Ju
ne
20
18
Legrand PDU User Guide 405
Specify a match condition for identifying a line or one Legrand PDU device in the device configuration file
"devices.csv."
The option's value comprises one word and one number as explained below:
The word prior to the colon is an identification property, which is either
serial
for serial number or
mac
for MAC address.
The number following the colon indicates a column in the
devices.csv
file.
For example,
mac:7
instructs the Legrand PDU to search for the MAC address in the 7th column of the
"devices.csv" file.
The default value is
serial:1
, making the Legrand PDU search for its serial number in the first column.
This option is used only if the "device_list" option has been set.
factory_reset
If this option is set to
true
, the Legrand PDU will be reset to factory defaults.
If the device configuration will be updated at the same time, the factory reset will be executed before
updating the device configuration.
bulk_config_restore
Specify the name of the bulk configuration file used to configure or restore the Legrand PDU.
Note: See
Bulk Configuration
(on page 239) for instructions on generating a bulk configuration file.
Additional configuration keys set via the
config.txt
file will be applied after performing the bulk restore
operation.
This option CANNOT be used with the option "full_config_restore."
If a firmware upgrade will be performed at the same time, you must generate the bulk configuration file
based on the NEW firmware version instead of the current firmware version.
full_config_restore
Specify the name of the full configuration backup file used to restore the Legrand PDU.
Note: See
Backup and Restore of Device Settings
(on page 243) for instructions on generating the full
configuration backup file.
Additional configuration keys set via the
config.txt
file will be applied after performing the configuration
restore operation.
This option CANNOT be used with the option "bulk_config_restore."
If a firmware upgrade will be performed at the same time, you must generate the full configuration
backup file based on the NEW firmware version instead of the current firmware version.
collect_diag
If this option is set to
true
, the diagnostic data of the Legrand PDU is transmitted to the USB drive.
The filename of the diagnostic data written into the USB drive is:
diag_<unit-serial>.zip
switch_outlets
This feature works on outlet-switching capable models only.
Switch on or off specific outlets.
The option's value comprises outlet numbers and the setting "on" or "off" as explained below:
Each "on" or "off" setting consists of three parts: outlet numbers, a colon, and the word "on" or "off".
Each "on" or "off" setting is separated with a semicolon.
If all outlets will share the same "on" or "off" setting, replace the outlet numbers with the word "all".
Examples:
Turn on outlets 1 to 3, and 10, and turn off outlets 4 to 9.