage control power 24...

Страница 19: ...Y1 Y2 C K1 S4 R C R W2 W1 Y2 C BLACK BLUE YELLOW Y Y1 G G W INDOOR UNIT TB1 THERMOSTAT A2 EL196E ML180E ML193E EL180E EL195E ML196E R W2 W1 G C BLACK BLUE YELLOW Y1 Y2 INDOOR UNIT A92 TB1 DS O W914 W9...

Страница 20: ...to shut off compressor operation The auto reset switch closes when the compressor cas ing temperature falls to 151 187 F 66 C 86 C and the compressor is re energized This single pole single throw SPS...

Страница 21: ...sure no obstructions restrict airflow to the outdoor unit Grass clippings leaves or shrubs crowding the unit can cause the unit to work harder and use more energy Keep shrubbery trimmed away from the...

Страница 22: ...all factory and field installed wiring for loose connections 3 After evacuation is complete open the liquid line and suction line service valves to release the refrigerant charge contained in outdoor...

Страница 23: ...pply Air Temperature Ambient Temperature Return Air Temperature System Refrigerant Charge Refer to manufacturer s information on unit or installation instructions for required subcooling and approach...