Repeat the same steps to cascade more DPX3 sensor packages.
3. Connect the first DPX3 sensor package to the Legrand PDU by plugging its cable's connector into the
RJ-45 SENSOR port of the Legrand PDU.
Connecting a DPX2 Sensor Package to DPX3
You can connect only one DPX2 sensor package to the "end" of a DPX3 sensor chain. It is strongly
recommended to use an RJ-12 to RJ-45 adapter for connecting the DPX2 to the final DPX3 in the chain.
The maximum number of DPX3 sensor packages in the chain must be less than 12 when a DPX2 sensor
package is involved.
When connecting a DPX2 sensor package containing three DPX2 sensors:
A maximum of nine DPX3 sensor packages can be cascaded because 12-3=9.
When connecting a DPX2 sensor package containing two DPX2 sensors:
A maximum of ten DPX3 sensor packages can be cascaded because 12-2=10.
When connecting a DPX2 sensor package containing one DPX2 sensor:
A maximum of eleven DPX3 sensor packages can be cascaded because 12-1=11.