23
1.- GENERAL CHARACTERISTICS
SM: Mixing section.
SR: return fan section.
UI: Indoor unit.
UE: Outdoor unit.
- - - - Mechanical installation to be carried out by the installer.
Freecooling supports, to be carried out by the installer.
The electrical box for the freecooling is supplied apart and has to be fixed by the installer.
1
The consumption of the return fan by unit is:
MODELS
MAXIMUM
CURRENT
POWER kW
(A)
230 / III
400/ III
22E
1,3
4,3
2,5
24E
1,4
4,3
2,5
28E
1,5
6,2
3,6
32E
1,8
6,2
3,6
38E
2
6,2
3,6
44D
2,6
8,8
5,1
48D
2,8
8,8
5,1
56D
3
12,5
7,2
64D
3,6
12,5
7,2
76D
4
12,5
7,2
6.- SUPPLY AND INSTALLATION
Configuration of freecooling supply for packaged system:
7.- FREECOOLING WITH RETURN FAN
If an extra static pressure is required on the return air duct, the freecooling should add a return fan section.
This return fan section includes a discharge damper.
The operation dampers for this freecooling with return fan is as follow:
As much as the air intake damper opens, that much the by-pass damper closes and the discharge air damper
opens, for the air return suction (see drawing).
This means that at the same time is reached a free cooled of the room, the discharge or return air and the air of
the room gets removable.
1.6.- AVAILABLE OPTIONS
FREECOOLING
- Packaged system
SM
UI
UE
22E 76D
SM
UI
UE
22E 76D
SR
1
1
UNITS