VENTING
Capacity of Type B Double−Wall Vents with Single−Wall Metal Connectors
Serving a Single Category I Appliance
Height
H
(m)
(m)
Lateral
L
Vent and Connector Diameter − D (mm)
76mm
100mm
125mm
150mm
Appliance Input Rating in Thousands of Btu Per Hour
MIN
MAX
MIN
MAX
MIN
MAX
MIN
MAX
1.8
2.4
6.0
9.0
4.5
3.0
0
38
77
59
151
85
249
126
373
0.6
39
51
60
96
85
156
123
231
1.2
NA
NA
74
92
102
152
146
225
1.8
0
0.6
1.5
2.4
0
0.6
1.5
3.0
0
0.6
1.5
3.0
4.5
0
0.6
1.5
3.0
4.5
6.0
0
0.6
1.5
3.0
4.5
6.0
9.0
NA
NA
83
89
114
147
163
220
37
83
58
164
83
273
123
412
39
56
59
108
83
176
121
261
NA
NA
77
102
107
168
151
252
NA
NA
90
95
122
161
175
243
37
87
57
174
82
293
120
444
39
61
59
117
82
193
119
287
52
56
76
111
105
185
148
277
NA
NA
97
100
132
171
188
261
36
93
56
190
80
325
116
499
38
69
57
136
80
225
115
337
51
63
75
128
102
216
144
326
NA
NA
95
116
128
201
182
308
NA
NA
NA
NA
158
186
220
290
35
96
54
200
78
346
114
537
37
74
56
148
78
248
113
375
50
68
73
140
100
239
141
363
NA
NA
93
129
125
223
177
344
NA
NA
NA
NA
155
208
216
325
NA
NA
NA
NA
186
192
254
306
34
99
53
211
76
372
110
584
37
80
55
164
76
281
109
429
49
74
72
157
98
271
136
417
NA
NA
91
144
122
255
171
397
NA
NA
115
131
151
239
208
377
NA
NA
NA
NA
181
223
246
357
NA
NA
NA
NA
NA
NA
NA
NA
NOTE − Single appliance venting configurations with zero lateral lengths are assumed to have no elbows in the vent system. For all other
vent configurations, the vent system is assumed to have two 90° elbows. For each additional 90° elbow or equivalent (for example two 45°
elbows equal one 90° elbow) beyond two, the maximum capacity listed in the venting table should be reduced by 10 percent (0.90 x maxi-
mum listed capacity).