SYMPTOM

PROBABLE CAUSE

CORRECTIVE ACTION

Thin black coating (soot) 

forms on the viewing 

glass, logs, or firebox

Improper log or ember 

placement

Improper air shutter 

setting

Not enough combus-

tion air

See 

Log Set Installation on Page 19

. If there is soot in one specific location, the 

rockwool below this location needs to be adjusted. This can be done by pulling embers 

forward slightly. If the flames have soot tails, the shutter will need to be opened.

If sooting continues open air shutter (see 

Air Shutter Adjustment on Page 25).

Check for debris obstructing air flow in valve compartment under fireplace or in front of 

lower venting.

Humming or whistling 

coming from fireplace.

Normal operating noise

Obstructed orifice 

opening

See 

Quiet Operation on Page 26

. The noise may be reduced by slightly turning down the 

flame. Turning the flame down will reduce the heat output of the fireplace.

If noise is excessive or is “whistling” have your gas supplier check the regulator and 

orifices and replace if necessary.

A change in flame appear-

ance or burner operation.

A change in gas pres-

sure

Improper log, ember or 

volcanic stone place-

ment

Have your gas supplier check for correct gas pressure (7" W.C. / po. C.E. [1.74 kPa] natu-

ral gas; 11" W.C. / po. C.E. [2.74 kPa] LP gas). 

NOTE:  NEVER BLOCK OR OBSTRUCT AIR 

INTAKE OR OUTLET VENTS.

See 

Log Set Installation on Page 19.

Spark igniter will not light 

pilot after repeated tries.

No gas supplied to unit 

or air in line

Defective igniter (no 

spark at electrode)

Defective or misaligned 

electrode at pilot (spark 

at electrode)

Check gas supply. To purge, hold in gas cock on valve for 1-2 minutes and try again.

Check for spark at electrode and pilot, if no spark and electrode wire is properly con-

nected, replace igniter and igniter wire.

Using a match, light pilot. If pilot lights, turn off pilot and trigger the igniter again. If pilot 

lights, an intermittent gas/air supply may be the problem, if longer purge will not light 

- check gap between electrode and pilot - should be 1/8 inch (3 mm) to have a strong 

spark. If OK, replace pilot.

Pilot will not stay lit after 

carefully following lighting 

instructions.

Low gas inlet pressure

Defective thermopile

Defective automatic 

valve operator

Check inlet pressure and adjust pilot if necessary.

Be sure wire connections from thermopile are tight at gas valve terminals.

Either rocker switch or thermostat wires may be grounded. Remove wires from valve 

terminals. If pilot stays lit, trace switch wiring for a ground. May be grounded to fireplace 

or gas supply.

Check open circuit millivolt output of thermopile. Reading should be greater than 325mV. 

Also check thermopile wire for kinks that can cause loss of mV. Replace faulty thermopile 

if wire is okay and reading is less than 325mV.

Turn valve knob to “ON” and thermostat (if installed) to 90º. Millivolt meter should read 

greater than 100 mV. If reading is OK and burner does not turn on, replace gas valve 

(qualified service technician only).

Main burner will not burn. Pilot has gone out

Rocker switch, thermo-

stat, or wires defective

Thermopile may not be 

generating sufficient 

millivolts

See 

Lighting Instructions.

Disconnect rocker switch and thermostat wires at terminals 1 and 3 on valve. Jumper 

across from 1 to 3 with pilot lit. If burner comes on either rocker switch, thermostat, or 

wiring is not functioning.

Check thermopile with millivolt meter (see 

Maintenance and Servicing

), recheck symp-

tom #2.

NOTE:  When troubleshooting the gas control system, be sure the external gas shut off valve, located at the gas supply inlet is in 

the “ON” position.

IMPORTANT:  Call your gas supplier or plumber for additional help with any gas control problem.  Valve system troubleshooting 

should only be accomplished by a qualified service technician.

TROUBLESHOOTING

Содержание RAVELLE 30

Страница 1: ...debiensuivrelesinstruc tionsdonn esdanscettenoticepourr duireauminimum le risque d incindie ou d explosion ou pour viter tout dommage mat riel toute blessure ou la mort These appliances may be install...

Страница 2: ...any make shift compromises during in stallation Any modification or alteration may result in damage to the appliance or dwelling and will void the warranty certification and listings of this unit Fail...

Страница 3: ...12 Vent Considerations 13 Horizontal Vent Installation 14 Vertical Vent Installation 14 Vertical Vent Termination Clearances 15 Flue Restrictors 16 Horizontal Terminations 17 Vertical Terminations 17...

Страница 4: ...rd for Mobile Home Installations ANSI A225 1 latest edition Must be vented directly to the outside in accordance with the latest edition of the National Fuel Gas Code and must never be attached to a c...

Страница 5: ...g the cassette valve and pilot assembly or installing a conversion kit Only Lennox Hearth Products conversion kits can be used to convert from NG to LP or LP to NG Contact your Lennox Hearth Products...

Страница 6: ...offs 0 0mm Rear corners to enclosure from standoffs 0 0mm Top to header from standoffs 0 0mm Bottom of unit to floor 0 0mm Edge of door glass to side wall and side trim 6 1 4 159mm Back to enclosure f...

Страница 7: ...ical power supply wiring should be routed to the right rear of the unit Note The fireplace may be placed directly on wood or non combustible flooring but not on vinyl floor covering or carpet Framing...

Страница 8: ...d if desired Should a hearth extension thicker than 7 8 22 mm be desired the height of the fireplace must be raised the thickness of that hearth extension less the 7 8 22 mm For example if a 2 7 8 73...

Страница 9: ...behind the fireplace see below Cement Board 3 8 Tile and 1 2 Cement Board Behind Fireplace Face Cement Board a minimum of five inches wide Sheetrock 1 Reveal 5 127mm Minimum Sheetrock Facing Installat...

Страница 10: ...d face installation The corners of the 1 25mm reveal around the fireplace opening need to be adjusted prior to installing an arched face see below Remove screws A and loosen screw B Rotate the corner...

Страница 11: ...efore installing the fire place face The acid wash will tarnish the face Consult your masonry installer Face Installation AnumberofdifferentfacesareavailablefortheRavelle 30gasfireplace however all th...

Страница 12: ...t approved or manufactured by the approved vent manufacturer Installation other than as instructed by Lennox Hearth Products and vent manufacturers instructions Vent Parts List DirectventpipeSecurity...

Страница 13: ...ed by examining the inside of the female ends Supports Horizontal runs of vent must be supported every three feet Wall straps are available for this purpose Pipe Sealing If Security Secure Vent pipe i...

Страница 14: ...6 mm rise for every one foot of run towards the termination 7 If the wall being penetrated is constructed of non combustible mate rial such as masonry block or concrete a 7 1 2 191 mm diameter hole is...

Страница 15: ...m is 10 feet 3M Vertical Vent Termination Clearances The vent air intake termination clearances above the high side of an angled roof is as shown in the Figure 17 Termination Heights For Vents Above F...

Страница 16: ...sitions are based on tests run in a laboratory The optimum restrictor positions may need to be adjusted slightly depending on the conditions surrounding the residential installation Do not adjust rest...

Страница 17: ...the top of the vertical length of pipe is allowed as long as the overall length of the horizontal run of pipe does not exceed those shown below Use the restrictor positions indicated Horizontal Termi...

Страница 18: ...ve meter regulator assembly 3 feet 91 cm within a height of 15 feet above the meter regulator assembly 3 feet 91 cm within a height of 15 feet above the meter regulator assembly I Clearance to service...

Страница 19: ...k panels which are shipped in the firebox 2 The long rectangular panel goes in the rear of the firebox he thin layer of bricks should be down The panel rests on 3 metal tabs protruding from the rear o...

