TROUBLESHOOTING

*  When Fuel Door Is Opened, Smoke Enters Room

1. The primary air draft control is closed. 

2. The chimney is too cool. Set the primary air draft control on “HIGH” 

for a few minutes before opening either fuel loading door.

3. Excess creosote will not only restrict your draft but it will create a 

risk of a creosote fire. Strictly adhere to maintenance requirements as 

outlined in this manual. If excess creosote has built up on the inside 

of the firebox sides and door, burn a small hot fire at intervals that 

are more frequent with air control on HIGH for a few minutes.

4. Deposits may have built up in the chimney and are restricting the 

draft, or the spark arrester on top of the chimney may be plugged.

5. Chimney diameter too large or too small to provide adequate draft.

6. The house is too airtight (usually takes 20 to 30 minutes for problem 

to appear as stove lowers air pressure in house). Crack a window 

open or provide an outside source of air near stove.

7. Insufficient vertical height to chimney to achieve adequate draft.

Does Not Produce Enough Heat

1. Using green or insufficiently cured wood.

2. Excessive draft.

3. High ceilings (heat rises quickly, but can be recirculated by a well-

placed ceiling fan with a winter/summer switch).

4. The area to heat is too large (square foot heating estimates are based 

on “average” climates and home design).

5. There is an obstruction in the chimney.

6. The  chimney  or  chimney  cap  is  restricted  by  creosote  preventing 

enough draw to sustain a “high” heat output rate.

*  Does Not Maintain A Fire 

1. Soft wood does not burn as long or as well as seasoned hardwood 

resulting in a short burn time.

2. Wood size too small. Burns at too rapid a rate.

3. The gasket seal on the fuel loading doors, or glass is leaking air. Repair 

or replace it if necessary.

4. Excessive draft.

5. There may be an obstruction in the chimney.

*  Backpuffing 

Definition: This is a term describing the condition when combustible 

gases remain unlit because of insufficient combustion air delivery which 

results in combustible gases building, then flash igniting. If backpuffing 

is occurring, it can push some smoke into the room through the primary 

or secondary air openings. The combustion air delivery is dependent 

upon the draft of the venting system. The following are variables, which 

can negatively affect the draft resulting in backpuffing. 

1. Downdraft in the chimney (a special wind cap may be needed).

2. The house is too air tight (ventilation is needed).

3. Insufficient vertical height to chimney to achieve adequate draft.

Odors

1. Creosote accumulation in firebox (brush out on next cleaning).

2. Chimney downdraft when stove is not operating (close the primary 

air draft control).

3. Paint curing on first several burns.

*  Dirty Glass

1. Poor draft conditions.

2. Long burn periods at low draft settings.

3. Burning wet, pitchy or spongy wood.

4. Poorly arranged logs (too close to glass).

*  Draft problems; if installing into a larger flue, it may be necessary 

to use a full-length liner to achieve adequate draft for the appliance. 

A  draft  gauge  should  read  a  minimum  of  .05”  W.C.  (inches  water 

column) not to exceed .06” W.C. for optimum performance (See Draft 

Requirements on Page 11).

OVERFIRING DAMAGE

If the heater or chimney connector glows, you are overfiring. Other symp-

toms may include: Cracking, warping or burning out of components, stove 

glass may develop a haze, which will not come off with cleaning.

Overfiring of a stove is a condition where excessive temperatures are 

reached, beyond the design capabilities of the appliance. The damage 

that  occurs  from  overfiring  is  not  covered  under  the  manufacturers 

limited warranty.

The following are a few conditions that should be evaluated and (corrected 

if necessary) if an overfiring condition is suspected:

Overfiring Caused From Improper Installation

Ensure that all installation requirements have been met as outlined in the 

installation manual. The chimney should be clean and in good repair. A 

draft test should be performed to determine if the draft requirements of 

the appliance are being met. A draft gauge should read between .05 and 

.06 “ W.C. (inches water column). Excessive draft (above .06 “ W.C.) will 

allow too much combustion air to be pulled in which results in hotter 

burns. Too little draft (below .05 “ W.C.) will not allow enough combus-

tion air delivery to maintain a fire (this may result in improper operation 

of appliance, i.e. wont maintain fire unless fuel loading door is left open. 

See following, 

Overfiring Caused From Improper Operation).

Overfiring Caused From Improper Operation

Operate this appliance only as outlined in this manual. Never burn the 

appliance with either fuel loading door open or ajar. Do not operate this 

stove with the 

Primary Air Draft Control 

in the full “open” position for 

extended periods. This wastes fuel and can cause dangerous overfiring 

conditions. NEVER leave the stove unattended on high settings.

Overfiring Caused From Improper Maintenance

Strictly adhere to all maintenance requirements at frequent intervals as 

prescribed in this manual including cleaning of flue and stove. Should 

either fuel loading door or glass gaskets become worn or damaged, they 

should be replaced.

Overfiring Caused From Improper Fuel

This appliance is approved for use with natural dry well-seasoned wood 

only (ask your authorized dealer what are approved fuels for your area). 

Do  not  burn  garbage,  particleboard  scraps,  or  pressed  logs  because 

they can produce conditions that will deteriorate metal. Do not overload 

or use kindling wood or mill ends as primary fuel as this may cause 

overfiring.

Содержание ELITE CI2000HT

Страница 1: ...lure to follow these instructions could result in property damage bodily injury or evendeath Contactyourlocalbuildingorfireofficialstoobtain apermitandinformationonanyinstallationrequirements and inspection requirements in your area INSTALLATION AND OPERATION MANUAL WARNINGS Hot Do not touch The glass and surfaces of this appliance will be hot during operation and will retain heat for a while afte...

Страница 2: ... is approved for burning dry seasoned natural wood only CAUTION BURN UNTREATEDWOODONLY DONOTBURNGARBAGEORFLAM MABLE FLUIDS SUCH AS GASOLINE NAPHTHA OR ENGINE OIL 10 Never use gasoline gasoline type lantern fuel kerosene charcoal lighter fluid or similar liquids to start or freshen up a fire in this heater Keep all such liquids well away from the heater while it is in use 11 DO NOT OVERFIRE If heat...

Страница 3: ... of your local code Check with your local building department for requirements in your area Installation Solid Fuel Standards National Fire Protection Association The primary NFPA standard that refers to installation and maintenance of wood fired appliances and venting is NFPA 211 Latest Edition Chimneys Fireplaces Vents and Solid Fuel appliances Note This appliance is NOT approved for installatio...

Страница 4: ...f you plan to vent your stove into an existing masonry chimney have it inspected by a local fire marshal or qualified installer Remember that a stove s performance is heavily influenced by the chimney and its location on the roof An oversized flue may not provide effective draw and a flue liner may be required see Draft Requirements on Page 11 Consult your dealer or qualified installer before fina...

Страница 5: ...isted material kL material TL TM inches kM x TL 84 TM inches 1 92 x 5 84 1 143 inches 2 286 x 5 Answer TheminimumrequiredthicknessoftheDurockis1 143 therefore round up to nearest standard thickness available which is 1 1 4 Minimum r value per Inch Specified min thickness of of listed material x thickness alternate r value per inch of listed material of alternate material material TM inches rL x TL...

Страница 6: ... kL material TL TM inches kM x TL 84 TM inches 1 92 x 1 45 84 1 143 inches 2 286 x 1 45 Answer TheminimumrequiredthicknessoftheDurockis3 31 therefore round up to nearest standard thickness available which is 3 5 16 Minimum r value per Inch Specified min thickness of of listed material x thickness alternate r value per inch of listed material of alternate material material TM inches rL x TL rM TM i...

Страница 7: ...the alternate material required using the formula s and shown in Table 3 Note Any noncombustible material having a minimum thickness of 1 2 13 mm whose k value is less than 84 or whose r value is more than 1 19 is acceptable If the alternate material used has a higher k value or lower r value will require a greater thickness of the material used In some cases if the k value is less or the r value ...

Страница 8: ...r your stove which were determined in a Laboratory test using various classes of stove pipe or chimney Mini mums are first established for the stove itself and increased based on how much heat is transferred by each class of pipe Position the unit no closer than the minimum clearances to combustible materials Check that no overhead cross members in the ceiling or roof will be cut Reposition unit i...

Страница 9: ...s Check that no overhead cross members in the ceiling or roof will be cut Reposition unit if necessary being careful not to move closer than the minimum clearances Single Wall Pipe CI2000HT Not approved for alcove installations Using single wall 24 MSG black or 25 MSG blued steel connector pipe with factory built chimney listed to either UL 103HT or ULC S629 Double Wall Pipe CI2000HT For alcove in...

Страница 10: ...on instructions Ensure that there is an effective vapor barrier at the location where the chimney penetrates to the exterior of the structure This can be accomplished by applying a non hardening waterproof sealant to the following components Around the chimney at the point where the storm collar will meet the chimney just above the Flashing Along the vertical seam of the chimney pipe where it is e...

Страница 11: ...ow burning appliance may increase This increased draft may cause dangerously high temperature to develop possibly causing failure of the unit or flue or ignition of nearby combustibles Closing down the combustion airflow Primary Air Draft Control may not guarantee that this will not happen CAUTION Manystructurefireshaveresultedwhenaslowburning fire has been left unattended for any extended period ...

Страница 12: ... The lack of air is caused by many common household appliances which exhaust air from the home such as a furnace heat pump air conditioner clothesdryer exhaustfans fireplaces andotherfuelburningappliances Also the combustion process of this heater uses oxygen from inside the dwelling If the available fresh air delivery in the dwelling is insufficient to support the demands of these appliances prob...

Страница 13: ... insulation from the outer surface of the wall thimble to wall combustibles Support the wall thimble and cover its opening with a 24 gageminimumsheetmetalsupport Maintainthe6 153mm space There should also be a support sized to fit and hold the metal chimney connector See that the supports are fastened securely to wall surfaces on all sides Make sure fasteners used to secure the metal chimney conne...

Страница 14: ...heet Steel Supports Chimney Connector Chimney Length 1 in 25 4 mm Air Space to Chimney Length Min Clearance 2 in 51 mm Figure 9 Combustible Wall Chimney Connector Pass Throughs Primary Air Draft Control Use the air control adjustment tool provided see FigrueX 10 to adjust the air controls per the following instructions Figure 10 Air Control Ash Pan Removal Tool The primary combustion air delivery ...

Страница 15: ...ee Start Up Air Control on this Page 2 Adjust the primary air draft control to the full open position see Primary Air Draft Control on Page 14 3 Open the side fuel loading door and build your fire directly on the grate in the firebox a Place five or six loosely crumpled sheets of newspaper in the stove b Add a small amount of dry kindling randomly on the top of the newspaper c Place a few more loo...

Страница 16: ...n operating the stove on low for extended periods of time the glass may get dirty A short hot fire 15 20 minutes will help clean off much of the normal buildup see Dirty Glass Page 21 A commercial glass cleaner designed for stoves is recommended for cleaning The glass should be cleaned thoroughly with glass cleaner and a soft cloth BEFORE the stove is burned Use Control Settings That Work For You ...

Страница 17: ...ING Read and use the information provided in this sec tion Todisregardthismaycauseseriouspermanent damage to the stove and void your warranty It is best to warm your stove up slowly and keep it at a moderate level Refueling CAUTION Always check for high flames when opening a door by partially opening door for a few seconds before opening fully To prevent smoke blowing into the room follow these re...

Страница 18: ...d to death Carbon monoxide poisoning early signs of carbon monoxide poisoning resemble the flu with head aches dizziness ornausea Ifyouhavethesesigns get fresh air at once Have the heater inspected by a qualified service technician Some people are more affected by carbon monoxide than others These include pregnant women people with heart orlungdiseaseoranemia thoseundertheinfluence of alcohol and ...

