background image

Page 1

©

2006 Lennox Industries Inc.

Corp. 0612−L2

13ACX

Service Literature

Revised 06−2007

13ACX  SERIES UNITS

The 13ACX  is a high efficiency residential split−system con-
densing unit, which features a scroll compressor and de-
signed for R−410A refrigerant. 13ACX units are available in
sizes ranging from 1−1/2 through 5 tons. The series is de-
signed for use with an expansion valve in the indoor unit.
This manual is divided into sections which discuss the major
components, refrigerant system, charging procedure, main-
tenance and operation sequence.
Information contained in this manual is intended for use by
qualified service technicians only. All specifications are sub-
ject to change.

IMPORTANT

Operating pressures of this R−410A unit are higher
than pressures in R−22 units. Always use service
equipment rated for R−410A.

WARNING

Improper installation, adjustment, alteration, service
or maintenance can cause property damage, person-
al injury or loss of life. Installation and service must
be performed by a qualified installer or service
agency.

WARNING

Warranty will be voided if covered equipment is re-
moved from original installation site. Warranty will
not cover damage or defect resulting from:
Flood, wind, lightning, or installation and operation in
a corrosive atmosphere (chlorine, fluorine, salt, re-
cycled waste water, urine, fertilizers, or other damag-
ing chemicals).

TABLE OF CONTENTS

General Page 

1

. . . . . . . . . . . . . . . . . . . . . . . . . . . 

Specifications / Electrical Data

Page 2

. . . . . . . . 

I Application

Page 3

. . . . . . . . . . . . . . . . . . . . . . . . 

II Unit Components

Page 3

. . . . . . . . . . . . . . . . . . 

III Refrigeration System

Page 6

. . . . . . . . . . . . . . 

IV Charging

Page 7

. . . . . . . . . . . . . . . . . . . . . . . . 

VI Maintenance

Page 13

. . . . . . . . . . . . . . . . . . . . . 

VII Wiring and Sequence of Operation

Page 14

Содержание 13ACX?018

Страница 1: ...g pressures of this R 410A unit are higher than pressures in R 22 units Always use service equipment rated for R 410A WARNING Improper installation adjustment alteration service or maintenance can cau...

Страница 2: ...bs kg 1 package 122 55 129 59 150 68 150 68 177 80 201 91 222 100 ELECTRICAL DATA Line voltage data 60 hz 1ph 208 230V 208 230V 208 230V 208 230V 208 230V 208 230V 208 230V 2 Maximum overcurrent prote...

Страница 3: ...ming any service procedure FIGURE 2 DUAL CAPACITOR C12 COMPRESSOR CONTACTOR K1 CONTROL BOX GROUNDING LUG TIMED OFF CONTROL OPTION 1 Compressor Contactor K1 DANGER Shock Hazard Remove all power at disc...

Страница 4: ...harge pressure forcing down on the top scroll helps seal off the upper and lower edges tips of the scrolls figure 5 During a single orbit several pockets of gas are compressed simultaneously providing...

Страница 5: ...g the four nuts found on top of the grill See figure 8 if condenser fan motor replacement is necessary Make sure all power is disconnected before beginning electrical service procedures DANGER FIGURE...

Страница 6: ...NOTE Use a 3 16 hex head extension for 3 8 line sizes or a 5 16 extension for large line sizes 3 Replace the stem cap Tighten finger tight then tighten an additional 1 6 turn To Close Service Valve 1...

Страница 7: ...set Disconnect the R 410A cylinder 4 Connect a cylinder of nitrogen with a pressure regulat ing valve to the center port of the manifold gauge set 5 Connect the manifold gauge set high pressure hose...

Страница 8: ...rant Open the manifold gauge valves to break the vacuum from 1 to 2 psig positive pressure in the line set and indoor unit Close manifold gauge valves and shut off the R 410A cylinder and remove the m...

Страница 9: ...38 394 143 402 144 393 142 410 142 406 143 394 137 400 136 407 137 105 41 417 145 430 145 418 143 436 143 432 143 418 139 426 137 433 138 110 43 445 146 457 146 445 144 463 145 459 145 446 140 451 13...

Страница 10: ...refrigerant is metered 39 F 3 8 C and Below Which metering device WEIGH IN 64 F 17 7 C and Below 40 F 4 4 C and Above FIGURE 12 Weigh in Charge 1 Recover the refrigerant from the unit 2 Conduct leak c...

Страница 11: ...for heat must have a cooling load between 70 80 F 21 26 C 5 Connect gauge set 6 When heat demand is satisfied set thermostat to call for cooling 7 Allow temperatures and pressures to stabilize 8 Meas...

Страница 12: ...mbient temperature BELOW USE WEIGH IN METHOD Weigh in or remove refriger ant based upon line length SC Subcooling Values F 1 0 C 0 6 Outdoor Am bient 65 F 18 C If refrigerant added or removed verify c...

Страница 13: ...positioning it in its original position and reinserting the push pin No tool is required to push the pin back into the same slot in the fins If the push pin is loose and tends not to stay in place br...

Страница 14: ...om indoor unit Y1 energizes the TOC timed off control if used which energizes contactor K1 3 K1 1 N O closes energizing compressor B1 and outdoor fan motor B4 4 Compressor B1 and outdoor fan motor B4...

Отзывы: