Lennox 13ACX?018 Скачать руководство пользователя страница 7

Page 7

IV − CHARGING

WARNING

R−410A refrigerant can be harmful if it is inhaled.
R−410A refrigerant must be used and recovered re-
sponsibly.

Failure to follow this warning may result in personal
injury or death.

A − Leak Testing

After the line set has been connected to the indoor and out-
door units, check the line set connections and indoor unit
for leaks.

IMPORTANT

The Clean Air Act of 1990 bans the intentional venting
of (CFC’s and HFC’s) as of July 1, 1992. Approved
methods of recovery, recycling or reclaiming must be
followed. Fines and/or incarceration my be levied for
noncompliance.

WARNING

Fire, Explosion and Personal Safety
Hazard.
Failure to follow this warning could
result in damage, personal injury or
death.
Never use oxygen to pressurize or
purge refrigeration lines. Oxygen,
when exposed to a spark or open
flame, can cause damage by fire
and / or an explosion, that can re-
sult in personal injury or death.

WARNING

Danger of explosion!
When using a high pressure gas such
as dry nitrogen to pressurize a refriger-
ant or air conditioning system, use a
regulator that can control the pressure
down to 1 or 2 psig (6.9 to 13.8 kPa).

Using an Electronic Leak Detector

 1 − Connect a cylinder of R−410A to the center port of the

manifold gauge set. Connect manifold gauge to service
valve port.

 2 − With both manifold valves closed, open the valve on the

R−410A cylinder.

 3 − Open the high pressure side of the manifold to allow the

R−410A into the line set and indoor unit. Weigh in a trace
amount of R−410A.

 

[A trace amount is a maximum of 2

ounces (57 g) or 3 pounds (31 kPa) pressure.]

 

Close the

valve on the R−410A cylinder and the valve on the high
pressure side of the manifold gauge set. Disconnect the
R−410A cylinder.

 4 − Connect a cylinder of nitrogen with a pressure regulat-

ing valve to the center port of the manifold gauge set.

 5 − Connect the manifold gauge set high pressure hose to

the vapor valve service port. 

(Normally, the high pres-

sure hose is connected to the liquid line port; however,
connecting it to the vapor port better protects the man-
ifold gauge set from high pressure damage.)

 6 − Adjust the nitrogen pressure to 150 psig (1034 kPa).

Open the valve on the high side of the manifold gauge
set which will pressurize line set and indoor unit.

 7 − After a few minutes, open a refrigerant port to ensure

the refrigerant you added is adequate to be detected.
(Amounts of refrigerant will vary with line lengths.)
Check all joints for leaks. Purge nitrogen and R−410A
mixture. Correct any leaks and recheck.

B − Evacuating

Evacuating the system of noncondensables is critical for
proper operation of the unit. Noncondensables are defined
as any gas that will not condense under temperatures and
pressures present during operation of an air conditioning
system. Noncondensables and water vapor combine with
refrigerant to produce substances that corrode copper pip-
ing and compressor parts.

NOTE − This evacuation process is adequate for a new
installation with clean and dry lines. If excessive mois-
ture is present, the evacuation process may be required
more than once.

IMPORTANT

Use a thermocouple or thermistor electronic vacuum
gauge that is calibrated in microns. Use an instrument
that reads from 50 microns to at least 20,000 microns.

 1 − Connect manifold gauge set to the service valve ports :

 

 

low pressure gauge to 

vapor 

line service valve

 

 

high pressure gauge to 

liquid 

line service valve

 2 − Connect micron gauge.

 3 − Connect the vacuum pump (with vacuum gauge) to the

center port of the manifold gauge set.

 4 − Open both manifold valves and start the vacuum

pump.

Содержание 13ACX?018

Страница 1: ...g pressures of this R 410A unit are higher than pressures in R 22 units Always use service equipment rated for R 410A WARNING Improper installation adjustment alteration service or maintenance can cau...

Страница 2: ...bs kg 1 package 122 55 129 59 150 68 150 68 177 80 201 91 222 100 ELECTRICAL DATA Line voltage data 60 hz 1ph 208 230V 208 230V 208 230V 208 230V 208 230V 208 230V 208 230V 2 Maximum overcurrent prote...

Страница 3: ...ming any service procedure FIGURE 2 DUAL CAPACITOR C12 COMPRESSOR CONTACTOR K1 CONTROL BOX GROUNDING LUG TIMED OFF CONTROL OPTION 1 Compressor Contactor K1 DANGER Shock Hazard Remove all power at disc...

Страница 4: ...harge pressure forcing down on the top scroll helps seal off the upper and lower edges tips of the scrolls figure 5 During a single orbit several pockets of gas are compressed simultaneously providing...

Страница 5: ...g the four nuts found on top of the grill See figure 8 if condenser fan motor replacement is necessary Make sure all power is disconnected before beginning electrical service procedures DANGER FIGURE...

Страница 6: ...NOTE Use a 3 16 hex head extension for 3 8 line sizes or a 5 16 extension for large line sizes 3 Replace the stem cap Tighten finger tight then tighten an additional 1 6 turn To Close Service Valve 1...

Страница 7: ...set Disconnect the R 410A cylinder 4 Connect a cylinder of nitrogen with a pressure regulat ing valve to the center port of the manifold gauge set 5 Connect the manifold gauge set high pressure hose...

Страница 8: ...rant Open the manifold gauge valves to break the vacuum from 1 to 2 psig positive pressure in the line set and indoor unit Close manifold gauge valves and shut off the R 410A cylinder and remove the m...

Страница 9: ...38 394 143 402 144 393 142 410 142 406 143 394 137 400 136 407 137 105 41 417 145 430 145 418 143 436 143 432 143 418 139 426 137 433 138 110 43 445 146 457 146 445 144 463 145 459 145 446 140 451 13...

Страница 10: ...refrigerant is metered 39 F 3 8 C and Below Which metering device WEIGH IN 64 F 17 7 C and Below 40 F 4 4 C and Above FIGURE 12 Weigh in Charge 1 Recover the refrigerant from the unit 2 Conduct leak c...

Страница 11: ...for heat must have a cooling load between 70 80 F 21 26 C 5 Connect gauge set 6 When heat demand is satisfied set thermostat to call for cooling 7 Allow temperatures and pressures to stabilize 8 Meas...

Страница 12: ...mbient temperature BELOW USE WEIGH IN METHOD Weigh in or remove refriger ant based upon line length SC Subcooling Values F 1 0 C 0 6 Outdoor Am bient 65 F 18 C If refrigerant added or removed verify c...

Страница 13: ...positioning it in its original position and reinserting the push pin No tool is required to push the pin back into the same slot in the fins If the push pin is loose and tends not to stay in place br...

Страница 14: ...om indoor unit Y1 energizes the TOC timed off control if used which energizes contactor K1 3 K1 1 N O closes energizing compressor B1 and outdoor fan motor B4 4 Compressor B1 and outdoor fan motor B4...

Отзывы: