1 - Compressor Contactor K1

The compressor is energized by a contactor located in the

control box. See figures 1 and 2. Contactors are SPST in

single phase units and 3PST in three phase units. The conĆ
tactor is energized by indoor thermostat terminal Y when

thermostat demand is present.
The contactor coil is energized by 24VAC supplied by the
indoor unit. All other controls in the outdoor unit are powĆ

ered  by  line  voltage.  Refer  to  unit  wiring  diagram.  The

HS24 is not equipped with a line voltage to 24V transformĆ
er.

2 - Dual Capacitor C12

The compressor and fan in single phase units use permanent
split capacitor motors. The capacitor is located inside the unit

control box (see figure 1). A single dual" capacitor (C12) is

used for both the fan motor and the compressor (see unit wirĆ
ing diagram). The fan side and the compressor side of the caĆ

pacitor have different MFD ratings. See table 1 for dual capacĆ

itor ratings.

TABLE 1

Unit

MFD

VAC

HS24 (C12) DUAL CAPACITOR RATING

HS24-261

HS24-311/411

HS24-461

HS24-511

5

30

5

45

5

370

10

50

45

Terminal

FAN

HERM

FAN

HERM

FAN

HERM

FAN

HERM

440

HS24-141/211

5

25

FAN

HERM

HS24-651

10

60

FAN

HERM

3 - Start Capacitor C7

All HS24-461, 511, 651 units use a start capacitor (C7) wired
in parallel with the compressor side of the dual capacitor. The

capacitor is located inside the unit control box (see figure 1).

C7 is switched off by potential relay (K31) when the compresĆ
sor nears full speed.ĂSee table 2 for startĂcapacitor ratings.

TABLE 2

Unit

MFD

VAC

HS24 START CAPACITOR RATING

HS24-461

HS24-511

189-227

HS24-651

330

189-227

330

135-155

320

4 - Transformer T5

Transformer T5 is used on all J" voltage units. T5 is used as
a stepĆdown transformer for fan B4. T5 is rated at 3.4 VA with

a 575 volt primary and a 460 volt secondary.

5 -  Potential (Start) Relay K31

All HS24-461, 511, 651 series units use a potential relay

which controls the operation of the starting circuit. The poĆ
tential relay is located inside the unit control box (see figure

1). The relay is normally closed when contactor K2 is deĆenĆ

ergized. When K1 energizes, the compressor immediately
begins  startĆup.  K31  remains  closed  during  compressor

startĆup and the start capacitor remains in the circuit. As the

compressor gains speed, K31 is energized. When K31 enĆ
ergizes, the contacts open and the start capacitor is taken

out of the circuit.

6 - Fan Capacitor C1

The fan in threeĆphase units use permanent split capacitor

motors. A single capacitor is used for the fan motor. The caĆ
pacitor is located inside the unit control box (see figure 2).

Table 3 shows the ratings of C1.

TABLE 3

Unit

MFD

VAC

HS24 FAN CAPACITOR RATING (C1)

HS24-413/463

HS24-513/653Y,G

HS24-651J

10

370

10

370

5

370

B - Compressor

Table 4 shows the specifications of compressors used in

HS24 series units.

TABLE 4

Unit

Phase

LRA

RLA

Oil

fl.oz.

HS24-211

HS24-311

HS24-511

1

1

1

49

71.0

110

32*

54*

45*

**Shipped  with  60%  Zerol  300Ċ40%  Sontex  200LT.  A  60/40  mixture  of 

Zerol 300/Sontex 200LT may be used if additional oil is required.

9.6

11.7

20.5

HS24-141

1

26.3

4.8

HS24-413

3

32.8

54*

4.6

HS24-651

1

147

24

65*

15**

HS24-653
HS24-653

3
3

150

73

65*
65*

16

8.0

HS24-463

3

130

70*

11.9

460

HS24-413

3

65.1

54*

9.2

208/230

HS24-653

3

50.0

6.4

65*

HS24-461

1

105

70*

16.4

HS24-411

1

86.7

54*

14.2

HS24-261

1

56

45*

10.9

HS24-463

3

64

70*

5.6

HS24-513

3

92.0

54*

13.4

HS24-513

3

46.0

54*

6.7

HS24-513

Voltage

208/230
208/230
208/230
208/230

208/230

208/230

208/230

208/230

208/230

208/230

208/230

460

460

460

575

575

HS24 COMPRESSOR SPECIFICATIONS

3

44.0

54*

5.3

*Shipped  with  conventional  white  oil  (Sontex  200LT)  or  3GS.  3GS  oil  may

be used if additional oil is required.

Содержание HS24-141

Страница 1: ...ated and operates only when required Several models are available in sizes ranging from 1 through 5 tons This manual is divided into sections which discuss the ma jor components refrigerant system cha...

Страница 2: ...2 2 1 2 3 3 1 2 4 and 5 ton capacities All major components indoor blower coil must be matched according to Lennox recommendations for the compressor to be covered under warranty Refer to the En gine...

Страница 3: ...ted at 3 4 VA with a 575 volt primary and a 460 volt secondary 5 Potential Start Relay K31 All HS24 461 511 651 series units use a potential relay which controls the operation of the starting circuit...

Страница 4: ...n exhaust cycle At this instant the compression is begin ning 1 The roller rotates and compression continues 2 When the blade is fully extended the suction port is separated from the discharge port 3...

Страница 5: ...s and up FIGURE 8 Access to the condenser fan motor on all units is gained by removing the six 6 screws securing the fan guard See figures 8 and 9 The condenser fan motor is attached to the fan guard...

Страница 6: ...ve is a front and back seating valve When the valve is backseated the service port is iso lated from the system CAUTION The service port cap is used to seal the liquid line service valve Access to ser...

Страница 7: ...Suction valves are non backseating Do not at tempt to backseat this valve Attempts to backseat this valve will cause snap ring to explode from valve body under pressure of refrigerant Person al injur...

Страница 8: ...cuating the System 1 Attach gauge manifold Connect vacuum pump with vacuum gauge to center port of gauge manifold With both manifold service valves open start pump and evacuate indoor coil and refrige...

Страница 9: ...move refrigerant from system to increase ap proach temperature TABLE 10 Model Liquid Temp Minus Ambient Temp F HS24 261 HS24 311 HS24 411 413 HS24 461 463 APPROACH METHOD EXPANSION VALVE SYSTEMS 4 1 8...

Страница 10: ...0 9 8 6 5 4 2 15 15 14 14 13 13 12 12 11 10 10 9 20 19 19 18 18 17 17 16 15 15 14 13 17 16 16 15 15 14 14 13 13 12 11 10 D Oil Charge Table 4 on page 3 shows the factory oil charge in HS24 units V Mai...

Страница 11: ...emand 5 Cooling demand is satisfied 6 Contactor K1 is de energized 7 K1 1 opens and compressor B1 and condenser fan motor B4 are de energized and stop immediately Cooling With Start Components 8 Cooli...

Страница 12: ...i cal or electronic Cooling 1 Cooling demand initiates at Y1 in the thermostat 2 Compressor contactor K1 is energized 3 K1 1 N O closes energizing terminal C of compressor B1 and condenser fan motor B...

Отзывы: