11
IMPORTANT
The protective devices have been fitted by the manufacturer for user safety during work.
CAUTION
Failure to follow the instructions below may cause injury or severe accidents.
It is absolutely forbidden to weld, braze, cut, grind, or search for a possible leak with an open flame
on a circuit containing A3 refrigerant fluid. Any intervention of this type must become the subject of a
risk analysis.
The equipment (detectors, vacuum pump, etc.) must be compatible with flammable fluids.
Before powering up and operating the unit, always perform refrigerant detection using a suitable
calibrated detector to make sure there is no gas around the unit.
If refrigerant gas leaks out, avoid entering the room, ventilate it as soon as possible and as much as
possible, and prohibit any source of active ignition.
During maintenance, we recommend that operators be equipped with suitable Personal Protective
Equipment (helmet, gloves, goggles, etc.), cut off the power supply and not approach with a potential
source of ignition without first checking that there is no potentially flammable area due to an
undetected leak. With suitable electrical and non-electrical equipment located in ATEX, he will be
able to ventilate the cold chamber to ensure that his intervention is safe.
2.7.
PROTECTIVE DEVICES AND SAFETY MEASURES
The manufacturer has provided the following safety protections:
1.
The metal casing is bolted to the structure.
2.
The fans are bolted to the metal structure.
3.
The fan access is covered by a grille bolted in place.
4.
The motor compressors have thermal protection.
5.
The units have a high pressure switch with manual reset for protection against high pressures.
2.8.
DISPOSING OF PACKAGING
Wooden, cardboard, plastic and polystyrene packaging must be disposed of in accordance with the laws
applicable in the country in which the unit is used.
2.9.
CONTROLS, ADJUSTMENTS AND CHECKS TO BE MADE
Before starting up the unit, check that:
-
the fixing bolts are properly tightened,
-
the electrical connections have been properly made.
-
the electrical connections are properly tightened
In case of opening the unit, check that:
-
no tools have been left inside the unit
-
the assembly has been made correctly,
-
there are no gas leaks,
-
the front cover has been correctly fitted.