Страница 19: ...HER COM BUSTIBLE RECEPTACLE Proper Disposal of Ashes Ashes should be placed in a metal container with a tight fitting lid The closed container of ashes should be placed on a noncombustible floor or on the ground well away from all combustible materials pending final disposal Iftheashesaredisposedofbyburialinsoilorotherwiselocallydispersed they should be retained in the closed container until all c...

Страница 20: ...0HT has one vermiculite firebrick which serves as a baffle for the flue gasses The CI2000HT has a 5 sided box made of ceramic fiber brick that serves as a baffle In both cases the baffles are located just above the secondary air tubes which must be removed to access the baffle Suggestion Wear a pair of leather work gloves when removing secondary air tube assembly and baffle 1 Toaccessthebaffle the...

Страница 21: ...ntrol 3 Paint curing on first several burns Dirty Glass 1 Poor draft conditions 2 Long burn periods at low draft settings 3 Burning wet pitchy or spongy wood 4 Poorly arranged logs too close to glass Draft problems if installing into a larger flue it may be necessary to use a full length liner to achieve adequate draft for the appliance A draft gauge should read a minimum of 05 W C inches water co...

Страница 22: ...18 457 mm Firebox Size 1 12 cu feet Loading Front Side Width overall 23 3 4 604 mm Depth overall 15 5 16 389 mm Height to flue 30 762 mm Height to stove top 27 1 4 693 mm Back to centerline of flue 6 7 16 163 mm Approx weight with brick 280 lbs 140 kg Note Dimensions shown are approximate only 1 4 FRONT VIEW SIDE VIEW Shown with optional window trim 17 3 16 436 mm 6 7 16 163 mm 8 15 16 226 mm 15 5...

Страница 23: ...mm Firebox Size 1 97 cu feet Loading Front Side Width overall 29 1 8 740 mm Depth overall 18 3 4 476 mm Height to flue 32 13 16 833 mm Height to stove top 29 3 4 756 mm Back to centerline of flue 7 11 16 195 mm Approx weight with brick 410 lbs 205 kg Note Dimensions shown are approximate only 1 4 FRONT VIEW SIDE VIEW Shown with optional window trim 21 9 16 547 mm 7 11 16 195 mm 10 3 4 274 mm 18 3 ...

Страница 24: ...uded CI1000HT 4 40M4301 Door Ashpan Charcoal Handle Receiver Not Included CI2000HT 1 40M1701 Door Firebox Charcoal Handle Receiver Not Included CI1000HT 1 40M8201 Door Firebox Charcoal Handle Receiver Not Included CI2000HT 2 40M1201 Door Side Loading Charcoal Handle Receiver Not Included CI1000HT 2 40M7801 Door Side Loading Charcoal Handle Receiver Not Included CI2000HT 47 40M3501 Draft Module Air...

Страница 25: ...uts 2 Washers CI1000HT CI2000HT 28 41M0901 Leg Front Left Charcoal Includes Gasket Hardware CI1000HT CI2000HT 28 40M9501 Leg Front Right Charcoal Includes Gasket Hardware CI1000HT CI2000HT 28 41M3101 Leg Right Left Rear Charcoal Includes Gasket Hardware CI1000HT CI2000HT 29 40M2801 Log Guard With 2 Andirons CI1000HT 30 40M9701 Log Guard With 3 Andirons CI2000HT 40M68 Paint Touch Up Spray Charcoal ...

Страница 26: ... Series 5 Bottom Center Firebrick CI2000HT Series 6 Bottom Side Firebrick CI2000HT Series 7 Left Lower Firebrick CI2000HT Series 8 Upper Left Firebrick CI2000HT Series i9 Lower Rear Firebrick CI2000HT Series 4 6 117 mm 7 87 x 200 mm 9 25 235 mm 12 36 314 mm 9 25 235 mm 2 87 73 mm 7 87 200 mm 79 20 mm thick 7 87 200 mm 10 08 256mm 79 20 mm thick 10 43 265 mm 5 51 140 mm 79 20 mm thick 13 94 354 mm ...

Страница 27: ... Firebrick above tubes on ceiling CI1000HT Series 16 Upper Rear Firebrick CI1000HT Series 17 Fuel Grate Frame CI1000HT Series 18 Fuel Grate Frame CI2000HT Series 19 Air Column Gasket CI1000HT CI2000HT Series 19 Start up Air Column Gasket CI2000HT Series 10 43 265 mm 4 72 120 mm 79 20 mm thick 13 93 354 mm 7 87 200 mm 79 20 mm thick 8 47 215 mm x 12 305 mm 79 20mm thick 6 50 165mm x 12 40 315 mm 98...

Страница 28: ...HT Series 24 Ashpan Door Hinge Pin CI1000HT CI2000HT Series 25 Front Firebox Door Hinge Pin CI1000HT Series 26 Front Firebox Door Hinge Pin CI2000HT Series 27 Side Door Hinge Pin CI1000HT CI2000HT Series 28 Stove Leg CI1000HT CI2000HT Series 29 Log Guard C1000HT Series 30 Log Guard CI2000HT Series 31 Left Air Column Assembly CI1000HT Series 31 Right Air Column Assembly CI1000HT Series REPLACEMENT ...

Страница 29: ...eries 35 Ashlip CI1000HT CI2000HT Series 36 Ashpan CI1000HT CI2000HT Series 37 Baffle Assembly Ceramic Fiber Brick above secondary air tubes CI2000HT Series 38 Start up Air Channel Assembly CI2000HT Series 39 Flue Outlet Collar CI1000HT Series 40 Flue Outlet Collar CI2000HT Series 41 Fire Poker CI1000HT CI2000HT Series 42 Ashpan Side Door and Firebox Door Handle Receivers CI1000HT CI2000HT Series ...

Страница 30: ...Series 49 Rear Firebrick Retainers CI2000HT Series Side Retainers Not Shown CI1000HT Firebrick Placement Diagram 15 Baffle Firebrick 16 Upper Rear Firebrick 13 Lower Rear Firebrick 12 Left Side Firebrick 14 Right Side Firebrick Note CI1000HT does not have fire brick on fire box floor fuel grate frame on floor only CI2000HT Firebrick Placement Diagram 11 Upper Rear Firebrick 9 Lower Rear Firebrick ...

Страница 31: ...ILLUSTRATIONS ARE NOT TO SCALE OPTIONAL ACCESSORIES Models CI1000HT CI2000HT Catalog No Model Description Stove Model 41M2401 WTK CI10 Window Trim Kit Charcoal CI1000HT 41M2001 WTK CI20 Window Trim Kit Charcoal CI2000HT ...

Страница 32: ...esté à UL 1482 ULC S627 Floor protectormust be a 1 2 minimum thickness non combustiblematerial havinganequalorbetterinsulatingvalue lower k Value of k 84 BTU In F t2 Hr F It mustextendbeneathheater andtothe front sides rear as indicated In Canada requiredfloor protection must be a 1 45 minimumthickness extending18 450mm in front and 8 200mm on all other sides of the appliance Le protecteurde planc...

Страница 33: ...e Ne pas connecter cet appareil à un tuyau de cheminée servant un autre appareil NOTE Remplacez la vitre avec une céramique de 5mm seulement Opérez avec les porte fermée Serial No Numéro de Série Model Modèle CI 2000HT Tested To Testé à UL 1482 ULC S627 Floor protector must be a 1 2 minimumthickness non combustible material having an equal or better insulating value lower k Value of k 84 BTU In F ...

Страница 34: ...34 EPA LABELS CI1000HT and CI2000HT PAGE 38 EPA LABELS CI1000HT and CI2000HT ...

Страница 35: ...5 OWNERSHIP RECORDS Dealer s Name Dealer s Address City State Serial Number Date Installed Date of Purchase Notes SERVICE AND MAINTENANCE LOG Service Service Service Date Technician Description Zip Code ...

Страница 36: ...ce Product reference information We recommend that you record the following important information about your fireplace Please contact your Lennox Hearth Products dealer for any questions or concerns For the number of your nearest Lennox Hearth Products dealer please call 1 800 9 Lennox Replacement parts See Pages 24 to 30 for a complete replacement parts list Use only parts supplied from the manuf...

Отзывы: