Pre-Installation Vent System Inspection

:

Before this furnace is installed, it is highly recommended

that any existing vent system be completely inspected.

For a chimney or “B” vent, this should include the

following:
1. Inspection for any deterioration in the chimney or “B” vent.

If deterioration is discovered, the chimney must be
repaired or the “B” vent must be replaced.

2. Inspection to ascertain that the vent system is clear and

free of obstructions.  Any blockage must be cleared before
installing this furnace.

3. Cleaning the chimney or “B” vent if previously used for

venting a solid fuel burning appliance or fireplace.

4. Confirming that all unused chimney or “B” vent connections

are properly sealed.

5. Verification that the chimney is properly lined and sized

per the applicable codes.

Masonry Chimney:

This furnace can be common vented into an existing

tile lined masonry chimney provided:
1. The chimney is currently serving at least one drafthood

equipped appliance.

2. The vent connectors and chimney are sized in accordance

with the applicable sections of the (U.S.) National Fuel
Gas Code ANSI Z223.1/NFPA54, and/or CSA B149.1
Natural Gas and Propane Installation Codes.

This furnace must 

NOT

 be vented 

ALONE

 into an

existing masonry chimney (either title lined or unlined) unless
the chimney is also lined with either a type “B” vent system
or a listed single wall, metal lining system.  Both of these
systems must be sized in accordance with the applicable
sections of the (U.S.) National Fuel Gas Code ANSI Z223.1/
NFPA 54, and/or CSA B149.1 Natural Gas and Propane
Installation Codes.

Before venting this furnace into a chimney, check the

chimney for deterioration and repair if necessary.  This
furnace must not be vented into a chimney serving a separate
appliance designed to burn solid fuel.  Type II “B” vent
connectors must be used on all installations and it must be
sized per the applicable sections of the (U.S.) National Fuel
Gas Code ANSI Z223.1/NFPA 54, and/or CSA B149.1
Natural Gas and Propane Installation Codes.

Type “B” Vent

:

The furnace is also approved for use with a “B” vent

that terminates through the roof.  Refer to the applicable
sections of the (U.S.) National Fuel Gas Code ANSI Z223.1/
NFPA 54, and/or CSA B149.1 Natural Gas and Propane
Installation Codes for proper sizing and set-up of this furnace
with “B” vent for a dedicated vent system or a common
vented system.

Horizontal Venting:

This furnace is design certified by CSA International for

horizontal venting through an outside wall by use of one of
the following auxiliary draft inducer kits:

See Figure 5 on page 12 for information on where the
sidewall vent terminal can and cannot terminate.

For Massachusetts Installations:

  The installation must

comply with Massachusetts 248 CMR 5.08 Modifications to
sections of NFPA-54, Chapter 10.  (See pages 26 and 27)

General Venting Requirements:

This furnace  may be common vented only with other

Category I appliances.  Common venting is allowed as
permitted by national and/or local codes.  Refer to the
applicable sections of the (U.S.) National Fuel Gas Code
ANSI Z223.1/NFPA 54, and/or CSA B149.1 Natural Gas and
Propane Installation Codes for proper sizing and set up.

The vent must be terminated with a listed vent cap or

roof assembly.  This venting must be installed in accordance
with the vent manufacturer’s instructions and be in
accordance with all local codes and/or national codes.

The following requirements are provided for a proper

venting system:
1. Be sure that the chimney flue is clear of any dirt or debris.
2. Be sure that the chimney is not servicing an open fireplace.

Table 3

AUXILIARY DRAFT INDUCERS

Содержание B050A3B

Страница 1: ...est Columbia SC 29170 SECTION 1 INSTALLATION AND SERVICING INSTRUCTIONS 1 28 Important Safety Information 2 Specification and Installation 3 Start up and Operation 17 Maintenance 21 Sequence of Operat...

Страница 2: ...e instructions 6 Always install furnace to operate within the furnace s intended temperature rise range with a duct system whichhasanexternalstaticpressurewithintheallowable range as specified in Temp...

Страница 3: ...506307 01 Page 3 of 36 Issue 1207...

Страница 4: ...al injury due to electrical shock or uncontrolled gas leakage WARNING When operating the furnace in the heating mode the static pressure and the temperature rise supply air temperature minus return ai...

Страница 5: ...506307 01 Page 5 of 36 Issue 1207 FURNACE WIRING SPECIFICATIONS...

Страница 6: ...ult the U S National Fuel Gas Code obtainable from the National Fire Protection Association Inc Batterymarch Park Quincy MA 02269 or the American Gas Association 1515 Wilson Boulevard Arlington VA 222...

Страница 7: ...e straps around each end of the furnace These straps should be attached to the furnace with sheet metal screws and to the rafters with bolts The furnace may also be suspended by using an angle iron fr...

Страница 8: ...o air needed for combustion ventilation in the form of process air must be provided as required for cooling of eqipment or material controlling dew point heating drying oxidation or dilution safety ex...

Страница 9: ...ons should be followed when installing the ductwork 1 Install locking type dampers in all branches of the individual ducts to balance out the system Dampers should be adjusted to impose the proper sta...

