III − REFRIGERANT SYSTEM

A − Plumbing

Field refrigerant piping consists of liquid and suction lines
from the condensing unit (sweat connections) to the indoor
evaporator coil (sweat connections). Use Lennox  L15
(sweat) series line sets as shown in table 1.

TABLE 1

 Unit

Liquid

Line

Suction

Line

L15 Line Sets

−018
−024
−030

3/8 in.

(10 mm)

3/4 in.

(19 mm)

L15−41

15 ft. − 50 ft.

(4.6 m − 15 m)

−036
−042
−048

3/8 in.

(10 mm)

7/8 in.

(22 mm)

L15−65

15 ft. − 50 ft.

(4.6 m − 15 m)

−060

3/8 in.

(10 mm)

1−1/8 in.

(29 mm)

Field

Fabricated

The liquid line and vapor line service valves (figures 9 and
10) and gauge ports are accessible from the outside of the
unit. Use the service ports for leak testing, evacuating,
charging and checking charge.

Each valve is equipped with a service port which has a facto-
ry−installed Schrader valve. A service port cap protects the
Schrader valve from contamination and serves as the pri-
mary leak seal.

 Service valves are not rebuildable. If a valve

has failed, you must replace it.

To Access Schrader Port:

 1 − Remove service port cap with an adjustable wrench.

 2 − Connect gauge to the service port.

 3 − When testing is complete, replace service port cap. Tight-

en finger tight, then an additional 1/6 turn.

To Open Service Valve:

 1 − Remove the stem cap with an adjustable wrench.

 2 − Using the adjustable wrench to keep the valve station-

ary, use a service wrench with a hex−head extension to
back the stem out counterclockwise as far as it will go.

NOTE − Use a 3/16" hex head extension for 3/8" line
sizes or a 5/16" extension for large line sizes.

 3 − Replace the stem cap. Tighten finger tight, then tighten

an additional 1/6 turn.

To Close Service Valve:

 1 − Remove the stem cap with an adjustable wrench.

 2 − Using the adjustable wrench to keep the valve station-

ary, use a service wrench with a hex−head extension to
turn the stem clockwise to seat the valve. Tighten the
stem firmly.

NOTE − Use a 3/16" hex head extension for 3/8" line
sizes or a 5/16" extension for large line sizes.

 3 − Replace the stem cap. Tighten finger tight, then tighten an

additional 1/6 turn.

NOTE − Stem cap must be replaced to help prevent
valve leakage.

Service Valve

(Valve Closed)

Schrader valve open

to line set when valve is

closed (front seated)

service

port

service

port cap

stem cap

insert hex

wrench here

(valve front seated)

to outdoor coil

to indoor coil

Service Valve

(Valve Open)

Schrader

valve

service

port

service port

cap

insert hex

wrench here

to indoor coil

to outdoor coil

stem cap

FIGURE  9

Vapor Line Ball Valve – 5 Ton Units Only

Vapor line service valves function the same way as the other
valves, the difference is in the construction.  A ball valve is
illustrated in figure 10.
The ball valve is equipped with a service port with a factory−
installed Schrader valve. A service port cap protects the
Schrader valve from contamination and assures a leak−free
seal.

Ball Valve (Valve Open)

FIGURE 10

Schrader valve

service port

service port

cap

stem cap

stem

Use Adjustable Wrench

To open:  rotate Stem Clockwise 90°.

To close:  rotate Stem Counter-clockwise 90°.

ball

(shown open)

to outdoor coil

to indoor coil

Содержание 13ACX?018

Страница 1: ...g pressures of this R 410A unit are higher than pressures in R 22 units Always use service equipment rated for R 410A WARNING Improper installation adjustment alteration service or maintenance can cau...

Страница 2: ...bs kg 1 package 122 55 129 59 150 68 150 68 177 80 201 91 222 100 ELECTRICAL DATA Line voltage data 60 hz 1ph 208 230V 208 230V 208 230V 208 230V 208 230V 208 230V 208 230V 2 Maximum overcurrent prote...

Страница 3: ...ming any service procedure FIGURE 2 DUAL CAPACITOR C12 COMPRESSOR CONTACTOR K1 CONTROL BOX GROUNDING LUG TIMED OFF CONTROL OPTION 1 Compressor Contactor K1 DANGER Shock Hazard Remove all power at disc...

Страница 4: ...harge pressure forcing down on the top scroll helps seal off the upper and lower edges tips of the scrolls figure 5 During a single orbit several pockets of gas are compressed simultaneously providing...

Страница 5: ...g the four nuts found on top of the grill See figure 8 if condenser fan motor replacement is necessary Make sure all power is disconnected before beginning electrical service procedures DANGER FIGURE...

Страница 6: ...NOTE Use a 3 16 hex head extension for 3 8 line sizes or a 5 16 extension for large line sizes 3 Replace the stem cap Tighten finger tight then tighten an additional 1 6 turn To Close Service Valve 1...

Страница 7: ...set Disconnect the R 410A cylinder 4 Connect a cylinder of nitrogen with a pressure regulat ing valve to the center port of the manifold gauge set 5 Connect the manifold gauge set high pressure hose...

Страница 8: ...rant Open the manifold gauge valves to break the vacuum from 1 to 2 psig positive pressure in the line set and indoor unit Close manifold gauge valves and shut off the R 410A cylinder and remove the m...

Страница 9: ...38 394 143 402 144 393 142 410 142 406 143 394 137 400 136 407 137 105 41 417 145 430 145 418 143 436 143 432 143 418 139 426 137 433 138 110 43 445 146 457 146 445 144 463 145 459 145 446 140 451 13...

Страница 10: ...refrigerant is metered 39 F 3 8 C and Below Which metering device WEIGH IN 64 F 17 7 C and Below 40 F 4 4 C and Above FIGURE 12 Weigh in Charge 1 Recover the refrigerant from the unit 2 Conduct leak c...

Страница 11: ...for heat must have a cooling load between 70 80 F 21 26 C 5 Connect gauge set 6 When heat demand is satisfied set thermostat to call for cooling 7 Allow temperatures and pressures to stabilize 8 Meas...

Страница 12: ...mbient temperature BELOW USE WEIGH IN METHOD Weigh in or remove refriger ant based upon line length SC Subcooling Values F 1 0 C 0 6 Outdoor Am bient 65 F 18 C If refrigerant added or removed verify c...

Страница 13: ...positioning it in its original position and reinserting the push pin No tool is required to push the pin back into the same slot in the fins If the push pin is loose and tends not to stay in place br...

Страница 14: ...om indoor unit Y1 energizes the TOC timed off control if used which energizes contactor K1 3 K1 1 N O closes energizing compressor B1 and outdoor fan motor B4 4 Compressor B1 and outdoor fan motor B4...

Отзывы: