31
Output voltage setting (Note: Insi-
de the broken line is the flashing
part.)
Frequency setting (Note: Inside
the broken line is the flashing
part.)
In the mode setting press “ON” or in frequency setting
press “Off”, it goes to the output voltage setting. The
output voltage line flashes as in above picture
1. Use button “
” to choose the different output volta-
ge. There are 3 different voltages---220, 230, 240.
2. Press “ON” to exit the output voltage setting and
save the output voltage setting value, and goes to
frequency setting.
3. Press “OFF” to exit the output voltage setting, and
goes to mode setting.
In the output voltage setting press “ON” or in battery
capacity setting press “OFF”, it goes to the frequency
setting. The frequency line flashes as in above picture.
1. Use button “
” to choose the different frequency.
There are 2 different frequency---50,60Hz.
2. Press ”ON” to exit the frequency setting and save
the frequency setting value and goes to battery
capacity setting.
3. Press ”OFF” to exit the frequency setting, and goes
to output voltage setting.
4.4.2 Output voltage setting
4.4.3 Frequency setting
CAUTION:
When powered by inverter, it is necessary to turn off the inverter
before setting voltage and frequency level.
CAUTION:
When powered by inverter, it is necessary to turn off the inverter
before setting voltage and frequency level.
Содержание STARK 10 kVA
Страница 51: ...51 ...
Страница 52: ...www informups com ...