background image

10

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE

Figure 5 - Types of Chimney

Types of Chimneys

The unit must be connected to either a code-approved masonry chimney 

with a flue liner, or a 6 inch diameter factory-built chimney complying with 

the requirements for Type HT chimneys in the standard UL 103.

The chimney is a vital part of your stove installation. A properly built 

masonry chimney or a properly installed factory-built chimney will assure 

a  consistent  draft  under  a  variety  of  weather  conditions  (a  smoking 

stove is usually caused by a chimney problem). The stove flue size is 

6 inches diameter, which is approximately 28 square inches minimum. 

The maximum flue size should be no more than three (3) times the cross 

sectional area of the size of the stove flue collar. In this case, that would 

be no larger than an 10-inch diameter stack, or approximately 85 square 

inches maximum.

All chimneys must be installed as specified by local building codes and 

according  to  the  chimney  manufacturer  instructions  (in  the  case  of 

a  factory-built  chimney).  See  the  chimney  manufacturer  instructions 

for exact specifications.  Factory-built chimneys must comply with UL 

103HT or ULC S629. A chimney connector shall not pass through an attic 

or roof space, closet or similar concealed space, or a floor, or ceiling.  

Where passage through a wall, or partition of combustible construction 

is desired, the installation shall conform to CAN/CSA-B365, Installation 

Code for Solid-Fuel-Burning Appliances and Equipment.

Factory 

Built

Chimney

Tile-lined Masonry Chimney

Minimum / Maximum Flue Diameter:

Minimum 6”, Maximum 10”

Chimney Connector Adapter 

Use a chimney connector adapter to connect the chimney connector up 

to the chimney.  The small ends of the chimney connector should all point 

down for a drip free installation.  Position all seams toward the back for 

aesthetics.  The chimney connector must be 6-inch diameter.

Secure adjoining sections of chimney connector to each other using three 

equally spaced sheet metal screws.  Secure the connector pipe to flue 

collar using three equally spaced sheet metal screws.  DO NOT secure 

chimney connector to chimney with screws.

Connection To A Factory-built Chimney

This space heater is to be connected to a factory-built chimney conforming 

to CAN / ULC – S629, Standard for 650°C Factory-Built Chimneys. All pipe 

connections must be sealed (ie. high temperature silicone).

For Reduced Residential Clearances Using Double Wall Pipe (Approved 

for Model CI2000HT Only):

Type L and listed double wall connector pipe is acceptable. Install any fac-

tory-built brand of pipe according to the manufacturer’s instructions.

Vapor Barrier at Chimney Penetration

Install all venting components per the Vent Manufacturers installation 

instructions. Ensure that there is an effective vapor barrier at the location 

where the chimney penetrates to the exterior of the structure. This can 

be accomplished by applying a non-hardening waterproof sealant to the 

following components:

•  Around the chimney at the point where the storm collar will meet the 

chimney just above the Flashing

•  Along the vertical seam of the chimney pipe, where it is exposed to 

the weather. 

•  On each nail head on the flashing. 

•  Around the chimney at the point where the storm collar will meet the 

chimney just above the flashing. 

Notes: 

•  On a flat or tarred and graveled roofs, nail and seal the flat roof flashing 

to the roof on all sides with roofing compound.

•  Do not put screws through the flashing into the chimney pipe.

Chimney Inspection

Existing chimneys must be inspected before installing your stove. Con-

sult your local building department for chimney code requirements. A 

masonry chimney must have a code approved liner. This liner must not 

have broken or missing pieces. Some non-code masonry chimneys may 

be brought up to code by being relined. (Consult your dealer or qualified 

chimney sweep).  Factory-built chimneys should also be inspected, first 

for creosote deposits (which should be removed), and then for integrity 

of the stainless steel liner. Look for obvious bulges in the lining, which 

may indicate the need to replace that section (use a bright flashlight).  

Also, inspect the attic to see that the chimney has proper clearance to 

combustible framing members. For interior masonry chimneys and most 

factory-built chimneys, this must be a two (2) inch air space clearance, 

which must not be filled with insulation or any other material. An exterior 

masonry chimney must have a  one (1) inch air space clearance.

Acceptable Connector Pipe For Installations

When Using Single Wall Pipe: Install a six (6) inch diameter, single wall, 

24 MSG black steel or 26 MSG blued steel connector pipe on the flue 

collar of the unit. When installing pipe, the crimped ends of the pipe 

should all point down.  Position all seams toward the back for aesthet-

ics. Three (3) pre-drilled holes are provided in the flue collar for fasten-

ing the pipe securely to the stove. Use sheet metal screws to do this. 

Additional sections of single wall pipe should be fastened together with 

at least three (3) sheet metal screws each section. All pipe connections 

must be sealed (ie. high temperature silicone). When connecting to the 

factory-built ceiling support package, use the manufacturer’s transition 

piece, usually called a dripless connector, to join single wall pipe to their 

factory-built chimney section.

When Using Approved Double Wall Pipe (Approved for Model CI2000HT 

Only)

Type L and listed double wall connector pipe is acceptable. Install any 

factory-built brand of pipe according to the manufacturer’s instructions. 

All pipe connections must be sealed (ie. high temperature silicone).

INSTALLATION

Содержание ELITE CI2000HT

Страница 1: ...lure to follow these instructions could result in property damage bodily injury or evendeath Contactyourlocalbuildingorfireofficialstoobtain apermitandinformationonanyinstallationrequirements and inspection requirements in your area INSTALLATION AND OPERATION MANUAL WARNINGS Hot Do not touch The glass and surfaces of this appliance will be hot during operation and will retain heat for a while afte...

Страница 2: ... is approved for burning dry seasoned natural wood only CAUTION BURN UNTREATEDWOODONLY DONOTBURNGARBAGEORFLAM MABLE FLUIDS SUCH AS GASOLINE NAPHTHA OR ENGINE OIL 10 Never use gasoline gasoline type lantern fuel kerosene charcoal lighter fluid or similar liquids to start or freshen up a fire in this heater Keep all such liquids well away from the heater while it is in use 11 DO NOT OVERFIRE If heat...

Страница 3: ... of your local code Check with your local building department for requirements in your area Installation Solid Fuel Standards National Fire Protection Association The primary NFPA standard that refers to installation and maintenance of wood fired appliances and venting is NFPA 211 Latest Edition Chimneys Fireplaces Vents and Solid Fuel appliances Note This appliance is NOT approved for installatio...

Страница 4: ...f you plan to vent your stove into an existing masonry chimney have it inspected by a local fire marshal or qualified installer Remember that a stove s performance is heavily influenced by the chimney and its location on the roof An oversized flue may not provide effective draw and a flue liner may be required see Draft Requirements on Page 11 Consult your dealer or qualified installer before fina...

Страница 5: ...isted material kL material TL TM inches kM x TL 84 TM inches 1 92 x 5 84 1 143 inches 2 286 x 5 Answer TheminimumrequiredthicknessoftheDurockis1 143 therefore round up to nearest standard thickness available which is 1 1 4 Minimum r value per Inch Specified min thickness of of listed material x thickness alternate r value per inch of listed material of alternate material material TM inches rL x TL...

Страница 6: ... kL material TL TM inches kM x TL 84 TM inches 1 92 x 1 45 84 1 143 inches 2 286 x 1 45 Answer TheminimumrequiredthicknessoftheDurockis3 31 therefore round up to nearest standard thickness available which is 3 5 16 Minimum r value per Inch Specified min thickness of of listed material x thickness alternate r value per inch of listed material of alternate material material TM inches rL x TL rM TM i...

Страница 7: ...the alternate material required using the formula s and shown in Table 3 Note Any noncombustible material having a minimum thickness of 1 2 13 mm whose k value is less than 84 or whose r value is more than 1 19 is acceptable If the alternate material used has a higher k value or lower r value will require a greater thickness of the material used In some cases if the k value is less or the r value ...

Страница 8: ...r your stove which were determined in a Laboratory test using various classes of stove pipe or chimney Mini mums are first established for the stove itself and increased based on how much heat is transferred by each class of pipe Position the unit no closer than the minimum clearances to combustible materials Check that no overhead cross members in the ceiling or roof will be cut Reposition unit i...

Страница 9: ...s Check that no overhead cross members in the ceiling or roof will be cut Reposition unit if necessary being careful not to move closer than the minimum clearances Single Wall Pipe CI2000HT Not approved for alcove installations Using single wall 24 MSG black or 25 MSG blued steel connector pipe with factory built chimney listed to either UL 103HT or ULC S629 Double Wall Pipe CI2000HT For alcove in...

Страница 10: ...on instructions Ensure that there is an effective vapor barrier at the location where the chimney penetrates to the exterior of the structure This can be accomplished by applying a non hardening waterproof sealant to the following components Around the chimney at the point where the storm collar will meet the chimney just above the Flashing Along the vertical seam of the chimney pipe where it is e...

Страница 11: ...ow burning appliance may increase This increased draft may cause dangerously high temperature to develop possibly causing failure of the unit or flue or ignition of nearby combustibles Closing down the combustion airflow Primary Air Draft Control may not guarantee that this will not happen CAUTION Manystructurefireshaveresultedwhenaslowburning fire has been left unattended for any extended period ...

Страница 12: ... The lack of air is caused by many common household appliances which exhaust air from the home such as a furnace heat pump air conditioner clothesdryer exhaustfans fireplaces andotherfuelburningappliances Also the combustion process of this heater uses oxygen from inside the dwelling If the available fresh air delivery in the dwelling is insufficient to support the demands of these appliances prob...

Страница 13: ... insulation from the outer surface of the wall thimble to wall combustibles Support the wall thimble and cover its opening with a 24 gageminimumsheetmetalsupport Maintainthe6 153mm space There should also be a support sized to fit and hold the metal chimney connector See that the supports are fastened securely to wall surfaces on all sides Make sure fasteners used to secure the metal chimney conne...

Страница 14: ...heet Steel Supports Chimney Connector Chimney Length 1 in 25 4 mm Air Space to Chimney Length Min Clearance 2 in 51 mm Figure 9 Combustible Wall Chimney Connector Pass Throughs Primary Air Draft Control Use the air control adjustment tool provided see FigrueX 10 to adjust the air controls per the following instructions Figure 10 Air Control Ash Pan Removal Tool The primary combustion air delivery ...

Страница 15: ...ee Start Up Air Control on this Page 2 Adjust the primary air draft control to the full open position see Primary Air Draft Control on Page 14 3 Open the side fuel loading door and build your fire directly on the grate in the firebox a Place five or six loosely crumpled sheets of newspaper in the stove b Add a small amount of dry kindling randomly on the top of the newspaper c Place a few more loo...

Страница 16: ...n operating the stove on low for extended periods of time the glass may get dirty A short hot fire 15 20 minutes will help clean off much of the normal buildup see Dirty Glass Page 21 A commercial glass cleaner designed for stoves is recommended for cleaning The glass should be cleaned thoroughly with glass cleaner and a soft cloth BEFORE the stove is burned Use Control Settings That Work For You ...

Страница 17: ...ING Read and use the information provided in this sec tion Todisregardthismaycauseseriouspermanent damage to the stove and void your warranty It is best to warm your stove up slowly and keep it at a moderate level Refueling CAUTION Always check for high flames when opening a door by partially opening door for a few seconds before opening fully To prevent smoke blowing into the room follow these re...

Страница 18: ...d to death Carbon monoxide poisoning early signs of carbon monoxide poisoning resemble the flu with head aches dizziness ornausea Ifyouhavethesesigns get fresh air at once Have the heater inspected by a qualified service technician Some people are more affected by carbon monoxide than others These include pregnant women people with heart orlungdiseaseoranemia thoseundertheinfluence of alcohol and ...

Страница 19: ...HER COM BUSTIBLE RECEPTACLE Proper Disposal of Ashes Ashes should be placed in a metal container with a tight fitting lid The closed container of ashes should be placed on a noncombustible floor or on the ground well away from all combustible materials pending final disposal Iftheashesaredisposedofbyburialinsoilorotherwiselocallydispersed they should be retained in the closed container until all c...

Страница 20: ...0HT has one vermiculite firebrick which serves as a baffle for the flue gasses The CI2000HT has a 5 sided box made of ceramic fiber brick that serves as a baffle In both cases the baffles are located just above the secondary air tubes which must be removed to access the baffle Suggestion Wear a pair of leather work gloves when removing secondary air tube assembly and baffle 1 Toaccessthebaffle the...

Страница 21: ...ntrol 3 Paint curing on first several burns Dirty Glass 1 Poor draft conditions 2 Long burn periods at low draft settings 3 Burning wet pitchy or spongy wood 4 Poorly arranged logs too close to glass Draft problems if installing into a larger flue it may be necessary to use a full length liner to achieve adequate draft for the appliance A draft gauge should read a minimum of 05 W C inches water co...

Страница 22: ...18 457 mm Firebox Size 1 12 cu feet Loading Front Side Width overall 23 3 4 604 mm Depth overall 15 5 16 389 mm Height to flue 30 762 mm Height to stove top 27 1 4 693 mm Back to centerline of flue 6 7 16 163 mm Approx weight with brick 280 lbs 140 kg Note Dimensions shown are approximate only 1 4 FRONT VIEW SIDE VIEW Shown with optional window trim 17 3 16 436 mm 6 7 16 163 mm 8 15 16 226 mm 15 5...

Страница 23: ...mm Firebox Size 1 97 cu feet Loading Front Side Width overall 29 1 8 740 mm Depth overall 18 3 4 476 mm Height to flue 32 13 16 833 mm Height to stove top 29 3 4 756 mm Back to centerline of flue 7 11 16 195 mm Approx weight with brick 410 lbs 205 kg Note Dimensions shown are approximate only 1 4 FRONT VIEW SIDE VIEW Shown with optional window trim 21 9 16 547 mm 7 11 16 195 mm 10 3 4 274 mm 18 3 ...

Страница 24: ...uded CI1000HT 4 40M4301 Door Ashpan Charcoal Handle Receiver Not Included CI2000HT 1 40M1701 Door Firebox Charcoal Handle Receiver Not Included CI1000HT 1 40M8201 Door Firebox Charcoal Handle Receiver Not Included CI2000HT 2 40M1201 Door Side Loading Charcoal Handle Receiver Not Included CI1000HT 2 40M7801 Door Side Loading Charcoal Handle Receiver Not Included CI2000HT 47 40M3501 Draft Module Air...

Страница 25: ...uts 2 Washers CI1000HT CI2000HT 28 41M0901 Leg Front Left Charcoal Includes Gasket Hardware CI1000HT CI2000HT 28 40M9501 Leg Front Right Charcoal Includes Gasket Hardware CI1000HT CI2000HT 28 41M3101 Leg Right Left Rear Charcoal Includes Gasket Hardware CI1000HT CI2000HT 29 40M2801 Log Guard With 2 Andirons CI1000HT 30 40M9701 Log Guard With 3 Andirons CI2000HT 40M68 Paint Touch Up Spray Charcoal ...

Страница 26: ... Series 5 Bottom Center Firebrick CI2000HT Series 6 Bottom Side Firebrick CI2000HT Series 7 Left Lower Firebrick CI2000HT Series 8 Upper Left Firebrick CI2000HT Series i9 Lower Rear Firebrick CI2000HT Series 4 6 117 mm 7 87 x 200 mm 9 25 235 mm 12 36 314 mm 9 25 235 mm 2 87 73 mm 7 87 200 mm 79 20 mm thick 7 87 200 mm 10 08 256mm 79 20 mm thick 10 43 265 mm 5 51 140 mm 79 20 mm thick 13 94 354 mm ...