Страница 10: ...ction BTU INPUT FILTER SIZE 50 000 75 000 100 000 125 000 13 X 23 13 X 23 16 1 2 X 26 20 X 23 Table 2 VENTING Venting for the furnace must be to the outside and in accordance with local codes or requi...

Страница 11: ...ace must not be vented into a chimney serving a separate appliance designed to burn solid fuel Type II B vent connectors must be used on all installations and it must be sized per the applicable secti...

Страница 12: ...t ANSI Z223 1 NFPA 54 National Fuel Gas Code A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings Permit...

Страница 13: ...ing system being placed into operation while all other appliances connected to the common venting system are not in operation 1 Seal any unused openings in the venting system 2 Inspect the venting sys...

Страница 14: ...223 1 NFPA54 and or CSA B149 1 Natural Gas and Propane Installation Codes If local codes allow the use of a flexible gas appliance connector always use a new listed connector Do not use a connector wh...

Страница 15: ...tap in order to test incoming gas pressure and outgoing manifold pressure See Figure 9 FIELD SUPPLIED MAIN MANUAL SHUT OFF VALVE GAS SUPPLY DRIP LEG F0000317 Many soaps used for leak testing are corr...

Страница 16: ...valve and begins post purge and blower off delay time Open Limit Any time the limit switch is open the control de energizes the gas valve and runs the indoor blower motor on heat speed and runs the i...

Страница 17: ...position 5 Set the thermostat above room temperaturae 6 The ignitior will spark and the main burners will ignite Do not attempt to manually light the burners Failure to follow this warning can lead to...

Страница 18: ...If the heating value of the natural gas is 1015 Btu cu and it takes 60 seconds to burn 2 cu ft of gas then Input 1015 Btu cu ft x 1 rev x 2 cu ft rev x 3600 60 sec Input 121 8000 btu hr Burner Orific...

Страница 19: ...Prior to any blower adjustment electrical service must be turned OFF This furnace is equipped with a 3 speed direct drive motor to deliver a temperature rise within the range specificed on the rating...

Страница 20: ...vent from the combustion blower Place the furnace into operation Gradually cover up the blower outlet the main burners should shut OFF Remvoe the restriction and the unit should relight Replace the v...

Страница 21: ...be necessary to use a soft bristly brush to remove dirt and then vacuum 3 Remove the burner opening inlet plate This will expose the burner openings of the primary heat exchangers 4 Vacuum the length...

Страница 22: ...nd continue sliding the blower forward until it is out of the unit Replacement 1 Place the blower in the blower opening of the unit and slide the blower back into the unit taking care to clear the top...

Страница 23: ...506307 01 Page 23 of 36 Issue 1207 SEQUENCE OF OPERATION DIRECT IGNITION SYSTEM CONTROL...

Страница 24: ...till present Combustion blower energized The heat speed circulation air fan will be energized after the selected heat fan on delay System waits for flame signal to disappear then goes to Soft Lockout...

Страница 25: ...506307 01 Page 25 of 36 Issue 1207 WIRING DIAGRAM f0000321...

Страница 26: ...sion can not be met at the time of completion of installaiton the owner shall have a period of thirty 30 days to comply with the above requirements provided however that during said thirty 30 day peri...

Страница 27: ...ollowing requirements shall be satisfied by the manufacturer 1 The identification of each special venting system shall include the listing of either the website phone number or manufacturer s address...

Страница 28: ...Page 28 of 36 506307 01 Issue 1207 NOTES...

Страница 29: ...eep you warm and comfortable during the winter months It will deliver superb performance with only minimal help from you To keep your operating costs low and to eliminate unnecessary service calls we...

Страница 30: ...e to the furnace before shutting off the electrical supply 6 Do not use the furnace if any part has been under water A flood damaged furnace is extremely dangerous Attempts to use the furnace can resu...

Страница 31: ...fan switch on the thermostat permits you to do this see Figure M 2 on page 32 With the switch in the ON position the fan will operate continuously AUTO position gives fan operation only when the unit...

Страница 32: ...ashlight will be useful for these inspections Make one inspection prior to the beginning of the heating season and another during the middle Should you observe unusual amounts of any of the following...

Страница 33: ...r washing Cleanable filters may be replaced with disposable filters Refer to Table 1 on page 33 when selecting the proper size and quantity of disposable filter If your air distribution system has a c...

Страница 34: ...urnace still does not operate call your dealer for service Lubrication Lubrication of the bearings in the circulating air blower motor and the combustion blower motor is not recommended Burner Flame W...

Страница 35: ..._______________ Serial _________________________ Installation Date ____________ Equipment Type ______________________________________ Model _________________________________ Serial ___________________...

Страница 36: ...AFFIX THIS INSTRUCTION PACKET ADJACENT TO THE FURNACE HOMEOWNER RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE INSTRUCTIONS D ENTRETIEN ET INSTALLATION ET MANUAL DE L USAGER INSTALLATEUR PLACEZ LA POC...

Отзывы: