background image

Page 15

TABLE 6

Defrost Control Board Diagnostic (5 strike)

LED 1

LED 2

Condition

Possible Cause(s)

Solution

OFF

OFF

Power problem

1

 No power (24V) to board terminals

R & C.

Board failure.

1

 Check control transformer power

(24V).

If power is available and LED(s) are

unlit, replace board and all sensors.

ON

ON

Coil sensor problem

1

 Coil temperature outside of sensor

range.

2

 

Faulty sensor wiring connections at

board or poor sensor contact on coil.

3

 

Sensor failure.

1

 Sensor function will resume when

coil temperature is between −20°F
and 110°F.

2

 

Check sensor wiring connections at

board and sensor contact on coil.

3

 

Replace board and all sensors.

OFF

ON

Ambient sensor problem

1

 Ambient temperature outside of

sensor range.

Faulty sensor wiring connections at

board or sensor.

3

 

Sensor failure.

1

 Sensor function will resume when

coil temperature is between −20°F
and 110°F.

2

 

Check sensor wiring connections at

board and sensor.

Replace board and all sensors.

FLASH

FLASH

Normal operation

Unit operating normally or in standby
mode.

None required.

ON

OFF

5−Strike pressure lockout
(Short test pins or reset
24V power to board to
override lockout)

1

 Restricted air flow over indoor or

outdoor coil.

2

 

Improper refrigerant charge.

1

 

Remove any blockages or restric-

tions. Check outdoor fan motor for
proper operation.

Check approach, superheat & sub-

li

t

t

ON

FLASH

Low pressure switch circuit
open during Y1 demand

2

 

Improper refrigerant charge.

3

 

Improper metering device opera-

ti

pp

,

p

cooling temperatures.

Check system pressures. Repair

leaks. Replace metering device.

FLASH

ON

High pressure switch or
discharge thermostat
switch circuit open during
Y1 demand

p p

g

p

tion.

4

 

Poor contact between coil sensor

and coil.

leaks. Replace metering device.

4

 

Make sure that sensor is properly

positioned on coil and that firm con-
tact is established. Refer to service
manual for proper placement.

ALTERNATING

FLASH

ALTERNATING

FLASH

5−minute delay
(Jumper test pins to over-
ride delay)

Thermostat demand for cooling or
heat pump operation. Unit operating
in 5−minute anti−short−cycle mode.

None required.

Demand Defrost Operation

The demand defrost control board initiates a defrost cycle based on either frost detection or time.

Frost Detection

 − If the compressor runs longer than 34 minutes and the actual difference between the clear coil and frosted coil temperatures exceeds

the maximum difference allowed by the control, a defrost cycle will be initiated.

IMPORTANT − The demand defrost control board will allow a greater accumulation of frost and will initiate fewer defrost cycles than a time/temperature
defrost system.

Time

 − If 6 hours of heating mode compressor run time has elapsed since the last defrost cycle while the coil temperature remains below 35°F (2°C),

the demand defrost control will initiate a defrost cycle.

Actuation

 − When the reversing valve is de−energized, the Y1 circuit is energized, and the coil temperature is below 35°F (2°C), the board logs the

compressor run time. If the board is not calibrated, a defrost cycle will be initiated after 34 minutes of heating mode compressor run time. The control
will attempt to self−calibrate after this (and all other) defrost cycle(s). Calibration success depends on stable system temperatures during the 20−minute
calibration period. If the board fails to calibrate, another defrost cycle will be initiated after 90 minutes of heating mode compressor run time. Once the
defrost board is calibrated, it will use demand defrost logic to initiate a defrost cycle. A demand defrost system initiates defrost when the difference be-
tween the clear coil and frosted coil temperatures exceeds the maximum difference allowed by the control OR after 6 hours of heating mode compressor
run time has been logged since the last defrost cycle.

Termination

 − The defrost cycle ends when the coil temperature exceeds the termination temperature or after 14 minutes of defrost operation. If the

defrost is terminated by the 14−minute timer, another defrost cycle will be initiated after 34 minutes of run time.

Test Mode

 − When Y1 is energized and 24V power is being applied to the board, a test cycle can be initiated by placing the termination temperature

jumper across the Test" pins for 2 to 5 seconds. If the jumper remains across the Test" pins longer than 5 seconds, the control will ignore the test pins
and revert to normal operation. The jumper will initiate one cycle per test.

Operational Description

The defrost control board has three basic operational
modes: normal, defrost, and calibration.

Normal Mode

The demand defrost board monitors the O line, to deter-
mine the system operating mode (heat/cool), outdoor am-
bient temperature, coil temperature (outdoor coil) and
compressor run time to determine when a defrost cycle is
required.

Defrost Mode

When a defrost cycle is initiated, the control energizes the
reversing valve solenoid and turns off the condenser fan.
The control will also put 24VAC on the W1 (auxiliary heat)
line. The unit will stay in this mode until either the coil sen-
sor temperature is above the selected termination temper-
ature, the defrost time of 14 minutes has been completed,
or the room thermostat demand cycle has been satisfied.
(If the temperature select shunt is not installed, the default
termination temperature will be 100°F.) If the room

thermostat demand cycle terminates the cycle, the defrost
cycle will be held until the next room thermostat demand
cycle. If the coil sensor temperature is still below the se-
lected termination temperature, the control will continue
the defrost cycle until the cycle is terminated in one of the
methods mentioned above. If a defrost is terminated by
time and the coil temperature did not remain above 35°F
(2°C) for 4 minutes, the control will go into  the 34−minute
Time/Temperature mode.

Calibration Mode

The board is considered uncalibrated when power is ap-
plied to the board, after cool mode operation, or if the coil
temperature exceeds the termination temperature when it
is in heat mode.

Calibration of the board occurs after a defrost cycle to en-
sure that there is no ice on the coil. During calibration, the
temperature of both the coil and the ambient sensor are
measured to establish the temperature differential which is
required to allow a defrost cycle.

Содержание HPXA19

Страница 1: ...of this R410A unit are higher than pressures in R22 units Always use service equipment rated for R410A WARNING Improper installation adjustment alteration service or maintenance can cause property da...

Страница 2: ...99 0 99 Outdoor Coil F M t Full load amps 0 8 0 8 2 8 1 7 1 7 Fan Motor Locked rotor amps 2 2 Not Applicable 3 1 3 1 OPTIONAL ACCESSORIES MUST BE ORDERED EXTRA Compressor Hard Start Kit Factory Instal...

Страница 3: ...ORBITING SCROLL DISCHARGE SUCTION CROSS SECTION OF SCROLLS TIPS SEALED BY DISCHARGE PRESSURE DISCHARGE PRESSURE The counterclockwise orbiting scroll draws gas into the out er crescent shaped gas pocke...

Страница 4: ...ing for second stage Second stage high capacity is achieved by blocking the bypass ports figure 5 bypass ports closed with a slider ring The slider ring begins in the open position and is con trolled...

Страница 5: ...ch Procedure 1 Turn main power OFF to outdoor unit 2 Adjust room thermostat set point above heating op eration on heat pump or below cooling operation the room temperature 5 F 3 Remove control access...

Страница 6: ...ctifier plug Listen for a click as the solenoid is energized See figure 6 compressor solenoid fusite terminals compressor fusite terminals meter rectifier plug leads apply 24vac FIGURE 6 3 Unplug the...

Страница 7: ...is normally closed and is permanently adjusted to trip open at 640 10 psi and close at 448 10 psi See fig ure 13 for switch location E Capacitor C12 The compressor in XP19 024 036 048 and 060 units us...

Страница 8: ...et to close at 40 2 F on a temperature drop and reset at 50 2 F on a temperature rise TABLE 2 Control Setpoints Low Ambient Thermostat Adjustable Range Factory Setting Min Max Cut In Close on Temperat...

Страница 9: ...s controlled by the compressor con tactor See ELECTRICAL DATA and SPECIFICATIONS section for more information See figure 11 if condenser fan motor replacement is necessary Rain shield location is crit...

Страница 10: ...er to maintain constant airflow cfm Motor rpm is continually adjusted internally to maintain constant static pressure against the fan blade The control ler monitors the static work load on the motor a...

Страница 11: ...rb moisture the dryness of the system must be verified any time the refrigerant sys tem is exposed to open air A compressor oil sample must be taken to determine if excessive moisture has been introdu...

Страница 12: ...s in all units are equipped with a 70 watt belly band type crankcase heater HR1 prevents liquid from ac cumulating in the compressor HR1 is controlled by the crankcaseheater thermostat X Crankcase hea...

Страница 13: ...sure switch is present check Flash Code 2 information 4 If low pressure switch is present check Flash Code 1 information Yellow Alert Flash Code 4 Locked Rotor 1 Run capacitor has failed 2 Low line vo...

Страница 14: ...e off the compressor and the strike counter in the board will count one strike S87 is ignored during certain conditions During the defrost cycle and 90 seconds after the termination of defrost When th...

Страница 15: ...nitiated after 34 minutes of heating mode compressor run time The control will attempt to self calibrate after this and all other defrost cycle s Calibration success depends on stable system temperatu...

Страница 16: ...connection of gauge manifold during charging procedure Figure 22 shows HPXA19 refrigerant flow and gauge manifold connections TABLE 7 M d l Valve Field Size Connections Recommended Line Set Model Liq...

Страница 17: ...nnect gauge to the service port 3 When testing is complete replace service port cap Tighten finger tight then an additional 1 6 turn To Open Service Valve 1 Remove stem cap with an adjustable wrench 2...

Страница 18: ...that can re sult in personal injury or death Using an Electronic Leak Detector 1 Connect a cylinder of R410A to the center port of the manifold gauge set 2 With both manifold valves closed open the v...

Страница 19: ...losing the manifold gauge valves 9 When the absolute pressure requirement above has been met disconnect the manifold hose from the vacu um pump and connect it to an upright cylinder of R410A refrigera...

Страница 20: ...r best results indoor temperature should be 70 F 21 C to 80 F 26 C Monitor system pressures while charging 1 Record outdoor ambient temperature using a digital thermometer 2 Attach high pressure gauge...

Страница 21: ...244 136 231 133 232 134 249 126 75 23 9 256 145 282 139 263 139 266 136 289 134 85 29 4 302 145 325 142 305 142 309 139 330 140 95 35 0 349 147 377 144 354 145 359 142 378 143 105 40 6 403 149 428 14...

Страница 22: ...506 5 43 125 0 74 214 0 105 340 5 136 512 9 44 127 3 75 217 4 106 345 3 137 519 3 45 129 7 76 220 9 107 350 1 138 525 8 46 132 2 77 224 4 108 355 0 139 532 4 47 134 6 78 228 0 109 360 0 140 539 0 48...

Страница 23: ...POE oil VI MAINTENANCE WARNING Electric shock hazard Can cause inju ry or death Before attempting to per form any service or maintenance turn the electrical power to unit OFF at dis connect switch es...

Страница 24: ...Page 24 VII DIAGRAM OPERATING SEQUENCE HPXA19 024 036 048 060...

Страница 25: ...nergized The slider ring re mains open limiting compressor to low capacity B Ambient temperature BELOW S23 low ambient thermostat setting S23 closes shunting Y1 and Y2 1 Internal wiring de energizes t...

Страница 26: ...Page 26 1 2 3 4 HPXA19 038 with Variable Speed Motor...

Страница 27: ...pen limiting compressor to low capacity B Ambient temperature BELOW S23 low ambient setting S23 closes shunting Y1 and Y2 1 Internal wiring de energizes terminal O by heating mode selection de energiz...

Отзывы: