The temperature setting can be viewed by pressing the button and changed by pressing the
and
buttons.
To protect the compressor from successive start-up and stopping, the adjustment system includes an anti-
short cycle timer.
The unit automatically goes into defrost mode after a cooling cycle functioning time of 4 hours. The unit is
supplied with the defrost mode controlled by the internal battery temperature. In this mode, the defrosting
process ends when the internal battery reaches a temperature of 10ºC, or after 25 minutes have elapsed.
After defrosting, the unit remains off for the drip time of 3 min so that all the defrost water can run off.
With the configuration the unit is supplied with, the fans remain off during defrosting.
3.4.
COLD ROOM LIGHT
The cold room light is switched off and on directly from the unit control using the
button, providing the
porthole is connected to the cold room light cable. With the optional Winter Kit, the operating of the camera
light on the control board is cancelled.
3.5.
CONTROL DEVICE
This consists of a 3-digit digital display, a keypad with 6 buttons and lights showing the operating modes,
failures and alarms.
1-
Fan warning light
2-
Warning light, defrost
3-
Warning light, cooling mode
4- Alarm warning light
5- Key maximum temperature
6- Minimum temperature key.
7- Compressor warning Light
8- Digital display
9-
Defrost button
10-
Camera light button
11- On / Off button
12- Key. Set point and parameter validation
For viewing and changing the temperature setting. In programming mode, it enables a parameter
to be selected and a value to be confirmed. If it is pressed and held down for 3 seconds, when the
max. and min. temperatures set are shown they will be erased.
For viewing the maximum temperature set. In programming mode it enables the parameter list to
be browsed or the value displayed to be increased.
For viewing the minimum temperature set. In programming mode it enables the parameter list to
be browsed or the value displayed to be reduced.
If this button is pressed and held down for 3 seconds, the defrost cycle begins.
For switching the cold room light on or off.
For switching the unit on or off.