43
Model
10kVA(S/H)
15kVA(S/H)
20kVA(S/H)
Capacity
10KVA
15KVA
20KVA
9KW
13.5KW
18KW
OUTPUT
Phase
3 Phase 4 Wires and Ground
Rated Voltage
380/400/415Vac
Power Factor
0.9
Voltage
Regulation
±1%
Frequ-
ency
Utility
Mode
±1%, ±2%, ±4%, ±5%, ±10% of the rated
frequency(optional)
Battery
Mode
(50/60±0.2%) Hz
Crest Factor
3:1
10kVA
Power
factor
(Long
run
unit)
0.9
Battery number: 20pcs
0.8
Battery number: 18pcs
0.7
Battery number: 16pcs
THD
≤2% with linear load
≤5% with nonlinear load
BA
TTERY
Voltage
Standard unit:
±96Vdc (16pcs
12V9AH);
Long run unit :
±96V/±108V/±120V-
dc (16/18/20pcs
optional)
Standard unit: ±120Vdc (2x16pcs
12V9AH);
Long run unit Optional Volta-
ge: ±192/204/216/228/240Vdc
(32/34/36/38/40pcs optional)
Charge Cur-
rent(A)(charge
current can be
set according to
battery capacity
installed)
Standard
unit: 1.35A
Long run unit:
Max. current 6A
Standard unit: 2.7A
Transfer Time
Utility to Battery: 0ms; Utility to bypass: 0ms