Lennox 13ACX?018 Скачать руководство пользователя страница 8

Page 8

 5 − Evacuate the line set and indoor unit to an 

absolute

pressure

 of 23,000 microns (29.01 inches  of mercury).

During the early stages of evacuation, it is desirable to
close the manifold gauge valve at least once to deter-
mine if there is a rapid rise in 

absolute pressure

. A rap-

id rise in pressure indicates a relatively large leak. If this
occurs, repeat the leak testing procedure.

NOTE − The term 

absolute pressure

 means the total

actual pressure within a given volume or system, above
the absolute zero of pressure. Absolute pressure in a
vacuum is equal to atmospheric pressure minus vacu-
um pressure.

 6 − When the absolute pressure reaches 23,000 microns

(29.01 inches  of mercury), close the manifold gauge
valves, turn off the vacuum pump and disconnect the
manifold gauge center port hose from vacuum pump.
Attach the manifold center port hose to a nitrogen cylin-
der with pressure regulator set to 150 psig (1034 kPa)
and purge the air from the hose with nitrogen. Open the
manifold gauge valves to break the vacuum in the line
set and indoor unit. Close the manifold gauge valves.

CAUTION

Danger of Equipment Damage.
Avoid deep vacuum operation. Do not use compres-
sors to evacuate a system.
Extremely low vacuums can cause internal arcing and
compressor failure.
Damage caused by deep vacuum operation will void
warranty.

 7 − Shut off the nitrogen cylinder and remove the manifold

gauge hose from the cylinder. Open the manifold gauge
valves to release the nitrogen from the line set and in-
door unit.

 8 − Reconnect the manifold gauge to the vacuum pump,

turn the pump on, and continue to evacuate the line set
and indoor unit until the absolute pressure does not rise
above 500 microns (29.9 inches of mercury) within a
20−minute period after shutting off the vacuum pump
and closing the manifold gauge valves.

 9 − When  the  absolute  pressure  requirement  above  has

been met, disconnect the manifold hose from the vacu-
um pump and connect it to an upright cylinder of R−410A
refrigerant. Open the manifold gauge valves to break the
vacuum from 1 to 2 psig positive pressure in the line set
and indoor unit. Close manifold gauge valves and shut
off the R−410A cylinder and remove the manifold gauge
set.

C − Charging

This system is charged with R−410A refrigerant which oper-
ates at much higher pressures than HCFC−22. The recom-
mended check expansion valve is approved for use with
R−410A. Do not replace it with a valve that is designed to be
used with HCFC−22. This unit is NOT approved for use with
coils that include metering orifices or capillary tubes.

Check Indoor Airflow before Charging

NOTE − Be sure that filters and indoor and outdoor coils are clean before testing.

Check indoor airflow using the step procedures as illustrated in figure 11.

Step 1. Determine the desired 

D

T

Measure entering air tempera-

ture using dry bulb (

A

) and wet bulb (

B

). 

D

T

 is the intersecting value

of 

A

 and

 B

 in the table (see triangle).

Step 2. Find temperature drop across coil

Measure the coil’s dry

bulb entering and leaving air temperatures (

A

 and 

C

). Temperature

Drop Formula: (

T

Drop

) = 

A

 minus 

C

.

Step 3. Determine if fan needs adjustment

If the difference be-

tween the measured 

T

Drop

 and the desired 

D

T

 

(T

Drop

D

T) 

is within

+3º, no adjustment is needed. See examples: Assume 

D

T

 = 15 and

A

 temp. = 72º, these 

temperatures would necessitate stated ac-

tions:

Cº T

Drop

D

T

=

ºF

ACTION

53º

 19

15

=

4

Increase the airflow

58º

14

15

=

−1

(3º range) no change

62º

10

15

=

−5

Decrease the airflow

Step 4. Adjust the fan speed

See indoor unit instructions to in-

crease/decrease fan speed.

Changing air flow affects all temperatures; recheck temperatures to
confirm that the temperature drop and 

D

T are 3º.

D

T

80

24 24 24 23 23 22 22 22 20 19 18 17 16 15

78

23 23 23 22 22 21 21 20 19 18 17 16 15 14

76

22 22 22 21 21 20 19 19 18 17 16 15 14 13

74

21 21 21 20 19 19 18 17 16 16 15 14 13 12

72

20 20 19 18 17 17 16 15 15 14 13 12 11 10

70

19 19 18 18 17 17 16 15 15 14 13 12 11 10

57 58 59 60 61 62 63 64 65 66 67 68 69 70

Temp.
of air
entering
indoor
coil ºF

INDOOR
COIL

DRY BULB

DRY

BULB

WET

BULB

B

T

Drop

19º

A

Dry−bulb

Wet−bulb ºF

A

72º

B

64º

C

53º

air flow

air flow

All temperatures are
expressed in ºF

FIGURE 11

Содержание 13ACX?018

Страница 1: ...g pressures of this R 410A unit are higher than pressures in R 22 units Always use service equipment rated for R 410A WARNING Improper installation adjustment alteration service or maintenance can cau...

Страница 2: ...bs kg 1 package 122 55 129 59 150 68 150 68 177 80 201 91 222 100 ELECTRICAL DATA Line voltage data 60 hz 1ph 208 230V 208 230V 208 230V 208 230V 208 230V 208 230V 208 230V 2 Maximum overcurrent prote...

Страница 3: ...ming any service procedure FIGURE 2 DUAL CAPACITOR C12 COMPRESSOR CONTACTOR K1 CONTROL BOX GROUNDING LUG TIMED OFF CONTROL OPTION 1 Compressor Contactor K1 DANGER Shock Hazard Remove all power at disc...

Страница 4: ...harge pressure forcing down on the top scroll helps seal off the upper and lower edges tips of the scrolls figure 5 During a single orbit several pockets of gas are compressed simultaneously providing...

Страница 5: ...g the four nuts found on top of the grill See figure 8 if condenser fan motor replacement is necessary Make sure all power is disconnected before beginning electrical service procedures DANGER FIGURE...

Страница 6: ...NOTE Use a 3 16 hex head extension for 3 8 line sizes or a 5 16 extension for large line sizes 3 Replace the stem cap Tighten finger tight then tighten an additional 1 6 turn To Close Service Valve 1...

Страница 7: ...set Disconnect the R 410A cylinder 4 Connect a cylinder of nitrogen with a pressure regulat ing valve to the center port of the manifold gauge set 5 Connect the manifold gauge set high pressure hose...

Страница 8: ...rant Open the manifold gauge valves to break the vacuum from 1 to 2 psig positive pressure in the line set and indoor unit Close manifold gauge valves and shut off the R 410A cylinder and remove the m...

Страница 9: ...38 394 143 402 144 393 142 410 142 406 143 394 137 400 136 407 137 105 41 417 145 430 145 418 143 436 143 432 143 418 139 426 137 433 138 110 43 445 146 457 146 445 144 463 145 459 145 446 140 451 13...

Страница 10: ...refrigerant is metered 39 F 3 8 C and Below Which metering device WEIGH IN 64 F 17 7 C and Below 40 F 4 4 C and Above FIGURE 12 Weigh in Charge 1 Recover the refrigerant from the unit 2 Conduct leak c...

Страница 11: ...for heat must have a cooling load between 70 80 F 21 26 C 5 Connect gauge set 6 When heat demand is satisfied set thermostat to call for cooling 7 Allow temperatures and pressures to stabilize 8 Meas...

Страница 12: ...mbient temperature BELOW USE WEIGH IN METHOD Weigh in or remove refriger ant based upon line length SC Subcooling Values F 1 0 C 0 6 Outdoor Am bient 65 F 18 C If refrigerant added or removed verify c...

Страница 13: ...positioning it in its original position and reinserting the push pin No tool is required to push the pin back into the same slot in the fins If the push pin is loose and tends not to stay in place br...

Страница 14: ...om indoor unit Y1 energizes the TOC timed off control if used which energizes contactor K1 3 K1 1 N O closes energizing compressor B1 and outdoor fan motor B4 4 Compressor B1 and outdoor fan motor B4...

Отзывы: