Page 25
NORMAL HEATING MODE
ABNORMAL HEATING MODE
FLAME RECTIFICATION CURRENT
CHECK. CAN FLAME BE PROVEN WITHIN
4 SECONDS AFTER GAS VALVE OPENS?
See table 19
FLAME PRESENT?
INDOOR BLOWER ON DELAY BEGINS
(45 seconds.)
PRIMARY AND SECONDARY LIMIT
SWITCHES CLOSED?
COMBUSTION AIR PROVE
SWITCH CLOSED?
LOW FLAME SIGNAL
(Does not affect operation of control)
LED #1 −− SLOW FLASH
LED #2 −− FAST FLASH
GAS VALVE DE−ENERGIZED.
COMBUSTION AIR INDUCER
DE−ENERGIZED.INDOOR BLOWER
ON UNTIL SWITCH CLOSES.LED #1
−− SLOW FLASH. LED #2 −− ON.
IS LIMIT SWITCH CLOSED?
GAS VALVE DE−ENERGIZED.
COMBUSTION AIR INDUCER ON.
INDOOR BLOWER OFF WITH DELAY
LED #1 −− OFF. LED #2 −− SLOW FLASH.
HAS CAB SWITCH CLOSED IN 2.5 MINUTES?
15-SECOND COMBUSTION AIR INDUCER PREPURGE
INITIATED BY CLOSED PRESSURE SWITCH.
YES
IGNITOR WARM-UP −− 20 SECONDS.
YES
YES
FLAME STABILIZATION PERIOD.
GAS VALVE OFF. COMBUSTION AIR INDUCER ON.
INDOOR BLOWER OFF.
HAS CONTROL FAILED TO SENSE FLAME FOR
FIVE CONSECUTIVE TRIES DURING A SINGLE
HEAT DEMAND?
IGNITION WATCHGUARD MODE. GAS VALVE OFF.
COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF WITH DELAY
LED 1 ALT. SLOW FLASH LED 2 ALT SLOW FLASH
IS 60-MINUTE RESET PERIOD COMPLETE?
YES
4 SECONDS
YES
HAS CONTROL RESET IGNITION
SEQUENCE FOUR TIMES?
FLAME SIGNAL NORMAL?
See table 19
YES
YES
HAS PRIMARY/SECONDARY LIMIT
RESET (CLOSED) WITHIN 3
MINUTES?
YES
ROLLOUT SWITCH CLOSED?
GAS VALVE POWER OFF.
COMBUSTION AIR INDUCER POWER OFF.
INDOOR BLOWER OFF WITH DELAY
LED #1 −− ON. LED #2 −− SLOW FLASH.
SEQUENCE HOLDS UNTIL ROLLOUT SWITCH IS RESET
YES
THERMOSTAT DEMAND SATISFIED.
LED #1 & #2 SIMULTANEOUS SLOW FLASHES.
COMB. AIR INDUCER CONTINUES 5-SECOND POST PURGE
AFTER T’STAT DEMAND IS SATISFIED. INDOOR AIR BLOWER
COMPLETES SELECTED OFF" DELAY BEFORE SHUTTING OFF.
HEAT SPEED, ACCESSORY AND EAC. TERMINAL OFF.
YES
NO
5-MINUTE PRESSURE SWITCH
WATCHGUARD MODE.
YES
IS THERE A PROPER GROUND?
IS VOLTAGE ABOVE 75 VOLTS?
IS IGNITOR INTACT AND CONNECTED?
LEDS SIGNAL
ALTERNATING
FAST FLASH
NO
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
NO
NO
YES
YES
NO
NO
NO
NO
YES
YES
LIMIT SWITCH WATCH GUARD
MODE. GAS VALVE OFF.
COMB. AIR INDUCER OFF. IN-
DOOR BLOWER OFF WITH
DELAY. LED#1−SLOW FLASH
LED#2− ON. IS 60MINUTE RE-
SET PERIOD COMPLETE.?
YES
YES
4-SECOND TRIAL FOR IGNITION. GAS VALVE OPENS.
IGNITOR ENERGIZED DURING TRIAL UNTIL FLAME
SENSED.