background image

Page 14

73

PSIG

285

84

10HP NORMAL OPERATING PRESSURES (COOLING MODE)

OUTDOOR COIL

ENTERING AIR

TEMPERATURE

10HP12

10HP24

10HP30

10HP36

65

°

 F (TXV)

75

°

F (TXV)

85

°

F (TXV)

95

°

F (TXV)

LIQ.

+ 10

SUC.

+ 10

PSIG PSIG

LIQ.

+ 10

SUC.

+ 10

PSIG PSIG

LIQ.

+ 10

SUC.

+ 10

PSIG PSIG

105

°

F (TXV)

LIQ.

+ 10

SUC.

+ 10

PSIG

PSIG

LIQ.

+ 10

SUC.

+ 10

PSIG PSIG

10HP18

10HP42

10HP48

10HP60

LIQ.

+ 10

SUC.

+ 10

PSIG

PSIG

LIQ.

+ 10

PSIG

SUC.

+ 10

SUC.

+ 10

PSIG

LIQ.

+ 10

PSIG

105

°

F (RFC III)

95

°

F (RFC III)

85

°

F (RFC III)

75

°

F (RFC III)

65

°

 F (RFC III)

TABLE 11

137
155
182
210
240
130

175

155

210
240

78
79
80
82
83
59

75

67

82
87

145
165
195
225
255
150

195

170

230
260

72
73
74
77
79
61

75

68

81
85

160
185
215
245
275
150

205

175

240
280

74
76
78
80
84
60

73

67

78
81

170
195
225
255
290
165

220

190

255

75
77
78
80
82
62

74

69

80

175
200
227
260
295
170

230

205

265
305

75
76
77
79
81
61

73

68

79
82

160
185
215
245
280
155

210

180

240
275

72
74
76
78
80
61

68

63

73
76

165
185
210
240
275
155

210

185

245
275

72
73
76
78
80
63

69

64

74
78

150
175
200
235
265

75
76
78
80

*

*

*

*

*

*

*

*

*

*

*

For an approved match-up the 10HP60 must be used with a TXV.

10HP36 (CAN)

LIQ.

+ 10

SUC.

+ 10

PSIG

PSIG

175
200
230
260
295
160

225

190

255
385

76
77
78
79
81
62

70

68

77
81

2 – RFCIII Systems

The system should not be charged at ambients below
60 

_

F (15

_

C). If charging below 60 

_

F (15

_

C) is required,

the recommended method of charging is to weigh the
refrigerant into the unit according to the total amount
shown on the unit nameplate and in table 8. For line sets
varying from 20 feet, refer to table 7 for refrigerant charge
adjustment. If ambient temperature is above  60 

_

F (15

_

C)

use the subcoooling method outlined below.

SUBCOOLING METHOD (RFCIII SYSTEMS)

(Ambient Temperature Above 60

_

F [16

_

C] )

 1 – Connect gauge manifold. Connect an upright

R–22 drum to center port of gauge manifold.

 2 – Operate  indoor  and  outdoor  units  in  cooling

mode. Allow outdoor unit to run until system
pressures stabilize.

 3 – Make  sure  thermometer  well  is  filled  with

mineral oil before checking liquid line
temperature.

 4 – Read  liquid  line  pressure  and  convert  to

condensing temperature using temperature/
pressure conversion chart.
Condensing temperature (read from gauges)
should be a few degrees warmer than the
liquid line temperature.

Outdoor

Unit

Indoor

Unit

65

_

F 75

_

F 85

_

F 95

_

F 105

_

F 115

_

F

CB19–51

10HP48

10HP12
10HP18
10HP24

10HP36 (CAN)

CB/CBH19–41

CB/CBH19–26

CB/CBH19–21

CB/CBH19–21

CB/CBH19–31

CB/CBH19–41

10HP30

10HP42

SUBCOOLING METHOD––RFCIII Systems*

5

13
12
12

11
11

5

13
12
12

10
10

4

13
11
10

7
8

1

12

9
8

6
7

0
6
7
6

4
5

0

4
5
4

2
2

*Approved matchups only

10HP36

CB/CBH19–41

17

15

14

11

8

5

18

16

15

12

9

6

Condensing Temp

°

F Warmer

Than Liquid Line At Various

Ambients

 

 5 – Place thermometer in well and read liquid line

temperature. Table 12 shows how much
warmer the condensing temperature should be.

Add refrigerant to make the liquid line
temperature cooler.
Recover refrigerant to make the liquid line
temperature warmer.

 6 – When  unit  is  properly  charged  liquid  line

pressures should approximate table 11.

E – Oil Charge

Refer to table 4 on page 6 for factory oil charge.

V – MAINTENANCE

At the beginning of each heating or cooling season, the
system should be cleaned as follows:

A – Outdoor Unit

 1 – Clean and inspect outdoor coil. (Coil may be

flushed with a water hose).

