Page 92/95
21January2021/Version 0
LEM International SA
Chemin des Aulx 8
1228 PLAN-LES-OUATES Switzerland
www.lem.com
FF# 32
- Error flag #5 - muFwIntegrityIsFailed
Value
Description
Solution
False
Nominal
N/A
True
CRC error on the
Meter Unit firmware
memory
1. Try to reboot the DCBM to force a new check right away or wait for next check cycle (30
minutes)
2. If not sufficient, then the memory is corrupted
FF# 64
- Error flag #6 - suIntegrityIsFailed
Value
Description
Solution
False
Nominal
N/A
True
CRC error on the date
or firmware memory of
the Sensor Unit
1. Try to reboot the DCBM to force a new check right away or wait for next check cycle (30
minutes)
2. If not sufficient, then the memory is corrupted
FF# 256
- Error flag #8 - logbookIntegrityIsFailed
Value
Description
Solution
False
Nominal
N/A
True
CRC error on logbook
memory
1. Try to reboot the DCBM to force a new check right away or wait for next check cycle (30
minutes)
2. If not sufficient, reboot a few more times
3. If not sufficient, then the memory is corrupted
FF# 512
- Error flag #9 - logbookIsFull
Value
Description
Solution
False
Nominal
N/A
True
Logbook is full
1. Once the logbook is full (approximately 40 000 events logged), no fix is possible (refer to
FF# 1024
- Error flag #10 - memoryAccessIsFailed
Value
Description
Solution
False
Nominal
N/A
True
Rejected access to
memory
1. Check for tampering marks, the DCBM code memory might have been altered
2. Reboot the product, the issue could come from a unknown software issue
FF# 8192
- Error flag #13 - muStateIsFailed
Value
Description
Solution
False
Nominal
N/A
True
Unexpected error in
the Meter Unit
1. Try to reboot the DCBM to force a new check right away or wait for next check cycle (30
minutes)
2. If not sufficient, reboot again a few more times or wait for a couple of hours