18
1.- GENERAL CHARACTERISTICS
MAIN SWITCH
The main switch is located on the access panel to the electrical box of the outdoor unit.
The main switch is endowed with a clutch gadget, which allows open the panel of the electrical box, when it is on
OFF position.
MODELS LEC
(INDOOR UNIT)
22E-24E-28E-32E-38E
MAXIMUM
CURRENT
(A)
230 / III
400/ III
POWER kW
7,5
18,8
10,8
11
27,6
15,9
15
37,7
21,7
44D-48D-56D-64D-76D
15
37,7
21,7
20
50,2
28,9
30
75,3
43,3
WEIGHTS Kg (*)
10
20
22E-24E-28E-32E-38E
(A)
230 / III
400/ III
7,5
18,8
10,8
11
27,6
15,9
15
37,7
21,7
44D-48D-56D-64D-76D
15
37,7
21,7
20
50,2
28,9
1
1
11
27,6
15,9
11
27,6
15,9
(*) Add to the unit's weight.
(*) Add to the unit's weight.
STAGES
1
2
10
20
MODELS LEH
(INDOOR UNIT)
MAXIMUM
CURRENT
POWER kW
WEIGHTS Kg (*)
STAGES
Check to make sure that the main switch is large enough to handle the current for the unit if electric heaters are
installed.
Security
thermostat
Small case for
contactors and
connections
Situation of the
electrical heater once
installed
Support
ELECTRICAL HEATER
Made of align shielded elements, supplied mounted on the unit as drawing shows.
All the range has three security elements: 2 security thermostat, one automatic other manual reset and an air flow
security pressure switch, which make the electrical heater stops when air flow is not enough.
The electrical heater must be supplied on from the units electrical box.
An small case on the electrical heater protects contactors and electrical connections.
DIRTY FILTER INDICATION
To install on the indoor unit.
It is based on an air flow security pressure switch, which detects the available static pressure through the air filter.
In case the filters are dirties, the detector is activated, showing an alarm, if the fan is ON.
1
1 ó 2
WITH MAIN SWITCH ON. DO NOT REMOVE THE PANEL
ATTENTION!
1.6.- AVAILABLE OPTIONS
Содержание Compactair LVCK 22E
Страница 1: ...COMPACTAIR LVCK LVHK English 03 2005 INSTALLATION OPERATION MAINTENANCE MANUAL...
Страница 50: ...49 NOTES...
Страница 51: ...50 NOTES...