PIR presence detector for high bay applications - ON/OFF
Technical data sheet: S000105276EN-2
Updated: 03/02/2021
Created: 27/11/2018
Cat. No(s): 0 489 59
CONTENTS
CONTENTS
F
7. SETTINGS (CONTINUED)
Parameter
Default
value
Value after
initialisation Range/option
Description
Manual control modes
Manual control
mode
-
-
Shared
2-position
push-button
A single centre-biased retractive switch will be used to control both channels at
the same time.
-
-
Separate
2-position
push-button
-
✔
-
Synchronised
1-position
push-button
A single push-button controls both channels at the same time.
-
-
Separate
1-position
push-button
-
8. TROUBLESHOOTING
1. If the load does not switch on
- Check that the live supply to the circuit is correct.
- Check that the load is functioning by bypassing the detector (link terminals L and L/Out).
- If the detection range is smaller than expected, see the Performance section. Rotating the sensor slightly may improve the detection range.
2. If the load does not switch off
− Ensure that the area is left unoccupied for longer than the timeout period.
− Ensure that the detector is not affected by circulating air, heaters or lamps.
3. In the event of “false tripping”, reduce the sensitivity settings.
4. If the lighting loads never switch off
• Reduce and adjust the value of the “Lux Off level” parameter and the “Lux On level” parameter in steps of 5 to 40.
Example:
- Lux On level = 190
- Lux Off level = 380
5. If the lighting loads never switch on
• Increase and adjust the value of the “Lux Off level” parameter and the “Lux On level” parameter in steps of 5 to 40.
Example:
- Lux On level = 220
- Lux Off level = 420
6. If the lighting loads switch on and off permanently
• Increase the difference between the value of the “Lux Off level” parameter and the “Lux On level” parameter.
Example:
- Lux On level = 190
- Lux Off level = 410