12
VENTING
16 − Vent connectors serving Category I appliances shall
not be connected to any portion of mechanical draft
systems operating under positive pressure such as
Category III or IV venting systems.
17 − If vent connectors are combined prior to entering the
common vent, the maximum common vent capacity
listed in the common venting tables must be reduced by
10%, the equivalent of one 90° elbow (0.90 x maximum
common vent capacity).
18 − The common vent diameter must always be at least as
large as the largest vent connector diameter.
19 − In no case, shall the vent connector be sized more than
two consecutive table size diameters over the size of
the draft hood outlet or flue collar outlet.
20 − Do not install a manual damper, barometric draft regu-
lator or flue restrictor between the furnace and the
chimney.
21 − When connecting this appliance to an existing dedi-
cated or common venting system, you must inspect the
venting system’s general condition and look for signs
of corrosion. The existing vent pipe size must conform
to these instructions and the provided venting tables. If
the existing venting system does not meet these re-
quirements, it must be resized.
Capacity of Type B Double−Wall Vents with Type B Double−Wall Connectors
Serving a Single Category I Appliance
Height
H
(m)
(m)
Lateral
L
Vent and Connector Diameter − D (mm)
76mm
100mm
125mm
150mm
Appliance Input Rating in Thousands of Btu Per Hour
MIN
MAX
MIN
MAX
MIN
MAX
MIN
MAX
1.8
2.4
4.5
3.0
6.0
9.0
0
0
78
0
152
0
251
0
375
0.6
13
51
18
97
27
157
32
232
1.2
21
49
30
94
39
153
50
227
1.8
25
46
36
91
47
149
59
223
0
0
84
0
165
0
276
0
415
0.6
12
57
16
109
25
178
28
263
1.5
23
53
32
103
42
171
53
255
2.4
28
49
39
98
51
164
64
247
0
0
88
0
175
0
295
0
447
0.6
12
61
17
118
23
194
26
289
1.5
23
57
32
113
41
187
52
280
3.0
30
51
41
104
54
176
67
267
0
0
94
0
191
0
327
0
502
0.6
11
69
15
136
20
226
22
339
1.5
22
65
30
130
39
219
49
330
3.0
29
59
40
121
51
206
64
315
4.5
35
53
48
112
61
195
76
301
0
0
97
0
202
0
349
0
540
0.6
10
75
14
149
18
250
20
377
1.5
21
71
29
143
38
242
47
367
3.0
28
64
38
133
50
229
62
351
4.5
34
58
46
124
59
217
73
337
6.0
48
52
55
116
69
206
84
322
0
0
100
0
213
0
374
0
587
0.6
9
81
13
166
14
283
18
432
1.5
21
77
28
160
36
275
45
421
3.0
27
70
37
150
48
262
59
405
4.5
33
64
44
141
57
249
70
389
6.0
56
58
53
132
66
237
80
374
9.0
NA
NA
73
113
88
214
104
346
NOTE − Single appliance venting configurations with zero lateral lengths are assumed to have no elbows in the vent system. For all other
vent configurations, the vent system is assumed to have two 90° elbows. For each additional 90° elbow or equivalent (for example two 45°
elbows equal one 90° elbow) beyond two, the maximum capacity listed in the venting table should be reduced by 10 percent (0.90 x maxi-
mum listed capacity).