background image

506307-01

Page  13  of  36

Issue 1207

3. Never reduce the pipe size below the outlet size of the

furnace without checking the applicable sections of the
(U.S.) National Fuel Gas Code ANSI Z223.1/NFPA54,
and/or CSA B149.1 Natural Gas and Propane Installa-
tion Codes.

4. All pipe should be supported using the proper clamps

and/or straps.  These supports should be at least every
four (4’) feet.

5. All horizontal runs of pipe should have at least a 1/4” (in.)

per foot of upward slope from the furnace to the vent
terminal.

6. All runs of pipe should be as short as possible with as few

turns as possible.

7. Seams should be tightly joined and checked for leaks.
8. The flue pipe must not extend into the chimney but be

flush with the inside wall.

9. The chimney or vent pipe must extend at least three (3’)
feet above the highest point where it passes through a roof
of a building and at least two (2’) feet higher than any portion
of a building within a horizontal distance of ten (10’) feet.  It
shall also extend at least five (5’) feet above highest
connected equipment flue collar.

Checking For Vent Oversizing

:

If this furnace is replacing a furnace that is attached to a

venting system serving other appliances, the venting system
is likely to be too large to properly vent all of the attached
appliances.  An improperly sized venting system can lead to
condensation, leakage, or spillage.

Failure to follow the steps outlined below for each appliance connected to the venting system being placed into
operation could result in carbon monoxide poisoning or death.

The following steps shall be followed for each appliance connected to the venting system being placed into
operation, while all other appliances connected to the common venting system are not in operation:

1. Seal any unused openings in the  venting system.

2. Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI

Z223.1/NFPA 54  or the CSA  B149.1, Natural Gas and Propane Installation Codes and these instructions.
Determine that there is no blockage or restriction, leakage, corrosion, or other deficiencies which could cause an
unsafe condition.

3. As far as practical, close all building doors and windows and all doors between the space in which the appliance(s)

connected to the venting system are located and other spaces of the building.

4. Close fireplace dampers.

5. Turn on clothes dryers and any appliance not connected to the venting system.  Turn on any exhaust fans, such

as range hoods and bathroom exhausts, so they are operating at maximum speed. Do not operate a summer
exhaust fan.

6. Follow the lighting instructions. Place the applicance being inspected in operation.  Adjust the thermostat so

appliance is operating continuously.

7. Test for spillage from draft hood equipped appliances at the draft hood relief opening after 5 minutes of main

burner operation.  Use the flame of a match or candle.

8. If improper venting is observed during any of the above tests, the venting system must be corrected in accordance

with the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or the CSA B149.1, Natural Gas and Propane
Installation Codes.

9. After it has been determined that each appliance connected to the venting system properly vents when tested as

outlined above, return doors, windows, exhaust fans, fireplace dampers, and any other gas-fired burning appliance
to their previous conditions of use.

CARBON MONOXIDE POISONING HAZARD

 WARNING

Содержание B050A3B

Страница 1: ...est Columbia SC 29170 SECTION 1 INSTALLATION AND SERVICING INSTRUCTIONS 1 28 Important Safety Information 2 Specification and Installation 3 Start up and Operation 17 Maintenance 21 Sequence of Operat...

Страница 2: ...e instructions 6 Always install furnace to operate within the furnace s intended temperature rise range with a duct system whichhasanexternalstaticpressurewithintheallowable range as specified in Temp...

Страница 3: ...506307 01 Page 3 of 36 Issue 1207...

Страница 4: ...al injury due to electrical shock or uncontrolled gas leakage WARNING When operating the furnace in the heating mode the static pressure and the temperature rise supply air temperature minus return ai...

Страница 5: ...506307 01 Page 5 of 36 Issue 1207 FURNACE WIRING SPECIFICATIONS...

Страница 6: ...ult the U S National Fuel Gas Code obtainable from the National Fire Protection Association Inc Batterymarch Park Quincy MA 02269 or the American Gas Association 1515 Wilson Boulevard Arlington VA 222...

Страница 7: ...e straps around each end of the furnace These straps should be attached to the furnace with sheet metal screws and to the rafters with bolts The furnace may also be suspended by using an angle iron fr...

Страница 8: ...o air needed for combustion ventilation in the form of process air must be provided as required for cooling of eqipment or material controlling dew point heating drying oxidation or dilution safety ex...

Страница 9: ...ons should be followed when installing the ductwork 1 Install locking type dampers in all branches of the individual ducts to balance out the system Dampers should be adjusted to impose the proper sta...

Страница 10: ...ction BTU INPUT FILTER SIZE 50 000 75 000 100 000 125 000 13 X 23 13 X 23 16 1 2 X 26 20 X 23 Table 2 VENTING Venting for the furnace must be to the outside and in accordance with local codes or requi...

