9.3.3 Failure phenomenon
Failure phenomenon
Operation lamp
Timer lamp
Indoor fan speed has been out of control for over 1 minute
☆
X
Indoor room temp. or evaporator sensor is open circuit or short circuit
☆
On
Over current protection of the compressor occurs 4 times
X
☆
EEROM error
On
☆
No over-zero signal
☆
☆
r
Extinguish
☆
☆
☆
☆
Flash at 5Hz
9.3.3.1 Operation lamp flashes and Timer lamp off.
9.3.3.2 Operation lamp flashes and Timer lamp on.
9.3.3.3 Operation lamp off and Timer lamp flashes
No Yes
Yes
No
9.3.3.4 Operation lamp on and Timer lamp flashes
EEROM error, indoor PCB is defective.
9.3.3.5 Operation lamp flashes, Timer lamp flashes .
This is alarm signal when the main chip can’t detect over-zero signal. When such failure occurs, the main
control board must have fault.
Operation lamp off and Timer lamp flashes
Indoor PCB is defective
Power supply fault
Outdoor unit fault (such as the compressor)
The voltage of power supply is too low (less than 187V)?
After changing the main control board, check if the failure releases
.
Is connector connection good?
Is voltage being applied to the fan motor?
Fan motor is defective
Repair the connector
Indoor PCB is defective
No
Yes
Yes
No
Is connection to connector good?
Replace the sensor
Repair connector
Yes
No
Yes
Содержание GCM07N
Страница 3: ...2 1 Features 1 1Compact design 1 2High efficiency and quiet operation 1 3A class energy level ...
Страница 6: ...5 3 Dimensions 3 1 Indoor unit GCM 07N GHM07N GCM09N GHM09N 3 2 Indoor unit GCM 12N GHM12N ...
Страница 7: ...6 3 2 Indoor unit GCM 18N GHM18N ...
Страница 8: ...7 3 4 Outdoor unit GCM 07N GHM07N 3 5 Outdoor unit GCM 09N1 GHM09N GCM12N GHM12N ...
Страница 9: ...8 GCM 18N GHM18N 12 5 ...
Страница 10: ...9 4 Refrigeration cycle diagram ...
Страница 24: ...23 7 2 2 Heating cooling 7 2 2 1 GHM07N GHM09N GHM12N I NDO OR UNI T O UTD OO R UNI T ...
Страница 30: ...29 T 0 High ...