Page 12
ECBA25 Electric Heat Data
ELECTRIC HEAT DATA
CBA25UHV-018 | SINGLE PHASE
Electic Heat
Model Number
Input
Blower
Motor
Full Load
Amps
2
Minimum
Circuit
Ampacity
3
Maximum
Overcurrent
Protection
Volt
kW
1
Btuh
5 kW
ECBA25-5 (
16Y36
)
Terminal Block
ECBA25-5CB (
16Y39
)
30A Circuit Breaker
208
3.6
12,300
3.9
27
30
220
4.0
13,800
3.9
28
30
230
4.4
15,000
3.9
29
30
240
4.8
16,400
3.9
30
30
7.5 kW
ECBA25-7.5 (
16Y37
)
Terminal Block
ECBA25-7.5CB (
16Y41
)
45A Circuit Breaker
208
5.6
19,200
3.9
39
4
40
220
6.3
21,500
3.9
41
45
230
6.9
23,500
3.9
42
45
240
7.5
25,600
3.9
44
45
10 kW
ECBA25-10 (
16Y38
)
Terminal Block
ECBA25-10CB (
16Y42
)
60A Circuit Breaker
208
7.2
24,600
3.9
48
4
50
220
8.0
27,500
3.9
51
60
230
8.8
30,000
3.9
53
60
240
9.6
32,700
3.9
55
60
ELECTRIC HEAT DATA
CBA25UHV-024 | SINGLE PHASE
Electic Heat
Model Number
Input
Blower
Motor
Full Load
Amps
2
Minimum
Circuit
Ampacity
3
Maximum
Overcurrent
Protection
Volt
kW
1
Btuh
5 kW
ECBA25-5 (
16Y36
)
Terminal Block
ECBA25-5CB (
16Y39
)
30A Circuit Breaker
208
3.6
12,300
3.9
27
30
220
4.0
13,800
3.9
28
30
230
4.4
15,000
3.9
29
30
240
4.8
16,400
3.9
30
30
7.5 kW
ECBA25-7.5 (
16Y37
)
Terminal Block
ECBA25-7.5CB (
16Y41
)
45A Circuit Breaker
208
5.6
19,200
3.9
39
4
40
220
6.3
21,500
3.9
41
45
230
6.9
23,500
3.9
42
45
240
7.5
25,600
3.9
44
45
10 kW
ECBA25-10 (
16Y38
)
Terminal Block
ECBA25-10CB (
16Y42
)
60A Circuit Breaker
208
7.2
24,600
3.9
48
4
50
220
8.0
27,500
3.9
51
60
230
8.8
30,000
3.9
53
60
240
9.6
32,700
3.9
55
60
NOTE - Circuit 1 Minimum Circuit Ampacity includes the Blower Motor Full Load Amps.
1
Electric heater capacity only - does not include additional blower motor heat capacity.
2
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Use wires suitable for at least 167°F.
3
HACR type breaker or fuse.
4
Bold indicates that the circuit breaker on “CB” circuit breaker models must be replaced with size shown.