Страница 11: ...ace must not be vented into a chimney serving a separate appliance designed to burn solid fuel Type II B vent connectors must be used on all installations and it must be sized per the applicable secti...

Страница 12: ...t ANSI Z223 1 NFPA 54 National Fuel Gas Code A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings Permit...

Страница 13: ...ing system being placed into operation while all other appliances connected to the common venting system are not in operation 1 Seal any unused openings in the venting system 2 Inspect the venting sys...

Страница 14: ...223 1 NFPA54 and or CSA B149 1 Natural Gas and Propane Installation Codes If local codes allow the use of a flexible gas appliance connector always use a new listed connector Do not use a connector wh...

Страница 15: ...tap in order to test incoming gas pressure and outgoing manifold pressure See Figure 9 FIELD SUPPLIED MAIN MANUAL SHUT OFF VALVE GAS SUPPLY DRIP LEG F0000317 Many soaps used for leak testing are corr...

Страница 16: ...valve and begins post purge and blower off delay time Open Limit Any time the limit switch is open the control de energizes the gas valve and runs the indoor blower motor on heat speed and runs the i...

Страница 17: ...position 5 Set the thermostat above room temperaturae 6 The ignitior will spark and the main burners will ignite Do not attempt to manually light the burners Failure to follow this warning can lead to...

Страница 18: ...If the heating value of the natural gas is 1015 Btu cu and it takes 60 seconds to burn 2 cu ft of gas then Input 1015 Btu cu ft x 1 rev x 2 cu ft rev x 3600 60 sec Input 121 8000 btu hr Burner Orific...

Страница 19: ...Prior to any blower adjustment electrical service must be turned OFF This furnace is equipped with a 3 speed direct drive motor to deliver a temperature rise within the range specificed on the rating...

Страница 20: ...vent from the combustion blower Place the furnace into operation Gradually cover up the blower outlet the main burners should shut OFF Remvoe the restriction and the unit should relight Replace the v...

Страница 21: ...be necessary to use a soft bristly brush to remove dirt and then vacuum 3 Remove the burner opening inlet plate This will expose the burner openings of the primary heat exchangers 4 Vacuum the length...

Страница 22: ...nd continue sliding the blower forward until it is out of the unit Replacement 1 Place the blower in the blower opening of the unit and slide the blower back into the unit taking care to clear the top...

Страница 23: ...506307 01 Page 23 of 36 Issue 1207 SEQUENCE OF OPERATION DIRECT IGNITION SYSTEM CONTROL...

Страница 24: ...till present Combustion blower energized The heat speed circulation air fan will be energized after the selected heat fan on delay System waits for flame signal to disappear then goes to Soft Lockout...

Страница 25: ...506307 01 Page 25 of 36 Issue 1207 WIRING DIAGRAM f0000321...

Страница 26: ...sion can not be met at the time of completion of installaiton the owner shall have a period of thirty 30 days to comply with the above requirements provided however that during said thirty 30 day peri...

Страница 27: ...ollowing requirements shall be satisfied by the manufacturer 1 The identification of each special venting system shall include the listing of either the website phone number or manufacturer s address...

Страница 28: ...Page 28 of 36 506307 01 Issue 1207 NOTES...

Страница 29: ...eep you warm and comfortable during the winter months It will deliver superb performance with only minimal help from you To keep your operating costs low and to eliminate unnecessary service calls we...

Страница 30: ...e to the furnace before shutting off the electrical supply 6 Do not use the furnace if any part has been under water A flood damaged furnace is extremely dangerous Attempts to use the furnace can resu...

Страница 31: ...fan switch on the thermostat permits you to do this see Figure M 2 on page 32 With the switch in the ON position the fan will operate continuously AUTO position gives fan operation only when the unit...

Страница 32: ...ashlight will be useful for these inspections Make one inspection prior to the beginning of the heating season and another during the middle Should you observe unusual amounts of any of the following...

Страница 33: ...r washing Cleanable filters may be replaced with disposable filters Refer to Table 1 on page 33 when selecting the proper size and quantity of disposable filter If your air distribution system has a c...

Страница 34: ...urnace still does not operate call your dealer for service Lubrication Lubrication of the bearings in the circulating air blower motor and the combustion blower motor is not recommended Burner Flame W...

Страница 35: ..._______________ Serial _________________________ Installation Date ____________ Equipment Type ______________________________________ Model _________________________________ Serial ___________________...

Страница 36: ...AFFIX THIS INSTRUCTION PACKET ADJACENT TO THE FURNACE HOMEOWNER RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE INSTRUCTIONS D ENTRETIEN ET INSTALLATION ET MANUAL DE L USAGER INSTALLATEUR PLACEZ LA POC...

Отзывы: