3.3 LCD CONTROL PANEL
3.4 INSTALLATION NOTES
1. LED (from top to bottom: “alarm”,
“bypass”, “battery”, “inverter”)
2. LCD display
3. Scroll button
4. Off button
5. On button(battery cold start
switch)
ώ
Please place the UPS in a clean, stable environment, avoid the vibration, dust,
humidity, flammable gas and liquid, corrosive. To avoid from high room temperature, a
system of room extractor fans is recommended to be installed. Optional air filters are
available if the UPS operates in a dusty environment.
ώ
The environment temperature around UPS should keep in a range of 0
℃~
40
℃
. If
the environment temperature exceeds 40
℃
, the rated load capacity should be reduced
by 12% per 5
℃
. The max temperature can’t be higher than 50
℃
.
ώ
If the UPS is dismantled under low temperature, it might be in a condensing con-
dition. The UPS can’t be installed unless the internal and external of the equipment is
fully dry. Otherwise, there will be in danger of electric shock.
ώ
Batteries should be mounted in an environment where the temperature is within
the required specs. Temperature is a major factor in determining battery life and capa-
city. In a normal installation, the battery temperature is maintained between 15°C and
25°C. Keep batteries away from heat sources or main air ventilation area, etc.
Note: Consider for the convenience of operation and maintenance, the space in front and
back of the cabinet should be left at least 100cm and 80cm respectively when installing the
cabinet.