Страница 27: ... Firebrick above tubes on ceiling CI1000HT Series 16 Upper Rear Firebrick CI1000HT Series 17 Fuel Grate Frame CI1000HT Series 18 Fuel Grate Frame CI2000HT Series 19 Air Column Gasket CI1000HT CI2000HT Series 19 Start up Air Column Gasket CI2000HT Series 10 43 265 mm 4 72 120 mm 79 20 mm thick 13 93 354 mm 7 87 200 mm 79 20 mm thick 8 47 215 mm x 12 305 mm 79 20mm thick 6 50 165mm x 12 40 315 mm 98...

Страница 28: ...HT Series 24 Ashpan Door Hinge Pin CI1000HT CI2000HT Series 25 Front Firebox Door Hinge Pin CI1000HT Series 26 Front Firebox Door Hinge Pin CI2000HT Series 27 Side Door Hinge Pin CI1000HT CI2000HT Series 28 Stove Leg CI1000HT CI2000HT Series 29 Log Guard C1000HT Series 30 Log Guard CI2000HT Series 31 Left Air Column Assembly CI1000HT Series 31 Right Air Column Assembly CI1000HT Series REPLACEMENT ...

Страница 29: ...eries 35 Ashlip CI1000HT CI2000HT Series 36 Ashpan CI1000HT CI2000HT Series 37 Baffle Assembly Ceramic Fiber Brick above secondary air tubes CI2000HT Series 38 Start up Air Channel Assembly CI2000HT Series 39 Flue Outlet Collar CI1000HT Series 40 Flue Outlet Collar CI2000HT Series 41 Fire Poker CI1000HT CI2000HT Series 42 Ashpan Side Door and Firebox Door Handle Receivers CI1000HT CI2000HT Series ...

Страница 30: ...Series 49 Rear Firebrick Retainers CI2000HT Series Side Retainers Not Shown CI1000HT Firebrick Placement Diagram 15 Baffle Firebrick 16 Upper Rear Firebrick 13 Lower Rear Firebrick 12 Left Side Firebrick 14 Right Side Firebrick Note CI1000HT does not have fire brick on fire box floor fuel grate frame on floor only CI2000HT Firebrick Placement Diagram 11 Upper Rear Firebrick 9 Lower Rear Firebrick ...

Страница 31: ...ILLUSTRATIONS ARE NOT TO SCALE OPTIONAL ACCESSORIES Models CI1000HT CI2000HT Catalog No Model Description Stove Model 41M2401 WTK CI10 Window Trim Kit Charcoal CI1000HT 41M2001 WTK CI20 Window Trim Kit Charcoal CI2000HT ...

Страница 32: ...esté à UL 1482 ULC S627 Floor protectormust be a 1 2 minimum thickness non combustiblematerial havinganequalorbetterinsulatingvalue lower k Value of k 84 BTU In F t2 Hr F It mustextendbeneathheater andtothe front sides rear as indicated In Canada requiredfloor protection must be a 1 45 minimumthickness extending18 450mm in front and 8 200mm on all other sides of the appliance Le protecteurde planc...

Страница 33: ...e Ne pas connecter cet appareil à un tuyau de cheminée servant un autre appareil NOTE Remplacez la vitre avec une céramique de 5mm seulement Opérez avec les porte fermée Serial No Numéro de Série Model Modèle CI 2000HT Tested To Testé à UL 1482 ULC S627 Floor protector must be a 1 2 minimumthickness non combustible material having an equal or better insulating value lower k Value of k 84 BTU In F ...

Страница 34: ...34 EPA LABELS CI1000HT and CI2000HT PAGE 38 EPA LABELS CI1000HT and CI2000HT ...

Страница 35: ...5 OWNERSHIP RECORDS Dealer s Name Dealer s Address City State Serial Number Date Installed Date of Purchase Notes SERVICE AND MAINTENANCE LOG Service Service Service Date Technician Description Zip Code ...

Страница 36: ...ce Product reference information We recommend that you record the following important information about your fireplace Please contact your Lennox Hearth Products dealer for any questions or concerns For the number of your nearest Lennox Hearth Products dealer please call 1 800 9 Lennox Replacement parts See Pages 24 to 30 for a complete replacement parts list Use only parts supplied from the manuf...

Отзывы: