Technical data sheet: S000082102EN-1 

Updated: 08/10/2013 

Created: 08/10/2013

Cat. No(s): 0 625 14/24/54/64/74

Kickspot Self-testing/AutoDiag

self-contained emergency lighting unit 

6. COMPLIANCE AND APPROVALS

NF C 71 800: French standard "Performance of self-contained emergency evacuation lighting units in public buildings and work premises covered by 

regulations"

Compliance with this standard is mandatory for installing self-contained emergency evacuation lighting units in France.

NF C 71 820: French standard "Automatic test system for emergency lighting equipment"

NF C 71 801: French standard "Performance of self-contained emergency background lighting units"

NF C 71 805: French standard "Performance of self-contained emergency home lighting units"

UTE C 71 803: Practical guide "Self-contained emergency home lighting unit for sleeping accommodation"

UTE C 71 806: Rules applicable to the use of NiMh batteries in self-contained emergency lighting units 

EN 60 598-2-22: European standard "Luminaires: specific rules. Luminaires for emergency lighting"

EN 60 598-1: European standard "Luminaires"

The "NF AEAS performance SATI" mark certifies compliance with these standards.

NF 413 NF ENVIRONNEMENT Emergency lighting units The "NF environnement" mark certifies compliance with this standard.

EN 50172: European standard "Emergency escape lighting systems"

EN 1838: European standard "Lighting applications – Emergency lighting"

Electromagnetic effects: EMC

EN 61547: European standard "EMC immunity requirements"

Emission

- EN 55015 (limits and methods of measurement of electrical lighting and similar equipment)

- EN 55022 (radiated interference) class B

Immunity

-  EN 61000-4-2 (electrostatic discharges) criterion B 4 kV (contact), 8 kV (air)

-  EN 61000-4-3 (electromagnetic fields) criterion A 10 V/m

-  EN 61000-4-4 (fast transients) criterion B 4 kV on network and 1 kV by coupling

-  EN 61000-4-5 (shock waves) 2 kV in common mode and 1 kV in residual current mode criterion B

-  EN 61000-4-6 (injected currents immunity) criterion A

Содержание 0 625 14

Страница 1: ...ng Self contained emergency lighting unit with LEDs used for evacuation in public buildings and work premises Cat Nos 0 625 14 24 54 74 or for background lighting Cat No 0 625 64 Conforming to standards 0 625 24 conforming to NF C 71 800 0 625 64 conforming to NF C 71 800 NF C 71 801 and UTE C 71 806 0 625 74 conforming to NF C 71 805 0 625 14 conforming to NF C 71 800 NF C 71 805 and UTE C 71 803...

Страница 2: ... the support Ring Polycarbonate self extinguishing 850 C 30 s Self contained emergency lighting unit Polycarbonate self extinguishing 850 C 30 s Protective cover Polycarbonate self extinguishing 850 C 30 s Terminal block Polyamide self extinguishing 850 C 30 s Tab Polyamide 850 C 30 s Pads Polyamide 850 C 30 s Pictogram holder plate Polycarbonate self extinguishing 850 C 30 s only for self contain...

Страница 3: ...it in the support Fully push in the tabs Swivel the unit only for evacuation lighting units Cat Nos 0 625 14 24 54 74 2 2 Connecting the wires to the terminal block REMOTE CONTROL Connection terminals no direction of connection with Legrand remote controls Terminal capacity 2 x 2 5 mm2 Insert the tabs in the unit Connect the terminal block to the unit N L 50 mm 10 Power supply Remote control CLICK...

Страница 4: ...unit 2 Lock with a 1 4 turn 1 2 3 1 Connecting the mains power to the self contained units Art EC 12 3 of the safety regulations The branch supplying a unit must be joined upstream of the protection device and downstream of the normal lighting control device for the room or exit route where the unit is installed The polarity of the remote control may not be followed on this lighting unit if a Legr...

Страница 5: ...maximum Important In the event of fire alarm activation remote control Cat No 0 039 00 memorises the alarm status for one hour to avoid accidentally setting the unit emergency lighting function to rest state emergency lighting units home lighting units emergency lighting units reinforced emergency lights if the main power supply fails again The red LED signals the fire alarm status If the fire ala...

Страница 6: ...766 30 or Céliane Cat No 0 675 31 not supplied Optional remote control via keyswitch Mosaic Cat No 0 766 30 or Céliane Cat No 0 675 31 not supplied Keyswitch Mosaic Cat No 0 766 30 or Céliane Cat No 0 675 31 not supplied Keyswitches cascaded Mosaic Cat No 0 766 30 or Céliane Cat No 0 675 31 not supplied Optional remote control via keyswitch Mosaic Cat No 0 766 30 or Céliane Cat No 0 675 31 not sup...

Страница 7: ...self testing display with LEDs AutoDiagTM self testing remote control Background lighting unit Background lighting unit Emergency lighting home lighting unit Reinforced emergency light Lighting power supply circuit The remote control power supply must be taken upstream of the normal lighting circuit protection devices It must not come from a protected auxiliary power supply 0 0 9 3 0 0 230 VA 50Hz...

Страница 8: ...ery fault Electronic fault Green steady or flashing Yellow steady rapid flashing The time of the tests is set at the time the unit is first switched on The day of the test is chosen randomly in order to ensure that a minimum number of units are tested at the same time The time at which all the units are tested can be changed to the required time by simultaneously pressing the and buttons on the re...

Страница 9: ...No 0 039 00 and keyswitch in accordance with wiring diagram 3 2 enables the units to be set to rest state at the same time as the normal lighting is switched off when the rooms or areas are not in use The user must regularly check the following Once a month That the unit switches to operating position if the normal power supply fails and that all the lights come on operation must be strictly limit...

Страница 10: ...25 14 2 x 0 610 87 0 625 54 0 610 90 Ni Cd 1 5 Ah 2 4 V Cs 0 625 64 2 x 0 610 88 NiMH 2 2 Ah 2 4 V Cs 3 Disconnect the batteries from the unit and remove them Legrand distribution partners take back used lighting units and batteries When the batteries have been changed replace the maintenance label marking on it the date on which the unit was returned to service n 5 2 spare parts Batteries n 5 3 R...

Страница 11: ... of NiMh batteries in self contained emergency lighting units EN 60 598 2 22 European standard Luminaires specific rules Luminaires for emergency lighting EN 60 598 1 European standard Luminaires The NF AEAS performance SATI mark certifies compliance with these standards NF 413 NF ENVIRONNEMENT Emergency lighting units The NF environnement mark certifies compliance with this standard EN 50172 Euro...

Отзывы: