background image

4

LIGHT LEVEL FEATURE

The Light Level feature holds lights off upon initial occupancy if adequate ambient light exists. It will not turn the lights 

OFF

 if they are 

ON

. The default setting is for maximum, meaning that even the brightest ambient light will not hold the lights 

OFF

.

Notes on Functionality

•  Avoid mounting the sensor close to lighting fixtures.

•  Adjust during daylight hours when ambient light in the area is at desired level.

•  Light Level cannot be enabled while Test Mode is active. Either wait for Test Mode to expire or select any of the other Time Delay 

settings before enabling the Light Level feature.

•  PIR occupancy indicator LED may still respond when lights are being held 

OFF

. LED will also flash periodically to indicate the 

sensor has Light Level enabled.

•  Light Level settings are only saved in the event of a power loss. Disabling Light Level and then reenabling it will not return it to 

previous settings.

•  If Test Mode is enabled after Light Level has been set, Light Level functionality will cease to function throughout the duration of Test 

Mode. When Test Mode period expires, the Light Level functionality will resume, even if the DIP Switches remain set to Test Mode.

Setting Light Level

1.  Make sure Test Mode is not active.

2.  Toggle the state of the sensor, by briefly pressing the Light Level button, to include or exclude the lighting load from the light level 

calibration. Open the Front Cover and locate the Light Level pusbbutton. See Sensor Adjustment.

3.  Press and hold the Light Level button for 2 or more seconds, or until the detection LED turns 

ON

. Do not exceed 5 seconds.* The 

sensor enters setup mode, as indicated by the rapidly flashing LED. The LED will flash throughout the setup process. Occupancy 

indication from the LED is disabled during setup.

4.  Move away from the sensor to avoid interference with light level detection. The sensor measures the light level for a 10 second 

period, then averages the readings and automatically sets the level that will be used as the new setting. The sensor will hold lights 

off when the ambient light exceeds this setting.

5.  When the LED stops flashing, replace the Front Cover.

*Disabling Light Level

•  Pressing the pushbutton for 5 seconds or more resets the light to default (maximum).

•  Press and hold the Light Level button for 5 seconds or until the detection LED turns 

ON

 and then 

OFF

. The LED flashes rapidly for 

10 seconds after the setting has changed.

DIP SWITCH SETTING

The CI-300 has 7 DIP switches under the cover.

Time Delay: Switches 1, 2, 3

The sensor will hold the lights 

ON

 as long as occupancy is detected. The time delay countdown starts when no 

motion is detected. After no motion is detected for the length of the time delay, the sensor will turn the lights OFF.

Walk-Through Switch 4

Walk-through mode turns the lights 

OFF

 three minutes after the area is initially occupied, if no motion is detected 

after the first 30 seconds. If motion continues beyond the first 30 seconds, the selected time delay applies.

PIR Sensitivity: Switch 5

•  Minimum forces a reduced detection range for the PIR. 

•  Maximum forces the sensitivity to the maximum coverage area. This setting is constantly updated.

Service: Switch 6

To override all sensor functions, set DIP switch 6 to the 

ON

 position. The red LED will come on and stay on for 

the duration of the override.
This bypasses the light level and occupancy detection control functions of the sensor, but still allows the 

lights to be manually controlled with a light switch, low voltage switch, or Light Level button.

On Mode: Switch 7

The Manual 

ON

 function is facilitated by installing a momentary switch such as a Wattstopper LVS-1 

Momentary Toggle Switch, or RS2-3 Low Voltage Momentary Switch. This switch connects to the sensor’s 

Manual (Man.) Switch and +24V terminals as shown in the wiring diagram. Each time the switch is pressed, 

the load changes state. The sensor’s operation as related to the manually operated switch is determined by 

the setting for DIP Switch 7.

Manual ON

: In this mode, the switch is required to turn on the load. The sensor is then used to keep the 

load on, based on occupant activity. After the time delay ends, if there is no movement detected within the 

30 second re-trigger period the manual switch must be used to turn 

ON

 the load.

Automatic ON:

 This mode uses occupancy as well as switch activation to turn the load 

ON

. A manual 

switch provides the following additional functionality:

1.  The load can be turned 

ON

 by manual switch activation and it stays on as long as occupancy is detected. The sensor time delay 

operates as programmed. When the load turns 

OFF

 due to lack of occupancy detection, the load can be turned 

ON

 again by 

occupancy detection or switch activation.

2.  Activating the manual switch while the load is 

ON

 turns the load 

OFF

.

Switch#

5 minutes

10 minutes

15 minutes

20 minutes

25 minutes

30 minutes

30 seconds

1 2 3

Time Delay

Test Mode/20 min

5

 

Maximum 

PIR Sensitivity

 

Minimum 

6

 

Normal 

 

Service 

Service

7

 

Auto On 

 

Manual On 

On Mode

   = ON

     = OFF

= Factory Setting

4

Disabled 

Enabled 

Walk-Through

Содержание Wattstopper CI-300

Страница 1: ...temperatures may cause false activations Mount the sensor to the ceiling The CI 300 sensors are designed for a ceiling height of about 8 10 feet Mounting above or below this range will significantly affect the coverage patterns Be aware that as you decrease the mounting height you decrease the range and increase the sensitivity to smaller motions Conversely when you increase the height you increas...

Страница 2: ...er Class 2 Power Packs For Indoor Use Only LISTED www legrand us wattstopper Relay Com N O N C Control Out Man Switch 24V Common v5 Wiring terminals Load 1 Load 2 Optional CI 300 Rear Housing Depluggable Terminal Front Cover Ceiling Spring Clips 2 Blue Control Out 24V Common Low Voltage Class 2 Line Voltage Line Neutral Feed Through Power Pack Black Red 1 2 Line Voltage Switches Standard wiring wi...

Страница 3: ...is optional The sensors are factory preset to allow for quick installation in most applications Verification of proper wiring or coverage or customizing the sensor s settings can be done using the following procedures To make adjustments open the Front Cover by pulling on the cover tab There is a 30 second warm up period when power is first applied Before making adjustments make sure the office fu...

Страница 4: ...hanged DIP SWITCH SETTING The CI 300 has 7 DIP switches under the cover Time Delay Switches 1 2 3 The sensor will hold the lights ON as long as occupancy is detected The time delay countdown starts when no motion is detected After no motion is detected for the length of the time delay the sensor will turn the lights OFF Walk Through Switch 4 Walk through mode turns the lights OFF three minutes aft...

Страница 5: ...o not turn OFF automatically 1 The sensor technology PIR may be experiencing activations from outside the controlled area or from some type of interference see Unwanted Sensor Activations below 2 Check all sensor and power pack wire connections 3 Disconnect power pack s blue wire If the lights do not turn off replace power pack Reconnect blue wire If the lights turn off the problem may be in the s...

Страница 6: ...nts À l inverse lorsque vous augmentez la hauteur vous augmentez la portée et diminuez la sensibilité aux petits mouvements À des hauteurs supérieures à 3 7 4 3 m 12 14 pi vous commencez à réduire la sensibilité de manière significative En règle générale chaque occupant doit être capable de voir clairement le détecteur Souvent l emplacement idéal d un CI 300 dans un bureau fermé est excentré Évite...

Страница 7: ...pper Relay Com N O N C Control Out Man Switch 24V Common v5 Bornes de raccordement AVERTISSEMENT COUPER LE COURANT AU DISJONCTEUR PRINCIPAL AVANT D INSTALLER LE CÂBLAGE Câblage standard avec interrupteur d arrêt local Câblage de la marche manuelle avec un interrupteur instantané basse tension Charge 1 Charge 2 en option CI 300 Boîtier arrière Borne débranchable Couvercle frontal Plafond Clips à re...

Страница 8: ... Couvercle frontal Plafond Vis Montage avec une boîte de jonction RÉGLAGE DU DÉTECTEUR L unité est préréglée pour un fonctionnement de base comme décrit dans ce guide LE RÉGLAGE EST OPTIONNEL Les détecteurs sont préréglés en usine afin de vous permettre de l installer rapidement dans la plupart des applications Pour vérifier que le câblage ou la portée sont corrects ou pour personnaliser les régla...

Страница 9: ...ité des occupants Une fois la temporisation écoulée si aucun mouvement n est détecté pendant la période de redéclenchement de 30 secondes l interrupteur manuel doit être utilisé pour remettre la charge en MARCHE Automatique MARCHE ce mode se sert des déclenchements dus à la présence ainsi que de l activation de l interrupteur pour ACTIVER la charge Un interrupteur manuel fournit les fonctionnalité...

Страница 10: ... Vérifiez que le disjoncteur de circuit a bien été réenclenché 2 Vérifiez tous les raccordements des fils du détecteur et du bloc d alimentation 3 Vérifiez que le capteur est raccordé à une tension de 24 V Si du 24 V est bien présent remplacez le détecteur Si vous ne trouvez pas de 24 V vérifiez la présence de haute tension au niveau du bloc d alimentation Si c est le cas remplacez le bloc d alime...

Страница 11: ...r los paquetes de alimentación Wattstopper de 24 V CA o CA de media onda rectificada Los sensores CI 300 también tienen un relé aislado con contactos Normalmente abierto N A y Normalmente cerrado N C para acoplarse con el sistema de calefacción ventilación y aire acondicionado HVAC o el sistema de administración de energía EMS GUÍAS PARA LA COLOCACIÓN Según los obstáculos como muebles o divisiones...

Страница 12: ...minal de 24 del sensor El cable del otro lado del interruptor a la terminal de interruptor man del sensor Cableado del relé aislado El relé aislado es apto para 1 A a 30 V CA V CC Conecte los cables necesarios para la aplicación que requiere esta salida Relé común se debe usar para el funcionamiento adecuado Normalmente abierto N A se cierra cuando se detecta una presencia Normalmente cerrado N C ...

Страница 13: ...para que los tornillos de montaje se inserten en las ranuras de los orificios tipo bocallave 6 Apriete los dos tornillos para fijar el sensor a la caja de conexiones 7 Encastre la cubierta frontal en el sensor ORMDPLHQWR WUDVHUR 7HUPLQDO GHVHQFKXIDEOH XELHUWD IURQWDO LHOR UDVR EUD DGHUDV GH UHVRUWH Montaje en techo Alojamiento trasero Terminal desenchufable Caja de conexiones octágonal de 4 al men...

Страница 14: ...rante el día cuando la luz ambiente en el área esté en el nivel deseado El nivel de luz no se puede activar mientras esté activo el modo de prueba Espere a que finalice el modo de prueba o seleccione cualquiera de las configuraciones adicionales de demora de tiempo antes de activar la función de nivel de luz El indicador LED de presencia PIR quizás aún responda cuando las luces se mantienen apagad...

Страница 15: ...omo la activación mediante interruptor para encender la carga Un interruptor manual proporciona la siguiente funcionalidad adicional 1 La carga puede encenderse con la activación del interruptor manual y permanece encendida según la configuración de lógica de presencia La demora de tiempo del sensor funciona según lo programado Cuando la carga se apaga a causa de la falta de detección de presencia...

Страница 16: ... algún tipo de interferencia consulte Activaciones no deseadas del sensor a continuación 2 Controle todas las conexiones de cables del sensor y de la fuente de alimentación 3 Desconecte el cable azul de la fuente de alimentación Si las luces no se apagan reemplace la fuente de alimentación Vuelva a conectar el cable azul Si las luces se apagan el problema puede estar en el sensor Para comprobar Vu...

Отзывы: