background image

5

•  When the load is turned 

OFF

 manually, as long as the sensor continues to detect occupancy the load stays 

OFF

. For the 

selected time delay, the lights stay off and the sensor reverts to the automatic-on mode.

•  When the load is turned 

OFF

 manually, pressing the switch again turns the load 

ON

 and the sensor reverts to the automatic-on mode.

•  Once the sensor returns to automatic-on mode, either the switch or occupancy detection can turn the load 

ON

.

OVERLOAD PROTECTION

The occupancy sensor has a built in overload protection function that will automatically turn off the control output when the load current 

exceeds 200mA. The sensor LED will then blink rapidly (~ 10Hz) to provide a visual indication of an overload condition. When the load 

current is corrected or returns to normal, the control output will turn back on.

TROUBLESHOOTING

Lights do not turn ON with occupancy, and the following condition exists:

Red LED does not flash:

1.  Check that the circuit breaker has been turned back on.

2.  Check all sensor and power pack wire connections.

3.  Check for 24V input to the sensor.

•  If 24V is present, replace the sensor.

•  If 24V is not present, check that high voltage is present to power pack. 

If it is, replace power pack.

4.  Make sure that PIR Sensitivity is set to minimum (DIP switch #5 set to on).

5.  If it still does not flash, call 800.879.8585 for Technical Support.

LED flashes:

1.  Check all sensor and power pack wire connections.

2.  Check for 24VDC at the power pack’s blue wire connection to sensor while sensor is activated. If there is no voltage, replace the 

sensor. If there is voltage, replace the power pack.

3.  If LED is flashing rapidly (~10Hz), an overload condition exists. When this is corrected, the sensor will return to normal operation. 

Check the blue wire connection. If necessary, replace the power pack.

Line voltage switch connected as shown in wiring example:

1.  Make sure switch is set to ON position.

Lights do not turn OFF automatically:

1.  The sensor technology (PIR) may be experiencing activations from outside the controlled area or from some type of interference 

(see “Unwanted Sensor Activations” below).

2.  Check all sensor and power pack wire connections.

3.  Disconnect power pack’s blue wire: 

If the lights do not turn off, replace power pack. Reconnect blue wire. 

If the lights turn off, the problem may be in the sensor. 

To check:

•  Reconnect the blue wire.

•  Turn sensitivity and time delay to minimum and allow the sensor to time out.

•  If the lights turn off, the sensor is working properly (see number 1, above, and “Sensor Adjustment” for readjustment of sensor).

Unwanted Sensor Activations (LED flashes):

Improper sensor location or inadequate masking causing detection outside of desired coverage area.

1.  The PIR sensitivity may be set too high.

2.  Sensor located too close to HVAC or VAV vents with heavy air flow.

3.  Check if Light Level is enabled.

•  If occupancy indicator LED blinks every few seconds, sensor is using Light Level feature.

•  If Light Level functionality is not desired, press and hold for 5 seconds to return sensor to the default setting (maximum).

Possible solutions: 

•  Mask the lens to reduce PIR coverage (see 

Masking the PIR Lens

, under 

Placement Guidelines

).

•  Change the logic configuration setting, see 

DIP Switches

.

•  Relocate the sensor.

ORDERING INFORMATION

Catalog Number

Description

CI-300

PIR Occupancy Sensor, low voltage, 360° lens, up to 1200 square ft., isolated relay & light level sensor.

CI-300-1

PIR Occupancy Sensor, low voltage, 360° high density/reduced range lens, up to 500 square ft., isolated relay 

& light level sensor.

BZ-50/BZ-150

Power Pack: 120/277VAC, 50/60Hz, 20A ballast or incandescent (BZ-150 with Hold-On and Hold-Off capability)

BZ-200/BZ-250

Power Pack: 120/277VAC, 50/60 Hz, 20A Ballast/ELV/MLV/Incandescent/LED, 16A, E-Ballast/CFL/Plug Load, 

(BZ-250 with Hold-On and Hold-Off capability)

BZ-250-347

Power Pack: 120/347VAC, 50/60 Hz, 16A Ballast/ELV/MLV/Incandescent/LED/ E-Ballast/CFL, 15A Plug Load, 

with Hold-On/Hold-Off capability

All sensors are white. BZ series power packs supply power for up to 8 CI-300 sensors.

Содержание Wattstopper CI-300

Страница 1: ...temperatures may cause false activations Mount the sensor to the ceiling The CI 300 sensors are designed for a ceiling height of about 8 10 feet Mounting above or below this range will significantly affect the coverage patterns Be aware that as you decrease the mounting height you decrease the range and increase the sensitivity to smaller motions Conversely when you increase the height you increas...

Страница 2: ...er Class 2 Power Packs For Indoor Use Only LISTED www legrand us wattstopper Relay Com N O N C Control Out Man Switch 24V Common v5 Wiring terminals Load 1 Load 2 Optional CI 300 Rear Housing Depluggable Terminal Front Cover Ceiling Spring Clips 2 Blue Control Out 24V Common Low Voltage Class 2 Line Voltage Line Neutral Feed Through Power Pack Black Red 1 2 Line Voltage Switches Standard wiring wi...

Страница 3: ...is optional The sensors are factory preset to allow for quick installation in most applications Verification of proper wiring or coverage or customizing the sensor s settings can be done using the following procedures To make adjustments open the Front Cover by pulling on the cover tab There is a 30 second warm up period when power is first applied Before making adjustments make sure the office fu...

Страница 4: ...hanged DIP SWITCH SETTING The CI 300 has 7 DIP switches under the cover Time Delay Switches 1 2 3 The sensor will hold the lights ON as long as occupancy is detected The time delay countdown starts when no motion is detected After no motion is detected for the length of the time delay the sensor will turn the lights OFF Walk Through Switch 4 Walk through mode turns the lights OFF three minutes aft...

Страница 5: ...o not turn OFF automatically 1 The sensor technology PIR may be experiencing activations from outside the controlled area or from some type of interference see Unwanted Sensor Activations below 2 Check all sensor and power pack wire connections 3 Disconnect power pack s blue wire If the lights do not turn off replace power pack Reconnect blue wire If the lights turn off the problem may be in the s...

Страница 6: ...nts À l inverse lorsque vous augmentez la hauteur vous augmentez la portée et diminuez la sensibilité aux petits mouvements À des hauteurs supérieures à 3 7 4 3 m 12 14 pi vous commencez à réduire la sensibilité de manière significative En règle générale chaque occupant doit être capable de voir clairement le détecteur Souvent l emplacement idéal d un CI 300 dans un bureau fermé est excentré Évite...

Страница 7: ...pper Relay Com N O N C Control Out Man Switch 24V Common v5 Bornes de raccordement AVERTISSEMENT COUPER LE COURANT AU DISJONCTEUR PRINCIPAL AVANT D INSTALLER LE CÂBLAGE Câblage standard avec interrupteur d arrêt local Câblage de la marche manuelle avec un interrupteur instantané basse tension Charge 1 Charge 2 en option CI 300 Boîtier arrière Borne débranchable Couvercle frontal Plafond Clips à re...

Страница 8: ... Couvercle frontal Plafond Vis Montage avec une boîte de jonction RÉGLAGE DU DÉTECTEUR L unité est préréglée pour un fonctionnement de base comme décrit dans ce guide LE RÉGLAGE EST OPTIONNEL Les détecteurs sont préréglés en usine afin de vous permettre de l installer rapidement dans la plupart des applications Pour vérifier que le câblage ou la portée sont corrects ou pour personnaliser les régla...

Страница 9: ...ité des occupants Une fois la temporisation écoulée si aucun mouvement n est détecté pendant la période de redéclenchement de 30 secondes l interrupteur manuel doit être utilisé pour remettre la charge en MARCHE Automatique MARCHE ce mode se sert des déclenchements dus à la présence ainsi que de l activation de l interrupteur pour ACTIVER la charge Un interrupteur manuel fournit les fonctionnalité...

Страница 10: ... Vérifiez que le disjoncteur de circuit a bien été réenclenché 2 Vérifiez tous les raccordements des fils du détecteur et du bloc d alimentation 3 Vérifiez que le capteur est raccordé à une tension de 24 V Si du 24 V est bien présent remplacez le détecteur Si vous ne trouvez pas de 24 V vérifiez la présence de haute tension au niveau du bloc d alimentation Si c est le cas remplacez le bloc d alime...

Страница 11: ...r los paquetes de alimentación Wattstopper de 24 V CA o CA de media onda rectificada Los sensores CI 300 también tienen un relé aislado con contactos Normalmente abierto N A y Normalmente cerrado N C para acoplarse con el sistema de calefacción ventilación y aire acondicionado HVAC o el sistema de administración de energía EMS GUÍAS PARA LA COLOCACIÓN Según los obstáculos como muebles o divisiones...

Страница 12: ...minal de 24 del sensor El cable del otro lado del interruptor a la terminal de interruptor man del sensor Cableado del relé aislado El relé aislado es apto para 1 A a 30 V CA V CC Conecte los cables necesarios para la aplicación que requiere esta salida Relé común se debe usar para el funcionamiento adecuado Normalmente abierto N A se cierra cuando se detecta una presencia Normalmente cerrado N C ...

Страница 13: ...para que los tornillos de montaje se inserten en las ranuras de los orificios tipo bocallave 6 Apriete los dos tornillos para fijar el sensor a la caja de conexiones 7 Encastre la cubierta frontal en el sensor ORMDPLHQWR WUDVHUR 7HUPLQDO GHVHQFKXIDEOH XELHUWD IURQWDO LHOR UDVR EUD DGHUDV GH UHVRUWH Montaje en techo Alojamiento trasero Terminal desenchufable Caja de conexiones octágonal de 4 al men...

Страница 14: ...rante el día cuando la luz ambiente en el área esté en el nivel deseado El nivel de luz no se puede activar mientras esté activo el modo de prueba Espere a que finalice el modo de prueba o seleccione cualquiera de las configuraciones adicionales de demora de tiempo antes de activar la función de nivel de luz El indicador LED de presencia PIR quizás aún responda cuando las luces se mantienen apagad...

Страница 15: ...omo la activación mediante interruptor para encender la carga Un interruptor manual proporciona la siguiente funcionalidad adicional 1 La carga puede encenderse con la activación del interruptor manual y permanece encendida según la configuración de lógica de presencia La demora de tiempo del sensor funciona según lo programado Cuando la carga se apaga a causa de la falta de detección de presencia...

Страница 16: ... algún tipo de interferencia consulte Activaciones no deseadas del sensor a continuación 2 Controle todas las conexiones de cables del sensor y de la fuente de alimentación 3 Desconecte el cable azul de la fuente de alimentación Si las luces no se apagan reemplace la fuente de alimentación Vuelva a conectar el cable azul Si las luces se apagan el problema puede estar en el sensor Para comprobar Vu...

Отзывы: