22
CAUTION
To prevent risk of cuts to hands, use protective gloves.
CAUTION
RISK OF ELECTRIC SHOCK
Switch off the electrical current (power), before servicing the unit.
CAUTION
Do not use solvents
4.2.
ORDINARY MAINTENANCE
To always obtain a good functioning of the equipment, it is necessary to periodically:
-Verify weekly that the evaporator is clean, without accumulation of ice.
-Monthly (at least) perform a cleaning of the condenser (the periodicity of this cleaning depends mainly on
the environment where said unit has been installed). This operation must be carried out with the equipment
stopped: it is advisable to use a jet of air from the outside to the inside. When this is not possible, use a long
bristle brush from the outside of the condenser.
4.3.
PERIODICAL AND PREVENTIVE MAINTENANCE
Check every four months:
-
The state of wear of the electrical contacts and the contactors, cleaning them and, if necessary, replacing
them.
-That the wiring and all terminals are properly tightened.
-Visually check the entire refrigeration circuit (components, materials, containers, and pipes) to detect
possible external corrosion, oil residues or possible losses. Check the oil level.
-Make control of refrigerant gas leaks.
-Check the operation of all the measuring, control and safety devices, as well as the protection and alarm
systems to verify that their operation is correct and that they are in perfect condition.
Every five years check the entire refrigeration system (including safety valves and inspection of pressure
equipment). Control the energetic performances of the installation.
4.4.
SERVICING TO BE CARRIED OUT BY QUALIFIED STAFF
There follows a list of maintenance operations requiring specific technical skills and which must therefore be
carried out by authorised, qualified staff.
The user must NOT carry out the following operations under any circumstances:
-
replacement of electrical components
-
manipulation of the electrical system
-
repairs to mechanical parts
-
manipulation of the refrigeration system
-
manipulation of the control panel or the On, Stop or Emergency switches
-
manipulation of the protective and safety device systems
-
cleaning the condenser