5.5. Performances
5.5.1. General
Parameter
Symbol
Unit
Min
Typ
Max
Comment
Supply voltage
V DC
+12
+48
±5 % tolerance
Supply current
mA
400
At +12 V DC
Supply bridging time
s
0.5
At +24 V DC
Voltage restoration (power up)
s
5
At +24 V DC
Rated conventional thermal current
A
400
600
DCBM-SU40xx
DCBM-SU60xx
Rated operational voltage
V
1000
Insertion loss in current path
W
10
Rated operational voltage
V
1000
Insertion loss in current path
W
10
Rated short time withstand current
I
CW
kA
12
18
DCBM-SU40xx
DCBM-SU60xx
30 ms