Technical data sheet: S000082102EN-1 

Updated: 08/10/2013 

Created: 08/10/2013

Cat. No(s): 0 625 14/24/54/64/74

Kickspot Self-testing/AutoDiag

self-contained emergency lighting unit 

4. USE

n

 4.1 Switch-on/Standby state

The white emergency LED(s) come on at low intensity and the green unit 

status LED comes on.

Note: The green self-test indicator flashes for the first 28 hours.

n

 4.2 Mains supply break/Emergency operation

0  625  14/24/54/74: The  green  unit  status  LED  goes  off  and  the  white 

emergency LEDs come on at higher intensity.

0  625  64: The  white  LED  and  the  green  unit  status  LED  go  off  and  all 

 

4 emergency LEDs come on.

n

 4.3 Setting to rest state via the remote control 

Cat. Nos. 0 039 00/01

After the normal lighting is switched off intentionally:

Pressing the 

 

button sets the unit to rest state to prevent the battery 

discharging.

Normal lighting switched back on:

The unit automatically returns to standby.

n

 4.4 Automatic checking of the unit status (self-testing system)

This unit automatically checks its operating status.

Once a week:

Switches to emergency state and tests for 15 s, and tests switch-on and 

the light sources.

Once every three months:

Switches to emergency state for one hour and tests the battery standby 

power. Tests the light sources and the duration of the standby battery 

power.

n

 4.5 Result of the automatic checks

LEDs

Unit  

OK

Battery  

fault

Electronic  

fault

Green

(steady or 

flashing)

Yellow

(steady)

(rapid flashing)

The time of the tests is set at the time the unit is first switched on. The 

day of the test is chosen randomly in order to ensure that a minimum 

number of units are tested at the same time.

The time at which all the units are tested can be changed to the required 

time by simultaneously pressing the 

 

and 

 

buttons on the remote 

control.

This change of test time triggers a standby power test immediately or 

within 24 hours.

n

 4.6 Stopping a test in progress

If a standby power test hinders operation, it can be stopped immediately. 

Press the OFF button on the remote control unit Cat. No. 0 039 00. The 

test is stopped and postponed until the following day.

n

 4.7 Special cases

When the unit has been switched off for more than 3 days, the tests are 

no longer carried out. The test cycle will resume after the unit is switched 

back on and the batteries have been recharged. The tests planned for 

the day the unit is switched back on are automatically postponed for 24 

hours.

n

  4.8  Operation  of  self-contained  emergency  lighting  +  home 

lighting unit Cat. No. 0 625 14 with a remote control module Cat. No. 

0 039 00 connected to a fire alarm control panel

Mains power 

supply

Fire alarm

Unit status

Emergency 

function

Home 

function

Present

Absent

Standby

Standby

Absent

Absent

Backup

Backup

Rest

Backup

Absent

Present

Backup

Backup

Present

Present or 

absent

Standby

Standby

Lighting

unit standby

and emergency

LEDs

Unit green

status LED

Home

lighting unit

emergency

LEDs

Yellow

fault LED

4 s

Содержание 0 625 14

Страница 1: ...ng Self contained emergency lighting unit with LEDs used for evacuation in public buildings and work premises Cat Nos 0 625 14 24 54 74 or for background lighting Cat No 0 625 64 Conforming to standards 0 625 24 conforming to NF C 71 800 0 625 64 conforming to NF C 71 800 NF C 71 801 and UTE C 71 806 0 625 74 conforming to NF C 71 805 0 625 14 conforming to NF C 71 800 NF C 71 805 and UTE C 71 803...

Страница 2: ... the support Ring Polycarbonate self extinguishing 850 C 30 s Self contained emergency lighting unit Polycarbonate self extinguishing 850 C 30 s Protective cover Polycarbonate self extinguishing 850 C 30 s Terminal block Polyamide self extinguishing 850 C 30 s Tab Polyamide 850 C 30 s Pads Polyamide 850 C 30 s Pictogram holder plate Polycarbonate self extinguishing 850 C 30 s only for self contain...

Страница 3: ...it in the support Fully push in the tabs Swivel the unit only for evacuation lighting units Cat Nos 0 625 14 24 54 74 2 2 Connecting the wires to the terminal block REMOTE CONTROL Connection terminals no direction of connection with Legrand remote controls Terminal capacity 2 x 2 5 mm2 Insert the tabs in the unit Connect the terminal block to the unit N L 50 mm 10 Power supply Remote control CLICK...

Страница 4: ...unit 2 Lock with a 1 4 turn 1 2 3 1 Connecting the mains power to the self contained units Art EC 12 3 of the safety regulations The branch supplying a unit must be joined upstream of the protection device and downstream of the normal lighting control device for the room or exit route where the unit is installed The polarity of the remote control may not be followed on this lighting unit if a Legr...

Страница 5: ...maximum Important In the event of fire alarm activation remote control Cat No 0 039 00 memorises the alarm status for one hour to avoid accidentally setting the unit emergency lighting function to rest state emergency lighting units home lighting units emergency lighting units reinforced emergency lights if the main power supply fails again The red LED signals the fire alarm status If the fire ala...

Страница 6: ...766 30 or Céliane Cat No 0 675 31 not supplied Optional remote control via keyswitch Mosaic Cat No 0 766 30 or Céliane Cat No 0 675 31 not supplied Keyswitch Mosaic Cat No 0 766 30 or Céliane Cat No 0 675 31 not supplied Keyswitches cascaded Mosaic Cat No 0 766 30 or Céliane Cat No 0 675 31 not supplied Optional remote control via keyswitch Mosaic Cat No 0 766 30 or Céliane Cat No 0 675 31 not sup...

Страница 7: ...self testing display with LEDs AutoDiagTM self testing remote control Background lighting unit Background lighting unit Emergency lighting home lighting unit Reinforced emergency light Lighting power supply circuit The remote control power supply must be taken upstream of the normal lighting circuit protection devices It must not come from a protected auxiliary power supply 0 0 9 3 0 0 230 VA 50Hz...

Страница 8: ...ery fault Electronic fault Green steady or flashing Yellow steady rapid flashing The time of the tests is set at the time the unit is first switched on The day of the test is chosen randomly in order to ensure that a minimum number of units are tested at the same time The time at which all the units are tested can be changed to the required time by simultaneously pressing the and buttons on the re...

Страница 9: ...No 0 039 00 and keyswitch in accordance with wiring diagram 3 2 enables the units to be set to rest state at the same time as the normal lighting is switched off when the rooms or areas are not in use The user must regularly check the following Once a month That the unit switches to operating position if the normal power supply fails and that all the lights come on operation must be strictly limit...

Страница 10: ...25 14 2 x 0 610 87 0 625 54 0 610 90 Ni Cd 1 5 Ah 2 4 V Cs 0 625 64 2 x 0 610 88 NiMH 2 2 Ah 2 4 V Cs 3 Disconnect the batteries from the unit and remove them Legrand distribution partners take back used lighting units and batteries When the batteries have been changed replace the maintenance label marking on it the date on which the unit was returned to service n 5 2 spare parts Batteries n 5 3 R...

Страница 11: ... of NiMh batteries in self contained emergency lighting units EN 60 598 2 22 European standard Luminaires specific rules Luminaires for emergency lighting EN 60 598 1 European standard Luminaires The NF AEAS performance SATI mark certifies compliance with these standards NF 413 NF ENVIRONNEMENT Emergency lighting units The NF environnement mark certifies compliance with this standard EN 50172 Euro...

Отзывы: