Page 5
G50UHi−48B−090
External
Jumper Speed Selector
External
Static
Pressure
Speed 1
Factory Default
Cool
Speed 2
Speed 3
Factory Default
Dehumid
Speed 4
Factory Default
Heat
Speed 5
Speed 6
Speed 7
Factory Default
Fan
in. w.g. Pa cfm
L/s
Watts
cfm L/s
Watts
cfm L/s
Watts
cfm L/s
Watts
cfm L/s
Watts
cfm L/s
Watts
cfm L/s
Watts
0
0
1800 850
655
1585 750
495
1465 690
420
1345 635
360
1225 575
300
1060 500
230
890 420
170
0.1
25 1795 845
670
1590 750
515
1485 700
455
1365 645
395
1225 580
320
1050 495
235
845 400
175
0.2
50 1755 830
690
1580 745
545
1495 705
490
1375 650
415
1240 585
350
1030 485
255
820 385
185
0.3
75 1710 805
690
1565 740
565
1470 695
500
1370 645
445
1245 585
375
1025 485
285
760 360
190
0.4
100 1605 755
660
1550 730
585
1450 685
525
1355 640
455
1225 580
395
1015 480
300
745 350
210
0.5
125 1610 760
715
1510 715
580
1435 675
540
1340 630
485
1210 570
415
1005 475
330
740 350
225
0.6
150 1550 730
680
1475 695
600
1410 665
570
1325 625
510
1190 560
445
980 465
345
745 350
250
0.7
175 1470 695
640
1430 675
625
1365 645
555
1290 610
500
1170 550
455
965 455
355
715 340
265
0.8
200 1350 635
585
1370 645
615
1315 620
590
1225 575
535
1130 530
470
955 450
370
695 325
285
0.9
225 1220 575
550
1260 595
575
1260 595
575
1195 565
540
1090 515
490
935 440
400
670 315
295
NOTES − All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished − field provided) in place. Also see Filter Air Resistance table.
Air volume based on bottom return air. Actual air volume may vary on side return air applications.
G50UHi−60C−110
External
Jumper Speed Selector
External
Static
Pressure
Speed 1
Factory Default
Cool
Speed 2
Speed 3
Factory Default
Dehumid
Speed 4
Factory Default
Heat
Speed 5
Speed 6
Speed 7
Factory Default
Fan
in. w.g. Pa cfm
L/s
Watts
cfm L/s
Watts
cfm L/s
Watts
cfm L/s
Watts
cfm L/s
Watts
cfm L/s
Watts
cfm L/s
Watts
0
0
2150 1015
915
1965 925
735
1850 875
640
1695 800
535
1515 715
425
1295 610
315
1000 470
215
0.1
25 2140 1010
935
1960 925
775
1830 865
660
1695 800
565
1535 725
460
1345 635
355
975 460
220
0.2
50 2085 985
930
1960 925
815
1825 860
710
1700 800
595
1545 730
500
1375 650
400
1000 475
240
0.3
75 2085 985
1000
1965 925
855
1825 860
735
1675 790
610
1540 725
520
1375 650
420
1075 505
290
0.4
100 2055 970
1015
1945 920
890
1825 860
775
1680 790
645
1525 720
545
1375 650
455
1075 505
310
0.5
125 2010 950
1025
1895 895
890
1810 855
810
1680 795
690
1515 715
580
1350 635
465
1075 505
335
0.6
150 1950 920
1015
1885 890
965
1795 845
850
1640 775
705
1505 710
605
1335 630
490
1050 495
345
0.7
175 1900 895
1010
1850 875
970
1760 830
865
1630 770
735
1485 700
625
1335 630
530
1010 480
360
0.8
200 1845 870
1025
1790 845
950
1700 800
875
1605 755
755
1460 690
645
1315 620
545
1000 470
385
0.9
225 1740 820
980
1715 810
955
1665 785
915
1570 740
785
1425 670
675
1275 600
570
995 470
420
NOTES − All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished − field provided) in place. Also see Filter Air Resistance table.
Air volume based on side return air. Actual air volume may vary on bottom return air applications.
G50UHi−60D−135
External
Jumper Speed Selector
External
Static
Pressure
Speed 1
Factory Default
Cool
Speed 2
Speed 3
Factory Default
Dehumid
Speed 4
Factory Default
Heat
Speed 5
Speed 6
Speed 7
Factory Default
Fan
in. w.g. Pa cfm
L/s
Watts
cfm L/s
Watts
cfm L/s
Watts
cfm L/s
Watts
cfm L/s
Watts
cfm L/s
Watts
cfm L/s
Watts
0
0
2160 1020
905
1985 935
735
1910 900
665
1705 805
520
1580 745
460
1290 610
315
1040 490
230
0.1
25 2165 1020
945
1975 930
770
1895 895
695
1725 815
565
1595 750
475
1345 635
350
990 465
220
0.2
50 2115 995
935
1970 930
805
1890 890
730
1710 805
575
1605 755
525
1380 650
385
945 445
225
0.3
75 2055 970
925
1975 935
845
1895 895
770
1705 805
620
1600 755
545
1395 660
425
1010 475
260
0.4
100 2090 985
1015
1960 925
870
1885 890
805
1705 805
650
1590 750
565
1410 665
455
1115 525
330
0.5
125 2065 975
1040
1940 915
895
1865 880
825
1700 800
670
1585 750
590
1380 650
465
1120 530
350
0.6
150 2020 955
1030
1880 885
880
1855 875
865
1685 795
700
1570 740
620
1355 640
490
1105 520
370
0.7
175 1965 925
1040
1880 885
965
1815 855
880
1650 780
725
1550 730
650
1340 630
510
1065 500
375
0.8
200 1910 900
1040
1850 875
960
1760 830
880
1645 775
760
1535 725
670
1340 635
550
1055 500
395
0.9
225 1805 850
975
1785 845
985
1740 820
920
1610 760
785
1500 710
695
1310 620
555
1035 490
430
NOTES − All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished − field provided) in place. Also see Filter Air Resistance table.
Air volume based on side return air. Actual air volume may vary on bottom return air applications.
Содержание G50UHi Series