30
8.8.6
Indoor evaporator high-temperature protection at heating mode
Condition
T= Indoor exchanger temp.
Compressor
Outdoor fan
T<TE8
On
On
TE8<T<TE7
On
Off
Indoor exchanger temp. up
T>TE7
Off
Off
T>TE9
Off
Off
Indoor exchanger temp. down
T<TE9
On
On
8.8.7. The louver opens to Standard Angle ANGLHEAT when power is on for the first time
8.9
Defrosting operation (Available for heating only).
8.9.1
Defrosting condition: Defrosting starts when either of the following
①
&
②
:
①
A and B are satisfied:
A: The compressor keeps running for 40 minutes or more.
B: The temperature difference of evaporator and room temperature meets one of the following:
Temp. of evaporator---room temp.
Fan speed is high
≤
TH
DEFROST
Fan speed is mid
≤
TM
DEFROST
Fan speed is low
≤
TL
DEFROST
Breeze
Meet only if it is Breeze
②
Calculate from the end of latest defrost, evaporator high temp. protection only closes outdoor fan
with the compressor still running. Add up to 90 minutes.
8.9.2 Defrosting time
If the temp. difference condition
①
is satisfied for less than 40 minutes, this can be regarded as
severe frosting. The defrosting time is 10 minutes.
If the temp. difference condition
②
is satisfied for more than 40 minutes, the defrosting time is 6
minutes.
If the temp. difference condition
①
is satisfied out of 40 minutes, generally the defrosting time is 6
minutes, after three continuous 6-minute defrost, the fourth should be 10 minutes defrost. The
circulation is as following:
→
7.5-minute defrost
→
7.5-minute defrost
→
7.5-minute defrost
→
10-minute defrost
→
8.9.3 Ending condition of defrosting
If one of following conditions is satisfied, end the defrost and turn into heating mode:
Содержание GCM07N
Страница 3: ...2 1 Features 1 1Compact design 1 2High efficiency and quiet operation 1 3A class energy level ...
Страница 6: ...5 3 Dimensions 3 1 Indoor unit GCM 07N GHM07N GCM09N GHM09N 3 2 Indoor unit GCM 12N GHM12N ...
Страница 7: ...6 3 2 Indoor unit GCM 18N GHM18N ...
Страница 8: ...7 3 4 Outdoor unit GCM 07N GHM07N 3 5 Outdoor unit GCM 09N1 GHM09N GCM12N GHM12N ...
Страница 9: ...8 GCM 18N GHM18N 12 5 ...
Страница 10: ...9 4 Refrigeration cycle diagram ...
Страница 24: ...23 7 2 2 Heating cooling 7 2 2 1 GHM07N GHM09N GHM12N I NDO OR UNI T O UTD OO R UNI T ...
Страница 30: ...29 T 0 High ...