Page 6
TABLE 2
BLOWER DATA
CBA25UHV-018 BLOWER PERFORMANCE
0 through 0.80 in. w.g. External Static Pressure Range
“ADJUST”
Jumper
Setting
Jumper Speed Positions
“HEAT” Speed
First Stage “COOL” Speed
Second Stage “COOL” Speed
1
2
3
4
1
2
3
4
1
2
3
4
cfm
cfm
cfm
cfm
cfm
cfm
cfm
cfm
cfm
cfm
cfm
cfm
+
500
705
925
1150
365
520
665
810
500
705
925
1150
NORM
465
650
850
1050
350
485
610
740
465
650
850
1050
–
420
600
760
950
320
425
560
680
420
600
760
950
NOTES - The effect of static pressure, filter and electric heater resistance is included in the air volumes listed.
First stage cooling air volume is 70% of COOL speed setting. Continuous blower speed is approximately 50% of COOL speed setting.
Lennox Harmony III™ Zoning System applications - minimum blower speed is 250 cfm.
BLOWER DATA
CBA25UHV-024 BLOWER PERFORMANCE
0 through 0.80 in. w.g. External Static Pressure Range
“ADJUST”
Jumper
Setting
Jumper Speed Positions
“HEAT” Speed
First Stage “COOL” Speed
Second Stage “COOL” Speed
1
2
3
4
1
2
3
4
1
2
3
4
cfm
cfm
cfm
cfm
cfm
cfm
cfm
cfm
cfm
cfm
cfm
cfm
+
450
670
900
1120
340
450
650
770
450
670
900
1120
NORM
420
620
820
1050
300
400
600
700
420
620
820
1050
–
390
570
750
915
280
390
500
650
390
570
750
915
NOTES - The effect of static pressure, filter and electric heater resistance is included in the air volumes listed.
First stage cooling air volume is 70% of COOL speed setting. Continuous blower speed is approximately 50% of COOL speed setting.
Lennox Harmony III™ Zoning System applications - minimum blower speed is 250 cfm.
BLOWER DATA
CBA25UHV-030 BLOWER PERFORMANCE
0 through 0.80 in. w.g. External Static Pressure Range
“ADJUST”
Jumper
Setting
Jumper Speed Positions
“HEAT” Speed
First Stage “COOL” Speed
Second Stage “COOL” Speed
1
2
3
4
1
2
3
4
1
2
3
4
cfm
cfm
cfm
cfm
cfm
cfm
cfm
cfm
cfm
cfm
cfm
cfm
+
680
885
1115
1340
490
635
770
930
680
885
1115
1340
NORM
620
810
1020
1220
440
575
715
845
620
810
1020
1220
–
550
725
905
1100
411
530
645
755
550
725
905
1100
NOTES - The effect of static pressure, filter and electric heater resistance is included in the air volumes listed.
First stage cooling air volume is 70% of COOL speed setting. Continuous blower speed is approximately 50% of COOL speed setting.
Lennox Harmony III™ Zoning System applications - minimum blower speed is 250 cfm.