 2 – Outdoor fan motor is prelubricated and sealed.

No further lubrication is required.

 3 – Visually inspect all connecting lines, joints

and coils for evidence of oil leaks.

NOTE-If insufficient heating or cooling occurs, unit
should be gauged and refrigerant charge checked.

B – Indoor Coil

 1 – Clean coil if necessary.
 2 – Check connecting lines, joints and coil for

evidence of oil leaks.

 3 – Check condensate line and clean if necessary.

C – Indoor Unit

 1 – Clean or change filters.
 2 – Check blower motor for debris. Blower motors 

are prelubricated and sealed. No further
lubrication required.

 

– 

Adjust blower speed for cooling. Static
pressure drop over the coil should be checked
to determine the correct blower CFM. Refer to
Lennox Engineering Handbook for Static
Pressure and CFM tables.

 4 – Check all wiring for loose connections.
 5 – Check for correct voltage at unit.
 6 – Check amp–draw on blower motor.

Unit nameplate_________Actual_________.

Содержание Diplomat 10HP12

Страница 1: ...ble in sizes ranging from 1 through 5 tons This manual is divided into sections which discuss the major components refrigerant system charging procedure maintenance and operation sequence Canadian spe...

Страница 2: ...breaker size amps 35 35 40 50 60 Minimum circuit ampacity 21 5 21 3 25 0 32 2 40 2 Refer to National Electric Code manual to determine wire fuse and disconnect size requirements NOTE Extremes of oper...

Страница 3: ...fan side and the compressor side of the capacitor have different MFD ratings See table 1 for dual capacitor ratings TABLE 1 Unit MFD VAC 10HP C12 DUAL CAPACITOR RATING 10HP18 24 and 30 2 10HP42 10HP4...

Страница 4: ...ents 1 Timing Pins 30 60 90 Each of these pins provides a different timed interval between defrosts A jumper connects the pins to circuit board pin W1 Table 3 shows the timings of each pin The defrost...

Страница 5: ...r to avoid damaging the circuit board 2 Make sure all control terminals are connected as shown on unit wiring diagram before attempting to place control in test mode See NOTE below NOTE Control will n...

Страница 6: ...DE ECCENTRIC ROTARY COMPRESSOR INTERNALS ROTOR SHAFT Figure 10 illustrates the four steps in a rotary compressor s continuous intake cycle The spring loaded blade is compressed fully at the beginning...

Страница 7: ...re 13 The reversing valve requires no maintenance It is not rebuildable If the reversing valve has failed it must be replaced If replacement is necessary access the reversing valve by removing the con...

Страница 8: ...he liquid line and vapor line service valves and gauge ports are accessible from outside of the unit Full service liquid and vapor line valves are used See figures 18 and 19 The service ports are used...

Страница 9: ...e stem cap with an adjustable wrench 2 Using service wrench backseat valve a Turn stem counterclockwise until backseated b Tighten firmly 3 Replace stem cap finger tighten then tighten an additional 1...

Страница 10: ...L10 41 50 20 30 40 50 3 8 3 4 3 4 3 4 3 4 3 8 3 8 3 8 10HP30 10HP36 L10 65 30 L10 65 40 L10 65 50 30 40 50 3 8 7 8 7 8 7 8 3 8 3 8 10HP42 10HP48 10HP60 Not Available 3 8 1 1 8 Field Fabricate LINE SET...

Страница 11: ...ATOR 10HP42 48 AND 60 ONLY DEFROST SWITCH S6 FILTER DRIER W INTERNAL CHECK VALVE MUFFLER LIQUID LINE FROM INDOOR COIL TO OUTDOOR COIL DISCHARGE LINE SERVICE PORT STRAINER LIQUID LINE SERVICE PORT REVE...

Страница 12: ...n to center port of gauge manifold 2 Open high pressure valve on gauge manifold and pressurize line set indoor coil to 150 psig 1034 kPa 3 Check lines and connections for leaks 4 Release nitrogen pres...

Страница 13: ...eways until liquid pressures in the 200 250 psig range are reached Block outdoor coil one side at a time with cardboard or plastic sheets until proper testing pressures are reached BLOCKING OUTDOOR CO...

Страница 14: ...Read liquid line pressure and convert to condensing temperature using temperature pressure conversion chart Condensing temperature read from gauges should be a few degrees warmer than the liquid line...

Страница 15: ...TB1 is energized initiating first stage heat from indoor unit 14 If outdoor temperature is below the balance point N O low ambient cut in thermostat S23 will close 15 When S23 is closed W2 of indoor...

Страница 16: ...Page 16 10HP WITH ELECTROMECHANICAL THERMOSTAT...

Отзывы: