26
8.4
Protection
8.4.1 3 minutes delay at restart for compressor.
8.4.2 Sensor protection at open circuit and breaking disconnection
8.4.3 Fan Speed is out of control. When Indoor Fan Speed is too high(higher than High Fan+300RPM)or
too low(lower than 400RPM), the unit stops and LED displays failure information and can’t returns to
normal operation automatically.
8.4.4 Cross Zero signal error warning. If there is no Cross Zero signals in 4 minutes, the unit stops and LED
displays failure information and can’t returns to normal operation automatically.
8.4.5 The current protection of the compressor
Condition
Indoor fan
Compressor
Outdoor fan
Remark
I< I
RESTORE
On
On
On
On
On
Off
Heating mode
I
RESTORE
<I< I
FAN
Low speed
On
On
Cooling mode
I
FAN
<I<I
5MIN
Off
Off
After 5 Minutes
Current up
I
5MIN
<I< I
3SEC
Off
Off
After 3 Seconds
I
5MIN
<I< I
3SEC
Off
Off
After 3 Seconds
I
FAN
<I<I
5MIN
Off
Off
After 5 Minutes
On
On
Off
Heating mode
I
RESTORE
<I< I
FAN
Low speed
On
On
Cooling mode
Current down
I< I
RESTORE
On
On
On
If compressor turns off for continuously 4 times due to current protection in 5 minutes from
Compressor On, the unit stops and LED displays failure information and can’t returns to normal
operation automatically.
8.5
Fan-only mode
Fan speed is high/mid/low/ Auto
8.6 Cooling mode
The 4-way valve is closed at cooling mode.
The action of the compressor and the outdoor fan:
Condition
T=Indoor Temp.
Ts=Setting Temp.
Compressor
Outdoor fan
T> Ts+1
On
On
Room temp. up
T<Ts+1
Off
Off
T> Ts
On
On
Room temp. down
T<Ts
Off
Off
Auto fan at cooling mode:
Condition
T=Indoor Temp.-Setting Temp.
Indoor fan speed
T<4
Low
4 <T<5
Med.
Room temp. up
T>5
High
T> 4
High
1 <T<4
Med.
Room temp. down
T<1
Low
Содержание GCM07N
Страница 3: ...2 1 Features 1 1Compact design 1 2High efficiency and quiet operation 1 3A class energy level ...
Страница 6: ...5 3 Dimensions 3 1 Indoor unit GCM 07N GHM07N GCM09N GHM09N 3 2 Indoor unit GCM 12N GHM12N ...
Страница 7: ...6 3 2 Indoor unit GCM 18N GHM18N ...
Страница 8: ...7 3 4 Outdoor unit GCM 07N GHM07N 3 5 Outdoor unit GCM 09N1 GHM09N GCM12N GHM12N ...
Страница 9: ...8 GCM 18N GHM18N 12 5 ...
Страница 10: ...9 4 Refrigeration cycle diagram ...
Страница 24: ...23 7 2 2 Heating cooling 7 2 2 1 GHM07N GHM09N GHM12N I NDO OR UNI T O UTD OO R UNI T ...
Страница 30: ...29 T 0 High ...