Страница 20: ...and join this wire to the black supply wire reusing the wire nut Repeat for white wire Reinstall the electrical box cover If a wall mounted burner on off switch or thermostat is to be used the wires r...

Страница 21: ...insertasmallphillipsscrewdriver into the tap and turn a half turn counter clockwise Cover the tap with the line from a manometer and check the pressure Close the tap gently but securely after completi...

Страница 22: ...ing with or without the fireplace fan running air is drawn from a distant room lowering the pressure in that room through the return air duct into the bottom of the fireplace The air then passes throu...

Страница 23: ...appliance is equipped with a piezo ignition device to light the pilot When lighting the pilot follow these instructions exactly B BEFORE LIGHTING smell around the appliance area for gas Be sure to sme...

Страница 24: ...r switch and or thermostat if in stalled to its lowest setting 2 Turn off electric power to the appliance if service is to be performed 3 Push in gas control knob slightly and turn clockwise to OFF Do...

Страница 25: ...ellow Flame Blue Flame Center Ports on Burner Assembly Burner Flame Appearance Figure 34 Air Shutter Control Lever Gas Valve Air Shutter Adjustment The Ravelle 30 gas fireplace has an air shutter cont...

Страница 26: ...cur Do not mount the thermostat where it may be affected by Radiant heat from this appliance fireplaces sun or other heat sources Drafts or dead spots behind doors or in corners Hot or cold air from d...

Страница 27: ...the chance of the burner not igniting Follow the instructions included with the thermostat for wiring The ther mostatandrockerswitchwillturntheburneronandoffindependently Be suretosettherockerswitcht...

Страница 28: ...s when the unit is hot o Check the hot air outlet vents for lint or other accumulations Never block or restrict vent openings obstruct flow of ventilation air or use vents other than those approved fo...

Страница 29: ...and Log Set Installation 3 Remove the two allen head screws at the left and right rear of the firebox securing the air control panel Lift out the air control panel 4 Remove the one allen head screw h...

Страница 30: ...ht pilot If pilot lights turn off pilot and trigger the igniter again If pilot lights an intermittent gas air supply may be the problem if longer purge will not light check gap between electrode and p...

Страница 31: ...Main Burner Orifice 52 LP H5958 Pilot Orifice NG H3141 Pilot Orifice LP H5897 Main Gas Valve Supply Line H3117 Blower W Mounting Bracket H3857 Blower Snap Switch H5742 Blower Speed Control rheostat H...

Страница 32: ...S Glass Door Box 1 of 3 75092 PILCST PILRS2 Back Pillars Top Box 2 of 3 75094 PILCST GRL TRD3 Grill Bars Traditional Box 3 of 3 or 75091 PILCST GRL FIL3 Grill Filigree Ornate Box 3 of 3 Gas Conversion...

Страница 33: ...a Black Nickel 75298 AI30 TUSCAN BLK Tuscan Black 75300 AI30 TUSCAN GOLD Tuscan Gold 75299 AI30 TUSCAN BRNKL Tuscan Brushed Nickel 75301 AI30 TUSCAN BKNKL Tuscan Black Nickel Insets Required Includes...

Страница 34: ...VEC DU COMBUSTIBLE SOLIDE TEST SELON LA NORME ANSI Z21 88 2005 CSA 2 33 2005 FOYER RADIANT AU GAZ UL307B CSA P 4 1 02 ET CGA 2 17 M91 CET APPAREIL DOIT TRE INSTALL CONFORM MENT AUX EXIGENCES DES CODES...

Страница 35: ...ssistance ou information suppl mentaires contactez un installateur qualifi un agent de service ou un fournisseur de gaz Si vous op rez cet appareil sans qu il ne soit correctement raccord un conduit d...

Страница 36: ...erage Retain this manual File it with your other documents for future refer ence Product reference information We recommend that you record the following important information aboutyourappliance Pleas...

Отзывы: