NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

Flue Restrictors

The flue restrictor settings shown in 

Figures 19 and 20

 are for typical 

installations and may need to be adjusted from standard to take into 

account other variables in the installation to achieve proper combustion.  

See 

Flue Restrictor Guidelines

 on this page to assist you in making a 

proper flue restrictor adjustment. 

The Ravelle™ 30 gas fireplace uses balanced flue technology to ensure 

proper combustion. As such, flue restrictors may need to be installed 

depending on the vent configuration of your fireplace. The drawings on 

Page 17

 show all the allowable pipe configurations for the Ravelle 30 

gas fireplace. To properly install the flue restrictor, first find your pipe 

configuration  in  the  drawings  on 

Page  17

  and  note  which  restrictor 

setting is recommended. The flue restrictors and four black self-tapping 

5/32” allen head screws can be found in the firebox in a plastic bag. The 

restrictors should be placed over the openings at both sides of the ceil-

ing of the firebox. For each restrictor, two self-tapping 5/32” allen head 

screws should be installed in either holes 1, 2, 3, 4, or 5 in the restrictor 

and screwed into the two holes in the firebox ceiling. 

(Note: There are 

four holes at each side of the firebox ceiling to receive only two screws. 

Insert the screws into either two holes).

  See 

Figure 18

 for the location of 

hole numbers on the restrictor. The numbered holes in which the screws 

are inserted in the restrictor should correspond to the restrictor position 

numbers found on the drawings for your pipe configuration. Restrictor 

positions are based on tests run in a laboratory. The optimum restrictor 

positions may need to be adjusted slightly depending on the conditions 

surrounding  the  residential installation. Do  not  adjust  restrictors to  a 

point where the fireplace is sooting.

Notes: The higher the number of the flue restrictor position, the greater 

amount of combustion air will be delivered.

Flue Restrictor Adjustment Guidelines

After the flue restrictors have been set to the standard settings as shown 

in 

Figures 19 and 20

, the burner flame appearance should be evaluated 

to determined if the flue restrictors need to be set to a different position 

to adjust for variables in your installation. Light the appliance and allow 

it to burn for 20 minutes. See 

Flame Color and Behavior

 on 

Page 26 

to 

determine if you have a proper burner flame appearance. If the proper 

flame appearance cannot be achieved, the flue restrictor may need to be 

set to a different position. See the following guidelines to determine if 

you need to readjust the flue restrictors.

Before proceeding, confirm the manifold and inlet gas pressure is correct, 

primary air shutter is properly adjusted, venting system connections are 

secure and not blocked and if you are at a high elevation, ensure unit has 

been properly derated:

Restrictors 

Interior of Firebox  

Figure 18

Symptoms - Lack of Combustion Air

If the symptoms listed below are present, you may need to adjust the 

flue restrictor to a more open position.   

•  Flame appears yellow

•  Floating Flames (lazy, ill defined, quiet, may roll)

•  Sooting

•  Pilot becomes yellow and appliance shuts down

Symptoms - Excessive Combustion Air

If the symptoms listed below are present, you may need to adjust the 

flue restrictor to a more closed position

•  Low Flame

•  Pilot pulls and appliance shuts down

•  Pilot flame ghosts

Содержание RAVELLE 30

Страница 1: ...debiensuivrelesinstruc tionsdonn esdanscettenoticepourr duireauminimum le risque d incindie ou d explosion ou pour viter tout dommage mat riel toute blessure ou la mort These appliances may be install...

Страница 2: ...any make shift compromises during in stallation Any modification or alteration may result in damage to the appliance or dwelling and will void the warranty certification and listings of this unit Fail...

Страница 3: ...12 Vent Considerations 13 Horizontal Vent Installation 14 Vertical Vent Installation 14 Vertical Vent Termination Clearances 15 Flue Restrictors 16 Horizontal Terminations 17 Vertical Terminations 17...

Страница 4: ...rd for Mobile Home Installations ANSI A225 1 latest edition Must be vented directly to the outside in accordance with the latest edition of the National Fuel Gas Code and must never be attached to a c...

Страница 5: ...g the cassette valve and pilot assembly or installing a conversion kit Only Lennox Hearth Products conversion kits can be used to convert from NG to LP or LP to NG Contact your Lennox Hearth Products...

Страница 6: ...offs 0 0mm Rear corners to enclosure from standoffs 0 0mm Top to header from standoffs 0 0mm Bottom of unit to floor 0 0mm Edge of door glass to side wall and side trim 6 1 4 159mm Back to enclosure f...

Страница 7: ...ical power supply wiring should be routed to the right rear of the unit Note The fireplace may be placed directly on wood or non combustible flooring but not on vinyl floor covering or carpet Framing...

Страница 8: ...d if desired Should a hearth extension thicker than 7 8 22 mm be desired the height of the fireplace must be raised the thickness of that hearth extension less the 7 8 22 mm For example if a 2 7 8 73...

Страница 9: ...behind the fireplace see below Cement Board 3 8 Tile and 1 2 Cement Board Behind Fireplace Face Cement Board a minimum of five inches wide Sheetrock 1 Reveal 5 127mm Minimum Sheetrock Facing Installat...

Страница 10: ...d face installation The corners of the 1 25mm reveal around the fireplace opening need to be adjusted prior to installing an arched face see below Remove screws A and loosen screw B Rotate the corner...

Страница 11: ...efore installing the fire place face The acid wash will tarnish the face Consult your masonry installer Face Installation AnumberofdifferentfacesareavailablefortheRavelle 30gasfireplace however all th...

Страница 12: ...t approved or manufactured by the approved vent manufacturer Installation other than as instructed by Lennox Hearth Products and vent manufacturers instructions Vent Parts List DirectventpipeSecurity...

Страница 13: ...ed by examining the inside of the female ends Supports Horizontal runs of vent must be supported every three feet Wall straps are available for this purpose Pipe Sealing If Security Secure Vent pipe i...

Страница 14: ...6 mm rise for every one foot of run towards the termination 7 If the wall being penetrated is constructed of non combustible mate rial such as masonry block or concrete a 7 1 2 191 mm diameter hole is...

Страница 15: ...m is 10 feet 3M Vertical Vent Termination Clearances The vent air intake termination clearances above the high side of an angled roof is as shown in the Figure 17 Termination Heights For Vents Above F...

Страница 16: ...sitions are based on tests run in a laboratory The optimum restrictor positions may need to be adjusted slightly depending on the conditions surrounding the residential installation Do not adjust rest...

Страница 17: ...the top of the vertical length of pipe is allowed as long as the overall length of the horizontal run of pipe does not exceed those shown below Use the restrictor positions indicated Horizontal Termi...

Страница 18: ...ve meter regulator assembly 3 feet 91 cm within a height of 15 feet above the meter regulator assembly 3 feet 91 cm within a height of 15 feet above the meter regulator assembly I Clearance to service...

Страница 19: ...k panels which are shipped in the firebox 2 The long rectangular panel goes in the rear of the firebox he thin layer of bricks should be down The panel rests on 3 metal tabs protruding from the rear o...

Страница 20: ...and join this wire to the black supply wire reusing the wire nut Repeat for white wire Reinstall the electrical box cover If a wall mounted burner on off switch or thermostat is to be used the wires r...

Страница 21: ...insertasmallphillipsscrewdriver into the tap and turn a half turn counter clockwise Cover the tap with the line from a manometer and check the pressure Close the tap gently but securely after completi...

Страница 22: ...ing with or without the fireplace fan running air is drawn from a distant room lowering the pressure in that room through the return air duct into the bottom of the fireplace The air then passes throu...

Страница 23: ...appliance is equipped with a piezo ignition device to light the pilot When lighting the pilot follow these instructions exactly B BEFORE LIGHTING smell around the appliance area for gas Be sure to sme...

Страница 24: ...r switch and or thermostat if in stalled to its lowest setting 2 Turn off electric power to the appliance if service is to be performed 3 Push in gas control knob slightly and turn clockwise to OFF Do...

Страница 25: ...ellow Flame Blue Flame Center Ports on Burner Assembly Burner Flame Appearance Figure 34 Air Shutter Control Lever Gas Valve Air Shutter Adjustment The Ravelle 30 gas fireplace has an air shutter cont...

Страница 26: ...cur Do not mount the thermostat where it may be affected by Radiant heat from this appliance fireplaces sun or other heat sources Drafts or dead spots behind doors or in corners Hot or cold air from d...

Страница 27: ...the chance of the burner not igniting Follow the instructions included with the thermostat for wiring The ther mostatandrockerswitchwillturntheburneronandoffindependently Be suretosettherockerswitcht...

Страница 28: ...s when the unit is hot o Check the hot air outlet vents for lint or other accumulations Never block or restrict vent openings obstruct flow of ventilation air or use vents other than those approved fo...

Страница 29: ...and Log Set Installation 3 Remove the two allen head screws at the left and right rear of the firebox securing the air control panel Lift out the air control panel 4 Remove the one allen head screw h...

Страница 30: ...ht pilot If pilot lights turn off pilot and trigger the igniter again If pilot lights an intermittent gas air supply may be the problem if longer purge will not light check gap between electrode and p...

Страница 31: ...Main Burner Orifice 52 LP H5958 Pilot Orifice NG H3141 Pilot Orifice LP H5897 Main Gas Valve Supply Line H3117 Blower W Mounting Bracket H3857 Blower Snap Switch H5742 Blower Speed Control rheostat H...

Страница 32: ...S Glass Door Box 1 of 3 75092 PILCST PILRS2 Back Pillars Top Box 2 of 3 75094 PILCST GRL TRD3 Grill Bars Traditional Box 3 of 3 or 75091 PILCST GRL FIL3 Grill Filigree Ornate Box 3 of 3 Gas Conversion...

Страница 33: ...a Black Nickel 75298 AI30 TUSCAN BLK Tuscan Black 75300 AI30 TUSCAN GOLD Tuscan Gold 75299 AI30 TUSCAN BRNKL Tuscan Brushed Nickel 75301 AI30 TUSCAN BKNKL Tuscan Black Nickel Insets Required Includes...

Страница 34: ...VEC DU COMBUSTIBLE SOLIDE TEST SELON LA NORME ANSI Z21 88 2005 CSA 2 33 2005 FOYER RADIANT AU GAZ UL307B CSA P 4 1 02 ET CGA 2 17 M91 CET APPAREIL DOIT TRE INSTALL CONFORM MENT AUX EXIGENCES DES CODES...

Страница 35: ...ssistance ou information suppl mentaires contactez un installateur qualifi un agent de service ou un fournisseur de gaz Si vous op rez cet appareil sans qu il ne soit correctement raccord un conduit d...

Страница 36: ...erage Retain this manual File it with your other documents for future refer ence Product reference information We recommend that you record the following important information aboutyourappliance Pleas...

Отзывы: